Yaxun Guo
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Yaxun Guo has a total of 17 co-authors. Here are the top co-authors by number of shared publications:
- Gang Liu
School of Electric Power Engineering, South China University of Technology, Guangzhou 510640, China
2 shared publications - Ming Zheng
China Energy Engineering Group Guangdong Electric Power Design Institute Co., Ltd., Guangzhou 510663, China
2 shared publications - Wenhu Tang
School of Electric Power Engineering, South China University of Technology, Guangzhou 510641, China
2 shared publications - Xiaofeng Jiang
Jieyang Power Supply Bureau of Guangdong Power Grid Co., Ltd., Jieyang 522000, China
2 shared publications - Xiaohua Li
School of Electric Power Engineering, South China University of Technology, Guangzhou 510643, China
2 shared publications Yulin Wang
South China University of Technology, Guangzhou, China
2 shared publications
Latest Publications
- 19 April 2023
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Systems
- Vol. 39 (1) , 2093-2105
A Hierarchical Identification Method of Commutation Failure Risk Areas in Multi-Infeed LCC-HVDC Systems
In the multi-infeed LCC-HVDC system, the concurrent commutation failure (CCF) caused by the AC fault of the receiving-end system may lead to the blocking of multiple converter stations, which challenges power grid security and stability. This paper proposes a novel method to quickly and accurately identify the CF risk areas, considering the CF probability (CFP) during the single-line-to-ground (SLG) fault. First, an AC-DC voltage asymmetry factor (ADVAF) and its theoretical derivation are proposed to quantify the influence of the fault position on the CF. Second, the critical ADVAF (CADVAF) is derived based on the equivalent method. By comparing ADVAF and CADVAF, the CF risk areas can be quickly divided into non-, possible- and inevitable-concurrent CF risk areas. Third, the relationship between local CFP (LCFP) and fault position is established, and the concurrent CFP (CCFP) is calculated. The proposed method has improved the accuracy and computational efficiency of theoretical analysis than earlier methods. Finally, the validity and accuracy of the proposed method are verified in dual-infeed and five-infeed LCC-HVDC systems built based on the IEEE 39-bus and IEEE 118-bus models, respectively.
- 19 April 2023
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Systems
- Vol. 39 (1) , 2093-2105
A Hierarchical Identification Method of Commutation Failure Risk Areas in Multi-Infeed LCC-HVDC Systems
In the multi-infeed LCC-HVDC system, the concurrent commutation failure (CCF) caused by the AC fault of the receiving-end system may lead to the blocking of multiple converter stations, which challenges power grid security and stability. This paper proposes a novel method to quickly and accurately identify the CF risk areas, considering the CF probability (CFP) during the single-line-to-ground (SLG) fault. First, an AC-DC voltage asymmetry factor (ADVAF) and its theoretical derivation are proposed to quantify the influence of the fault position on the CF. Second, the critical ADVAF (CADVAF) is derived based on the equivalent method. By comparing ADVAF and CADVAF, the CF risk areas can be quickly divided into non-, possible- and inevitable-concurrent CF risk areas. Third, the relationship between local CFP (LCFP) and fault position is established, and the concurrent CFP (CCFP) is calculated. The proposed method has improved the accuracy and computational efficiency of theoretical analysis than earlier methods. Finally, the validity and accuracy of the proposed method are verified in dual-infeed and five-infeed LCC-HVDC systems built based on the IEEE 39-bus and IEEE 118-bus models, respectively.
- Open Access
- 1 October 2022
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 16 (22) , 4505-4519
Fast and accurate evaluation method of commutation failure in line‐commutated converter‐based high‐voltage direct current systems considering probability characteristics
Line‐commutated converter‐based high‐voltage direct current (LCC‐HVDC) systems suffer from commutation failure (CF) when receiving‐end AC grid faults occur, which is a major drawback and threatens the security and stability of power systems. This paper presents a fast and accurate evaluation method of CF for the LCC‐HVDC systems, considering the CF probability characteristics. Firstly, based on the analysis of the CF probability characteristics from the view of short‐circuit impedance, the CF tolerance index (CFTI) and CF vulnerability index (CFVI) are proposed to quantitatively evaluate the LCC‐HVDC systems' risk of the possible‐ and inevitable‐occurrence CF, respectively. Secondly, four factors, that is, commutation voltage, fault occurrence time, DC current and firing angle command, are considered to calculate CF evaluation indices (CFEIs) and identify the CF risk area boundaries based on the theoretical analysis. Moreover, the relationships among short‐circuit impedance, fault position, and extinction angle are established based on the AC/DC decoupling method, which helps realize the decoupling of multi‐factors affecting CF during fault. Compared to earlier methods, this evaluation method combines the advantages of the accuracy of the electromagnetic transient simulation method and the rapidity of theoretical derivation. Finally, the validity and accuracy of the evaluation method are verified in the CIGRE HVDC benchmark model and IEEE 39‐bus system.
- 1 October 2022
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 16 (22) , 4505-4519
Open AccessFast and accurate evaluation method of commutation failure in line‐commutated converter‐based high‐voltage direct current systems considering probability characteristics
Line‐commutated converter‐based high‐voltage direct current (LCC‐HVDC) systems suffer from commutation failure (CF) when receiving‐end AC grid faults occur, which is a major drawback and threatens the security and stability of power systems. This paper presents a fast and accurate evaluation method of CF for the LCC‐HVDC systems, considering the CF probability characteristics. Firstly, based on the analysis of the CF probability characteristics from the view of short‐circuit impedance, the CF tolerance index (CFTI) and CF vulnerability index (CFVI) are proposed to quantitatively evaluate the LCC‐HVDC systems' risk of the possible‐ and inevitable‐occurrence CF, respectively. Secondly, four factors, that is, commutation voltage, fault occurrence time, DC current and firing angle command, are considered to calculate CF evaluation indices (CFEIs) and identify the CF risk area boundaries based on the theoretical analysis. Moreover, the relationships among short‐circuit impedance, fault position, and extinction angle are established based on the AC/DC decoupling method, which helps realize the decoupling of multi‐factors affecting CF during fault. Compared to earlier methods, this evaluation method combines the advantages of the accuracy of the electromagnetic transient simulation method and the rapidity of theoretical derivation. Finally, the validity and accuracy of the evaluation method are verified in the CIGRE HVDC benchmark model and IEEE 39‐bus system.
- Open Access
- 13 November 2019
- Published by MDPI AG in Journal of Marine Science and Engineering
- Vol. 7 (11) , 415
Study on Transient Overvoltage of Offshore Wind Farm Considering Different Electrical Characteristics of Vacuum Circuit Breaker
For the study of transient overvoltage (TOV) in an offshore wind farm (OWF) collector system caused by switching off vacuum circuit breakers (VCBs), a simplified experimental platform of OWF medium-voltage (MV) cable collector system was established in this paper to conduct switching operation tests of VCB and obtain the characteristic parameters for VCB, especially dielectric strength parameters; also, the effectiveness of the VCB reignition model was verified. Then, PSCAD/EMTDC was used to construct the MV collector system of the OWF, and the effects of normal switching and fault switching on TOV amplitude, steepness, and the total number of reignition of the VCB were studied, respectively, with the experimental parameters and traditional parameters of dielectric strength of the VCB. The simulation results show that when the VCB is at the tower bottom, the overvoltage amplitude generated by the normal switching is the largest, which is 1.83 p.u., and the overvoltage steepness of the fault switching is the largest, up to 142 kV/μs. The overvoltage amplitude and steepness caused by switching off VCB at the tower bottom faultily with traditional parameters are about 2 and 1.5 times of the experimental parameters under the same operating condition.
- 13 November 2019
- Published by MDPI AG in Journal of Marine Science and Engineering
- Vol. 7 (11) , 415
Open AccessStudy on Transient Overvoltage of Offshore Wind Farm Considering Different Electrical Characteristics of Vacuum Circuit Breaker
For the study of transient overvoltage (TOV) in an offshore wind farm (OWF) collector system caused by switching off vacuum circuit breakers (VCBs), a simplified experimental platform of OWF medium-voltage (MV) cable collector system was established in this paper to conduct switching operation tests of VCB and obtain the characteristic parameters for VCB, especially dielectric strength parameters; also, the effectiveness of the VCB reignition model was verified. Then, PSCAD/EMTDC was used to construct the MV collector system of the OWF, and the effects of normal switching and fault switching on TOV amplitude, steepness, and the total number of reignition of the VCB were studied, respectively, with the experimental parameters and traditional parameters of dielectric strength of the VCB. The simulation results show that when the VCB is at the tower bottom, the overvoltage amplitude generated by the normal switching is the largest, which is 1.83 p.u., and the overvoltage steepness of the fault switching is the largest, up to 142 kV/μs. The overvoltage amplitude and steepness caused by switching off VCB at the tower bottom faultily with traditional parameters are about 2 and 1.5 times of the experimental parameters under the same operating condition.
- Open Access
Analysis of Switching Transients during Energization in Large Offshore Wind Farms
In order to study switching transients in an offshore wind farm (OWF) collector system, we employ modeling methods of the main components in OWFs, including vacuum circuit breakers (VCBs), submarine cables, and wind turbine transformers (WTTs). In particular, a high frequency (HF) VCB model that reflects the prestrike characteristics of VCBs was developed. Moreover, a simplified experimental system of an OWF electric collection system was set up to verify the developed models, and a typical OWF medium voltage (MV) cable collection system was built in PSCAD/EMTDC based on the developed models. Finally, we investigated the influences of both the initial closing phase angle of VCBs and typical system operation scenarios on the amplitude and steepness of transient overvoltages (TOVs) at the high-voltage side of WTTs.
Open AccessAnalysis of Switching Transients during Energization in Large Offshore Wind Farms
In order to study switching transients in an offshore wind farm (OWF) collector system, we employ modeling methods of the main components in OWFs, including vacuum circuit breakers (VCBs), submarine cables, and wind turbine transformers (WTTs). In particular, a high frequency (HF) VCB model that reflects the prestrike characteristics of VCBs was developed. Moreover, a simplified experimental system of an OWF electric collection system was set up to verify the developed models, and a typical OWF medium voltage (MV) cable collection system was built in PSCAD/EMTDC based on the developed models. Finally, we investigated the influences of both the initial closing phase angle of VCBs and typical system operation scenarios on the amplitude and steepness of transient overvoltages (TOVs) at the high-voltage side of WTTs.