David Antonio Aragón Verduzco
David Antonio Aragón Verduzco has a total of 16 co-authors. Here are the top co-authors by number of shared publications:
- Juan Carlos Olivares Galvan
Departamento de Energia, Universidad Autonoma Metropolitana, Ciudad de Mexico 02128, Mexico
5 shared publications - Rafael Escarela-Perez
Departamento de Energia, Universidad Autonoma Metropolitana, Ciudad de Mexico 02128, Mexico
5 shared publications - José Luis Hernández Ávila
Departamento de Energia, Universidad Autonoma Metropolitana, Ciudad de Mexico 02128, Mexico
2 shared publications - Raúl Arturo Ortiz-Medina
Direccion de Posgrado e Investigacion, Universidad Politecnica de Aguascalientes, Aguascalientes 20342, Mexico
2 shared publications - Serguei Maximov
Tecnológico Nacional de México, Instituto Tecnológico de Morelia, Av. Tecnológico 1500, Morelia 58120, Michoacán, Mexico
2 shared publications - Carlos H. Alonso
Department of Electrical and Computer Engineering, New York University, Brooklyn, NY, USA
1 shared publication
Latest Publications
- Open Access
- 7 November 2026
- Published by MDPI AG in Technologies
- Vol. 14 (11) , 735
Station Service Voltage Transformer Technologies: Design Advances, Established and Emerging Applications
Access to reliable low-voltage power is challenging where distribution networks are unavailable or uneconomic, including switching substations, construction sites, and remote communities. Station Service Voltage Transformers (SSVTs), also known as Power Voltage Transformers (PVTs), address this problem by supplying useful low-voltage power from transmission or subtransmission networks. This paper reviews SSVT terminology, operating principles, construction architectures, electromagnetic and thermal modeling, testing, reliability, monitoring, and applications. The most extensively documented applications concern substation auxiliary services, while rural minisubstations are supported by SSVT-specific development studies and selected field reports. Electric mobility has progressed beyond a prospective concept: an SSVT-based, transmission-connected micro-substation pilot has demonstrated direct 220 kV-to-low-voltage supply for electric-vehicle (EV) charging. However, SSVT-specific characterization for this application, long-term operating data, and application-oriented design guidance remain limited. Key research gaps concern coupled multiphysics validation, nonlinear-load performance, reliability statistics, techno-economic assessment, and life-cycle analysis. Particular attention is given to distinguishing applications already demonstrated with SSVT technology from emerging uses for which validation, standardization, or long-term operating experience remains limited. The review concludes by proposing a roadmap to develop reproducible, experimentally validated, and digitally supported SSVT platforms for remote energy access and selected electric-mobility applications.
- 7 November 2026
- Published by MDPI AG in Technologies
- Vol. 14 (11) , 735
Open AccessStation Service Voltage Transformer Technologies: Design Advances, Established and Emerging Applications
Access to reliable low-voltage power is challenging where distribution networks are unavailable or uneconomic, including switching substations, construction sites, and remote communities. Station Service Voltage Transformers (SSVTs), also known as Power Voltage Transformers (PVTs), address this problem by supplying useful low-voltage power from transmission or subtransmission networks. This paper reviews SSVT terminology, operating principles, construction architectures, electromagnetic and thermal modeling, testing, reliability, monitoring, and applications. The most extensively documented applications concern substation auxiliary services, while rural minisubstations are supported by SSVT-specific development studies and selected field reports. Electric mobility has progressed beyond a prospective concept: an SSVT-based, transmission-connected micro-substation pilot has demonstrated direct 220 kV-to-low-voltage supply for electric-vehicle (EV) charging. However, SSVT-specific characterization for this application, long-term operating data, and application-oriented design guidance remain limited. Key research gaps concern coupled multiphysics validation, nonlinear-load performance, reliability statistics, techno-economic assessment, and life-cycle analysis. Particular attention is given to distinguishing applications already demonstrated with SSVT technology from emerging uses for which validation, standardization, or long-term operating experience remains limited. The review concludes by proposing a roadmap to develop reproducible, experimentally validated, and digitally supported SSVT platforms for remote energy access and selected electric-mobility applications.
- Open Access
- 13 February 2026
- Published by MDPI AG in Applied System Innovation
- Vol. 9 (2) , 41
3D Finite Element Models of Zigzag Grounding Transformer for Zero-Sequence Impedance Calculation
Accurate prediction of the zero-sequence impedance () of three-legged zigzag grounding transformers is essential for ground-fault protection and power-quality performance, yet manufacturer analytical estimations often have limited accuracy. This paper investigates how accurately can be predicted using 3D finite element method (FEM) models based on the stored magnetic energy approach and how modeling the metallic tank and nonlinear core B–H behavior affects relative to analytical calculations and laboratory measurements. Two 3D FEM models are developed for a three-legged zigzag grounding transformer, incorporating the nonlinear core characteristic; impedance boundary conditions are used to efficiently account for tank-induced currents while reducing computational cost. The FEM results are compared with laboratory tests and with the analytical method used by manufacturers. The proposed models achieve errors below 4% with respect to the nominal and outperform the analytical approach. The contributions are a validated 3D FEM methodology that resolves zero-sequence flux paths under fault conditions and a practical modeling tool that improves grounding transformer design and ground-fault protection settings in modern power systems.- 13 February 2026
- Published by MDPI AG in Applied System Innovation
- Vol. 9 (2) , 41
Open Access3D Finite Element Models of Zigzag Grounding Transformer for Zero-Sequence Impedance Calculation
Accurate prediction of the zero-sequence impedance () of three-legged zigzag grounding transformers is essential for ground-fault protection and power-quality performance, yet manufacturer analytical estimations often have limited accuracy. This paper investigates how accurately can be predicted using 3D finite element method (FEM) models based on the stored magnetic energy approach and how modeling the metallic tank and nonlinear core B–H behavior affects relative to analytical calculations and laboratory measurements. Two 3D FEM models are developed for a three-legged zigzag grounding transformer, incorporating the nonlinear core characteristic; impedance boundary conditions are used to efficiently account for tank-induced currents while reducing computational cost. The FEM results are compared with laboratory tests and with the analytical method used by manufacturers. The proposed models achieve errors below 4% with respect to the nominal and outperform the analytical approach. The contributions are a validated 3D FEM methodology that resolves zero-sequence flux paths under fault conditions and a practical modeling tool that improves grounding transformer design and ground-fault protection settings in modern power systems. - Open Access
- 4 April 2025
- Published by MDPI AG in Applied System Innovation
- Vol. 8 (2) , 50
Distinction Between Interturn Short-Circuit Faults and Unbalanced Load in Transformers
Transformers are essential in electrical networks, and their failure can lead to the shutdown of a section or the entire grid. This study proposes a combination of techniques for early fault detection, distinguishing between small load imbalances and incipient interturn short circuits. An experimental setup was developed using a three-phase transformer bank with three single-phase dry-type transformers. One transformer was modified to create controlled short circuits of two and four turns and to simulate a load imbalance by reducing the winding by four turns. The main contribution of this research is the development of a combined diagnostic approach using instantaneous space phasor (ISP) spectral analysis and infrared thermal imaging to differentiate between load imbalances and incipient interturn short circuits in transformers. This method enhances early fault detection by identifying distinctive electrical and thermal signatures associated with each condition. The results could improve transformer monitoring, reducing the risk of failure and enhancing grid reliability.
- 4 April 2025
- Published by MDPI AG in Applied System Innovation
- Vol. 8 (2) , 50
Open AccessDistinction Between Interturn Short-Circuit Faults and Unbalanced Load in Transformers
Transformers are essential in electrical networks, and their failure can lead to the shutdown of a section or the entire grid. This study proposes a combination of techniques for early fault detection, distinguishing between small load imbalances and incipient interturn short circuits. An experimental setup was developed using a three-phase transformer bank with three single-phase dry-type transformers. One transformer was modified to create controlled short circuits of two and four turns and to simulate a load imbalance by reducing the winding by four turns. The main contribution of this research is the development of a combined diagnostic approach using instantaneous space phasor (ISP) spectral analysis and infrared thermal imaging to differentiate between load imbalances and incipient interturn short circuits in transformers. This method enhances early fault detection by identifying distinctive electrical and thermal signatures associated with each condition. The results could improve transformer monitoring, reducing the risk of failure and enhancing grid reliability.
- 11 August 2024
- Published by Elsevier in Journal of Magnetism and Magnetic Materials
- Vol. 607
Enhanced analytical solution of magnetic field dynamics in nonlinear magnetic materials
- 11 August 2024
- Published by Elsevier in Journal of Magnetism and Magnetic Materials
- Vol. 607
Enhanced analytical solution of magnetic field dynamics in nonlinear magnetic materials
- 1 October 2021
- Published by Universidad Nacional Autonoma de Mexico in Ingeniería Investigación y Tecnología
- Vol. 22 (4) , 1-10
Numerical simulation of a squirrel cage motor including magnetic wedges and radial vents
This work is a proposal of a finite element model to obtain the electromagnetic performance of a squirrel cage motor considering the magnetic wedges and radial vents. To analyze the electromagnetic performance at the design stage, without the need to build a prototype, the paper proposes a simple two dimensions finite element model, which includes components as magnetic wedges used to hold the windings in the stator slots, radial vents in the core, which are part of motor cooling system, and edge effects to improve the model. The stator and rotor cores are modeled with an equivalent homogeneous permeability, obtained from the combination of the radial air vents of rotor and stator and the magnetic core material. The permeability of magnetic wedges is also considered. Edge effects considered are the end winding leakage inductance, representing the leakage flux in the end coils of the stator, and an equivalent impedance between rotor bars due to conductivity and leakage flux in the rings of the squirrel cage. The results obtained are compared with experimental tests performed in steady state to validate the model. Furthermore, no-load, and blocked-rotor tests are simulated to estimate the equivalent circuit parameters and draw the typical induction motor torque-speed curve, which is compared with the obtained curve by means of Thevenin’s theorem. With this proposed model, the results are close to the ones obtained experimentally. The implementation of a 3D model is complex, and the computational cost can be much higher, compared to the 2D model developed here.
- 1 October 2021
- Published by Universidad Nacional Autonoma de Mexico in Ingeniería Investigación y Tecnología
- Vol. 22 (4) , 1-10
Numerical simulation of a squirrel cage motor including magnetic wedges and radial vents
This work is a proposal of a finite element model to obtain the electromagnetic performance of a squirrel cage motor considering the magnetic wedges and radial vents. To analyze the electromagnetic performance at the design stage, without the need to build a prototype, the paper proposes a simple two dimensions finite element model, which includes components as magnetic wedges used to hold the windings in the stator slots, radial vents in the core, which are part of motor cooling system, and edge effects to improve the model. The stator and rotor cores are modeled with an equivalent homogeneous permeability, obtained from the combination of the radial air vents of rotor and stator and the magnetic core material. The permeability of magnetic wedges is also considered. Edge effects considered are the end winding leakage inductance, representing the leakage flux in the end coils of the stator, and an equivalent impedance between rotor bars due to conductivity and leakage flux in the rings of the squirrel cage. The results obtained are compared with experimental tests performed in steady state to validate the model. Furthermore, no-load, and blocked-rotor tests are simulated to estimate the equivalent circuit parameters and draw the typical induction motor torque-speed curve, which is compared with the obtained curve by means of Thevenin’s theorem. With this proposed model, the results are close to the ones obtained experimentally. The implementation of a 3D model is complex, and the computational cost can be much higher, compared to the 2D model developed here.
- 18 November 2019
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Magnetics
- Vol. 55 (12) , 1-12
Computation of Leakage Inductance of End Coils in Electrical Machines Considering Core Effects
A new analytical method is presented for computing the leakage inductance of the single-end coils of electrical machines, based on the solution of Maxwell’s equations, which considers core eddy currents. Maxwell’s equations are solved in general form in two regions: inside and outside the core, employing appropriate boundary conditions and an iteration scheme. Asymptotic methods are effectively employed for the analytical calculation of Green’s functions in both the regions. Analytical results are compared with 3-D finite-element computations. The comparison shows a close correspondence between the analytical and numerical results. Our formula is the basis for further computations of the end-winding leakage inductance of rotating electric machines.
- 18 November 2019
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Magnetics
- Vol. 55 (12) , 1-12
Computation of Leakage Inductance of End Coils in Electrical Machines Considering Core Effects
A new analytical method is presented for computing the leakage inductance of the single-end coils of electrical machines, based on the solution of Maxwell’s equations, which considers core eddy currents. Maxwell’s equations are solved in general form in two regions: inside and outside the core, employing appropriate boundary conditions and an iteration scheme. Asymptotic methods are effectively employed for the analytical calculation of Green’s functions in both the regions. Analytical results are compared with 3-D finite-element computations. The comparison shows a close correspondence between the analytical and numerical results. Our formula is the basis for further computations of the end-winding leakage inductance of rotating electric machines.