Xianda Deng
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Research Subjects
Research Interests
Xianda Deng has a total of 12 co-authors. Here are the top co-authors by number of shared publications:
- Wenxuan Yao
Hunan University
4 shared publications - Yilu Liu
Department of Electrical Engineering and Computer Science, University of Tennessee, Knoxville, TN, USA
4 shared publications - Weikang Wang
Department of Electrical Engineering and Computer Science, University of Tennessee, Knoxville, TN, USA
3 shared publications Abigail Till
Department of Electrical Engineering and Computer Science, University of Tennessee, Knoxville, TN, USA
1 shared publicationChang Chen
Department of Electrical Engineering and Computer Science, The University of Tennessee, Knoxville, USA
1 shared publication- Chang Chen
The University of Tennessee 37996 Knoxville TN USA
1 shared publication
Latest Publications
- 2 March 2020
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Systems
- Vol. 35 (3) , 2483-2486
Fast and Accurate Frequency Response Estimation for Large Power System Disturbances Using Second Derivative of Frequency Data
Accurate Frequency Response Estimation (FRE) is critical to reliability risk management of large power system disturbances. This letter proposes a measurement-driven approach for FRE by calculating the second derivative of frequency from synchrophasor data. Compared with conventional methods, the proposed method has major advantages of low computational burden and high accuracy, which makes it appropriate for real-time FRE in bulk power systems. The effectiveness of this method is validated with actual synchrophasor data on 96 confirmed historical power system disturbances in the U.S. eastern interconnection.
- 2 March 2020
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Systems
- Vol. 35 (3) , 2483-2486
Fast and Accurate Frequency Response Estimation for Large Power System Disturbances Using Second Derivative of Frequency Data
Accurate Frequency Response Estimation (FRE) is critical to reliability risk management of large power system disturbances. This letter proposes a measurement-driven approach for FRE by calculating the second derivative of frequency from synchrophasor data. Compared with conventional methods, the proposed method has major advantages of low computational burden and high accuracy, which makes it appropriate for real-time FRE in bulk power systems. The effectiveness of this method is validated with actual synchrophasor data on 96 confirmed historical power system disturbances in the U.S. eastern interconnection.
- 5 February 2020
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Smart Grid
- Vol. 11 (4) , 3593-3605
Frequency Disturbance Event Detection Based on Synchrophasors and Deep Learning
Power system frequency disturbances are caused by various generation and transmission events including generator trips, load disconnections, line trips, etc. Accurate detections of the events are crucial to bulk power system situation awareness and event investigation. This paper utilizes the recent advances of deep learning to build a convolutional neural network model to detect events in an accurate yet straightforward manner. In this paper, the rate of change of frequency and the relative angle shift are converted to images as the inputs of the proposed model. Finally, this paper uses two convolutional neural networks and classifier fusion to achieve the detection result. Compared with the conventional event detection algorithm and the frequency only deep learning model, the proposed model improves the detection accuracy by over 48%. As a promising tool for bulk power system situation awareness, the proposed model requires a short decision time, which is suitable for practical scenarios.
- 5 February 2020
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Smart Grid
- Vol. 11 (4) , 3593-3605
Frequency Disturbance Event Detection Based on Synchrophasors and Deep Learning
Power system frequency disturbances are caused by various generation and transmission events including generator trips, load disconnections, line trips, etc. Accurate detections of the events are crucial to bulk power system situation awareness and event investigation. This paper utilizes the recent advances of deep learning to build a convolutional neural network model to detect events in an accurate yet straightforward manner. In this paper, the rate of change of frequency and the relative angle shift are converted to images as the inputs of the proposed model. Finally, this paper uses two convolutional neural networks and classifier fusion to achieve the detection result. Compared with the conventional event detection algorithm and the frequency only deep learning model, the proposed model improves the detection accuracy by over 48%. As a promising tool for bulk power system situation awareness, the proposed model requires a short decision time, which is suitable for practical scenarios.
- 22 August 2019
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 35 (3) , 1588-1591
Timestamp Shift Detection for Synchrophasor Data Based on Similarity Analysis Between Relative Phase Angle and Frequency
Timestamp Shift (TS) in synchrophasor data can lead to false operation of synchrophasor-based wide-area monitoring, protection and control applications. The letter presents a method to detect TS of synchrophasor data based on similarity analysis between its own relative phase angle and frequency. A linear correlation component, caused by TS, between relative phase angle and measured frequency is discovered via theoretical derivation. Then a detection method is developed utilizing this linear component for TS diagnosis. Firstly, system phase angle is leveraged as angle reference and then relative phase angle is calculated. Secondly, the correlation coefficient between relative phase angle and frequency is calculated for similarity analysis. Thirdly, the TS is detected via threshold criterion and corresponding time error is estimated. The effectiveness of this method is validated via experiments with actual synchrophasor data in FNET/Grideye.
- 22 August 2019
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 35 (3) , 1588-1591
Timestamp Shift Detection for Synchrophasor Data Based on Similarity Analysis Between Relative Phase Angle and Frequency
Timestamp Shift (TS) in synchrophasor data can lead to false operation of synchrophasor-based wide-area monitoring, protection and control applications. The letter presents a method to detect TS of synchrophasor data based on similarity analysis between its own relative phase angle and frequency. A linear correlation component, caused by TS, between relative phase angle and measured frequency is discovered via theoretical derivation. Then a detection method is developed utilizing this linear component for TS diagnosis. Firstly, system phase angle is leveraged as angle reference and then relative phase angle is calculated. Secondly, the correlation coefficient between relative phase angle and frequency is calculated for similarity analysis. Thirdly, the TS is detected via threshold criterion and corresponding time error is estimated. The effectiveness of this method is validated via experiments with actual synchrophasor data in FNET/Grideye.
- 2 July 2019
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Smart Grid
- Vol. 11 (1) , 895-904
A Fast Load Control System Based on Mobile Distribution-Level Phasor Measurement Unit
The increase of renewable penetration in power grids calls for loads to participate in frequency regulation to avoid under-frequency load shedding after large resource contingencies. The motivation of this paper is to fulfill a fast residential load control for frequency stability enhancement. For this purpose, a novel mobile distribution-level phasor measurement unit (MDPMU) is developed for disturbance event detection, power mismatch estimation and fast load control. First, the systematic design of the MDPMU introduced. The proposed MDPMU has the major advantages of low cost and high frequency measurement accuracy. Second, the distribution-level measurement is utilized for the rate of change of frequency (ROCOF) calculation. Upon detection of a power system frequency event, power mismatch is estimated at the early stage of the event. Details of a robust approach to calculate ROCOF and determine the event starting point are presented. Practical issues including the measurement reporting rate and estimation time are also considered. Last, with the proposed control system, residential load responses can be controlled coordinately based on load availability and compensation prices offered by customers, providing adaptive frequency regulation service after large resource contingencies. The accuracy of frequency measurement and power mismatch estimation are evaluated via experimental analysis. The frequency stability improvement by load control is validated via PSS/E simulation.
- 2 July 2019
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Smart Grid
- Vol. 11 (1) , 895-904
A Fast Load Control System Based on Mobile Distribution-Level Phasor Measurement Unit
The increase of renewable penetration in power grids calls for loads to participate in frequency regulation to avoid under-frequency load shedding after large resource contingencies. The motivation of this paper is to fulfill a fast residential load control for frequency stability enhancement. For this purpose, a novel mobile distribution-level phasor measurement unit (MDPMU) is developed for disturbance event detection, power mismatch estimation and fast load control. First, the systematic design of the MDPMU introduced. The proposed MDPMU has the major advantages of low cost and high frequency measurement accuracy. Second, the distribution-level measurement is utilized for the rate of change of frequency (ROCOF) calculation. Upon detection of a power system frequency event, power mismatch is estimated at the early stage of the event. Details of a robust approach to calculate ROCOF and determine the event starting point are presented. Practical issues including the measurement reporting rate and estimation time are also considered. Last, with the proposed control system, residential load responses can be controlled coordinately based on load availability and compensation prices offered by customers, providing adaptive frequency regulation service after large resource contingencies. The accuracy of frequency measurement and power mismatch estimation are evaluated via experimental analysis. The frequency stability improvement by load control is validated via PSS/E simulation.