Direct Grid Current Control of LCL-Filtered Grid-Connected Inverter Mitigating Grid Voltage Disturbance

Authors:

Abstract
A direct grid current control strategy for LCL-filtered grid-connected inverters is proposed in this paper. The conventional current control strategies are analyzed and compared, and then the necessity of direct grid current control is presented to mitigate the grid voltage disturbance. In the proposed control strategy, the virtual resistance based on the capacitance current is used to realize active damping, zero compensation is brought in to enhance the stability, and the proportional resonant (PR) controller under two-phase static coordinate is designed to track the ac reference current as well as to avoid the strong coupling brought by the coordinate transformation. Under the distortion grid voltage, the PR plus harmonic compensator (PR+HC) structure is adopted to restrain the distortion of the grid current. Finally, the proposed control strategy is verified by the experimental results.

This publication has 17 references indexed in Scilit: