Factors that influence transformer no-load current harmonics
Authors:
- 1 January 2000
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 15 (1) , 163-166
Abstract
The harmonic components of the no-load current are influenced by many factors. These factors are the flux density, the degree of saturation and the core stacking technique. This paper tested many transformers for the no-load current and its harmonic components. A slight over-excitation results in a substantial increase of the THD level. The increase in the THD is not linear with the flux density. Also this work has demonstrated that having a lower no-load current should not be an indication of lower harmonics. The simulation of the transformer through the use of nonlinear inductors and resistors provided reasonable accuracy.Keywords
This publication has 6 references indexed in Scilit:
- Influence of air gaps in stacked transformer cores consisting of several packagesIEEE Transactions on Magnetics, 1994
- Harmonics generated from a DC biased transformerIEEE Transactions on Power Delivery, 1993
- Improvement of transformer core magnetic properties using the step-lap designJournal of Magnetism and Magnetic Materials, 1992
- Distribution transformer excitation harmonicsElectric Power Systems Research, 1989
- Harmonics from Transformer SaturationIEEE Transactions on Power Delivery, 1986
- Magnetic performance of step-lap joints in distribution transformer coresIEEE Transactions on Magnetics, 1982