  • Open Access

    Inherent Interaction Analysis for Harmonic Oscillations in the Multi-Paralleled Grid-Connected Inverter System Using a Sum Type Criterion: Global Admittance (GA)

    by Wu Cao, Shunyu Wang, Haotian Kang, Kangli Liu, Qingsong Wang, Jianfeng Zhao

    With the extensive use of power electronics converters, harmonic oscillation issues in the multi-paralleled grid-connected inverter system have drawn much attention. Apart from the stability analysis using the impedance-based stability analysis method, the interaction analysis is aimed at revealing the changing process of the system state under the variation of some parameters such as the grid impendence, the number of grid-connected inverters and the control parameter of the inverter current control, etc. In this paper, after comparing the ratio type stability criterion and the sum type stability criterion, the interaction analysis using global admittance is presented in two frequency-domain dimensions. It shows that the harmonic instability depends on both the imaginary part of global admittance which determines the appearance of the resonance point and the real part of global admittance which reflects the property of such resonance point. The essence of this approach is to reveal the appearance of the resonance point and its influence on the system stability. The inherent changing rules of the resonance point are illustrated in the following typical occasions: different grid impendence, different number of grid-connected inverters and different control parameters of the current control loop. Finally, detailed simulations and experimental results validate the effectiveness of the proposed approach.


  • Open Access

    Responsibility Identification for Harmonic Oscillation Issues in the Parallel Grid-Connected Inverters System

    by Wu Cao, Shunyu Wang, Kangli Liu, Haotian Kang, Jianfeng Zhao

    The responsibility identification for harmonic oscillation issues, caused by the interaction among the inner control loops of power electronics converters and passive components in renewable energy systems, can provide guidelines to the harmonic oscillation suppression. However, the identification method using the impendence-based stability criterion has not been fully discussed. In this paper, two methods based on a sum type impedance-based stability criterion are proposed to identify the responsibility of each inverter. The proposed Method-1, which is called the result-oriented method, calculates the system state quantitatively assuming one of the inverters is removed from the system and the responsibility of each inverter can be obtained when the calculation is done removing each inverter. The proposed Method-2, which is called the cause-oriented method, employs the calculation of the original system state and the inverter state using the combination weighting method to analyze the responsibility of each inverter on system instability. The former method is more accurate while the later one is more suitable in the large-scale system due to less computation. Finally, simulation and experiment results validate the effectiveness of the proposed methods and analysis.


  • Distributed Active Damping for Harmonic Instability Suppression in the Multi-paralleled Grid-connected Inverter System

    by Shunyu Wang, Wu Cao, Kangli Liu, Haotian Kang, Jianfeng Zhao, Chao Shi, Jing Song

    Aiming at the harmonic instability problem of multi-paralleled grid-connected inverter system, which is caused by the interaction among the fast inner current or voltage control loops of inverters and grid impendence, distributed active damping is proposed in this paper. This approach is based on the grid voltage feedforward strategy and increase the damping of the global admittance (GA), which effectively improves the system stability. One of the advantages of this approach is that when some of the active damping fail to work, the remaining active damping can still maintain the system stability. Another is the employment of a second-order lag corrector which can alleviate the influence of the ignorance the prediction component and improve the characteristic of inverter output admittance at the harmonic controlled frequencies. Simulations are carried out and the results verify the effectiveness of the proposed method.


  • Open Access

    Resonance Detection Strategy for Multi-Parallel Inverter-Based Grid-Connected Renewable Power System Using Cascaded SOGI-FLL

    by Wu Cao, Kangli Liu, Haotian Kang, Shunyu Wang, Dongchen Fan, Jianfeng Zhao

    The increasing use of multi-parallel grid-connected inverters introduces both high-quality and high-capacity power, while it tends to cause a resonance instability problem. A resonance damper can virtualize a resistor at resonant frequency to suppress the instability effectively, but the resonant frequency should be detected primarily. However, the resonant current or voltage is severely distorted and oscillating, which will lead to the resonant frequency extraction being more difficult. To address it, this paper proposes a resonance detection strategy based on the cascaded second-order generalized integrators (SOGI) and the normalized frequency locked loop (FLL). The cascaded structure ensures the accuracy by completely filtering the fundamental component from the detected voltage or current, and the normalization accelerates the frequency detection. The proposed method can be used as a crucial unit of the resonance damping controller. Finally, the performance of the proposed method is verified by the MATLAB-based simulation and Hardware-in-the-Loop (HIL)-based emulation results.


  • Open Access

    Harmonic Stability Analysis for Multi-Parallel Inverter-Based Grid-Connected Renewable Power System Using Global Admittance

    by Wu Cao, Kangli Liu, Shunyu Wang, Haotian Kang, Dongchen Fan, Jianfeng Zhao

    Multi-parallel grid-connected voltage source inverters (VSIs) are widely applied in the fields of renewable energy, energy storage, harmonic suppression, etc. However, these inverters may cause harmonic stability problems due to the interactions among the grid-connected inverters through the grid impedance, which can seriously threaten system stability. The impedance-based stability criterion provides an effective tool for analyzing harmonic instability issues and can be divided into two types, namely, a ratio type and a sum type. Based on the existing studies of the sum-type criterion, this paper further proposes a new sum-type form based on the global admittance from the PCC to assess system stability through frequency-domain analysis. This global admittance-based stability criterion can be used not only to analyze system stability, but also to reveal the influence of each VSI unit on system stability with a lower computational burden and provide guidance for resonance suppression, especially in the case of a large number of grid-connected inverters and asymmetric inverter parameters. Finally, a MATLAB/Simulink model and 400 kVA/400 V experimental platform consisting of six grid-connected VSIs were established, and the corresponding results are presented to verify the effectiveness of the proposed method.