Saeed AsghariGovar
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Previous Organizations / Institutes
The organizations / institutes from the scholar's other articles in the past ten years
Saeed AsghariGovar has a total of 9 co-authors. Here are the top co-authors by number of shared publications:
Heresh Seyedi
Univ Tabriz, Fac Elect & Comp Engn, Tabriz, Iran
4 shared publications- Heresh Seyedi
Faculty of Electrical and Computer Engineering University of Tabriz Tabriz Iran
3 shared publications - Pouya Pourghasem
University of Tabriz
3 shared publications Omer Usta
1 shared publication- Omer Usta
Istanbul Technical University
1 shared publication Saeid Ghasemzadeh
Faculty of Electrical and Computer Engineering University of Tabriz Tabriz Iran
1 shared publication
Latest Publications
- 23 September 2021
- Published by The Scientific and Technological Research Council of Turkey (TUBITAK-ULAKBIM) - DIGITAL COMMONS JOURNALS in Turkish Journal of Electrical Engineering and Computer Sciences
- Vol. 29 (5) , 2403-2415
Performance evaluation of HHT and WT for detection of HIF and CT saturation in smart grids
- 23 September 2021
- Published by The Scientific and Technological Research Council of Turkey (TUBITAK-ULAKBIM) - DIGITAL COMMONS JOURNALS in Turkish Journal of Electrical Engineering and Computer Sciences
- Vol. 29 (5) , 2403-2415
Performance evaluation of HHT and WT for detection of HIF and CT saturation in smart grids
- 11 November 2019
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 35 (4) , 1749-1757
A Novel Transfer Matrix-Based Approach for Pilot Protection of Hybrid Transmission Lines Considering HIF Location
Distance protection encounters some problems such as time coordination, protection of short lines, capacitive charging current and high impedance faults. Its shortcomings are extended in the case of protection of hybrid transmission lines, including overhead line and underground cable. To cope with the mentioned problems, in this paper, a novel approach is proposed for pilot protection of hybrid transmission lines. The proposed approach utilizes three phase voltage and current signals of both ends and transfer matrix of the hybrid line. Indeed, voltage and current angles of specific points on the line are calculated from both ends and the absolute values of the differences between the results obtained from the sending and receiving ends are computed for each point to detect the fault and identify its exact location and phase. The achieved results confirm the security, dependability, and efficiency of the algorithm in critical conditions of power system, i.e. high impedance fault occurrence, power swing, different strengths of equivalent sources at both ends, loss of time synchronization of remote end data, and different fault locations with various inception angles. Although the proposed method is very simple, its performance is surprisingly satisfactory and it is suitable for practical implementation in real-life applications.
- 11 November 2019
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 35 (4) , 1749-1757
A Novel Transfer Matrix-Based Approach for Pilot Protection of Hybrid Transmission Lines Considering HIF Location
Distance protection encounters some problems such as time coordination, protection of short lines, capacitive charging current and high impedance faults. Its shortcomings are extended in the case of protection of hybrid transmission lines, including overhead line and underground cable. To cope with the mentioned problems, in this paper, a novel approach is proposed for pilot protection of hybrid transmission lines. The proposed approach utilizes three phase voltage and current signals of both ends and transfer matrix of the hybrid line. Indeed, voltage and current angles of specific points on the line are calculated from both ends and the absolute values of the differences between the results obtained from the sending and receiving ends are computed for each point to detect the fault and identify its exact location and phase. The achieved results confirm the security, dependability, and efficiency of the algorithm in critical conditions of power system, i.e. high impedance fault occurrence, power swing, different strengths of equivalent sources at both ends, loss of time synchronization of remote end data, and different fault locations with various inception angles. Although the proposed method is very simple, its performance is surprisingly satisfactory and it is suitable for practical implementation in real-life applications.
- 27 July 2018
- Published by The Scientific and Technological Research Council of Turkey (TUBITAK-ULAKBIM) - DIGITAL COMMONS JOURNALS in Turkish Journal of Electrical Engineering and Computer Sciences
- Vol. 26 (4) , 2056-2065
Optimal coordination of overcurrent protection in the presence of SFCL and distributed generation
- 27 July 2018
- Published by The Scientific and Technological Research Council of Turkey (TUBITAK-ULAKBIM) - DIGITAL COMMONS JOURNALS in Turkish Journal of Electrical Engineering and Computer Sciences
- Vol. 26 (4) , 2056-2065
Optimal coordination of overcurrent protection in the presence of SFCL and distributed generation
- Open Access
- 31 January 2018
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 12 (6) , 1366-1373
Adaptive CWT‐based overcurrent protection for smart distribution grids considering CT saturation and high‐impedance fault
In this study, an adaptive continuous wavelet transform (CWT)‐based overcurrent protection for smart grids is proposed to enhance the overcurrent protection performance encountering high‐impedance fault (HIF) and current transformer (CT) saturation, which are extremely complex phenomena and their impacts often cause mis‐coordination or mal‐operation. The proposed algorithm samples three phase current waveforms and imports them to CWT to extract high frequency coefficients. Afterwards, the sum of absolute values of the coefficients, S coef , is calculated for each sample during the last cycle. Meanwhile, several simulations related to HIFs with different impedances and CT saturations with different severities are executed and the fault currents and the sum of absolute values of the coefficients are achieved and saved in the relay memory as ( X , Y ) coordinates of points ( I L‐ fault , S L‐ coef ), named ‘learning data’. Thereafter, each S coef is imported to the X − Y plane and, consequently, the occurrence of HIF or CT saturation is detected and the real‐fault current is estimated by both non‐linear interpolation and extreme learning machine approaches. Subsequently, new time dial setting and I pickup of the relays are computed and reloaded. Security, dependability, and sensitivity of the proposed adaptive protection method are confirmed by numerous simulation studies.
- 31 January 2018
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 12 (6) , 1366-1373
Open AccessAdaptive CWT‐based overcurrent protection for smart distribution grids considering CT saturation and high‐impedance fault
In this study, an adaptive continuous wavelet transform (CWT)‐based overcurrent protection for smart grids is proposed to enhance the overcurrent protection performance encountering high‐impedance fault (HIF) and current transformer (CT) saturation, which are extremely complex phenomena and their impacts often cause mis‐coordination or mal‐operation. The proposed algorithm samples three phase current waveforms and imports them to CWT to extract high frequency coefficients. Afterwards, the sum of absolute values of the coefficients, S coef , is calculated for each sample during the last cycle. Meanwhile, several simulations related to HIFs with different impedances and CT saturations with different severities are executed and the fault currents and the sum of absolute values of the coefficients are achieved and saved in the relay memory as ( X , Y ) coordinates of points ( I L‐ fault , S L‐ coef ), named ‘learning data’. Thereafter, each S coef is imported to the X − Y plane and, consequently, the occurrence of HIF or CT saturation is detected and the real‐fault current is estimated by both non‐linear interpolation and extreme learning machine approaches. Subsequently, new time dial setting and I pickup of the relays are computed and reloaded. Security, dependability, and sensitivity of the proposed adaptive protection method are confirmed by numerous simulation studies.
- 1 January 2017
- Published by The Scientific and Technological Research Council of Turkey (TUBITAK-ULAKBIM) - DIGITAL COMMONS JOURNALS in Turkish Journal of Electrical Engineering and Computer Sciences
- Vol. 25 (4) , 2846-2859
Development of PMU-based backup wide area protection for power systems considering HIF detection
- 1 January 2017
- Published by The Scientific and Technological Research Council of Turkey (TUBITAK-ULAKBIM) - DIGITAL COMMONS JOURNALS in Turkish Journal of Electrical Engineering and Computer Sciences
- Vol. 25 (4) , 2846-2859
Development of PMU-based backup wide area protection for power systems considering HIF detection
- Open Access
- 1 June 2016
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 10 (9) , 2035-2041
Adaptive CWT‐based transmission line differential protection scheme considering cross‐country faults and CT saturation
In this study a new adaptive continuous wavelet transform (CWT)‐based current differential protection scheme is proposed to cope with problems of conventional current differential protection in transmission lines. Current transformer (CT) saturation is a major problem for protection engineers in current differential protection systems. The mentioned problem is highlighted when an external fault occurs and causes mal‐operation of differential protection. In this study, three phase currents at both ends of transmission line have been sampled and used as input signals to the proposed method using appropriate communication link. In addition, CWT with the aid of Mexican hat as a mother wavelet has been employed to extract high‐frequency information of signals and detect fault occurrence and CT saturation in each phase. As a result, the proposed technique is able to prevent unwanted trip due to CT saturation during external faults. Nevertheless, simulation results confirm sensitivity and security of the proposed protection technique in facing with second internal fault of cross‐country faults after a short delay.
- 1 June 2016
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 10 (9) , 2035-2041
Open AccessAdaptive CWT‐based transmission line differential protection scheme considering cross‐country faults and CT saturation
In this study a new adaptive continuous wavelet transform (CWT)‐based current differential protection scheme is proposed to cope with problems of conventional current differential protection in transmission lines. Current transformer (CT) saturation is a major problem for protection engineers in current differential protection systems. The mentioned problem is highlighted when an external fault occurs and causes mal‐operation of differential protection. In this study, three phase currents at both ends of transmission line have been sampled and used as input signals to the proposed method using appropriate communication link. In addition, CWT with the aid of Mexican hat as a mother wavelet has been employed to extract high‐frequency information of signals and detect fault occurrence and CT saturation in each phase. As a result, the proposed technique is able to prevent unwanted trip due to CT saturation during external faults. Nevertheless, simulation results confirm sensitivity and security of the proposed protection technique in facing with second internal fault of cross‐country faults after a short delay.