Volodymyr Grinchenko
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Research Subjects
Research Interests
Volodymyr Grinchenko has a total of 17 co-authors. Here are the top co-authors by number of shared publications:
- Oleksandr Tkachenko
Державна установа "Інститут технічних проблем магнетизму Національної академії наук України
8 shared publications - Kostiantyn Chunikhin
Anatolii Pidhornyi Institute of Power Machines and Systems of the National Academy of Sciences of Ukraine
5 shared publications - Volodymyr Rozov
Anatolii Pidhornyi Institute of Power Machines and Systems of the National Academy of Sciences of Ukraine, Ukraine
3 shared publications A.V. Yerisov
1 shared publicationAnatolii Yerisov
State Institution, Institute of Technical Problems of Magnetism of the National Academy of Sciences of Ukraine, Department of Physics and Technology of Magnetic Phenomena, Kharkiv, Ukraine
1 shared publication- Bartlomiej Blachowski
Institute of Fundamental Technological Research, Polish Academy of Sciences, 02-106 Warsaw, Poland
1 shared publication
Latest Publications
- Open Access
- 2 March 2026
- Published by National Technical University Kharkiv Polytechnic Institute in Electrical Engineering & Electromechanics
- No. 2,p. 89-92
Highly accurate approximation for sheath currents in high-voltage three-phase cable line
Introduction. This study focuses on sheath currents in high-voltage single-core XLPE-insulated power cables with solid bonding. The analysis covers flat and trefoil three-phase cable lines. Sheath current calculation is essential for evaluating thermal conditions, losses, and overall cable performance. Problem. The regulatory documents of the Ministry of Energy of Ukraine provide formulas for sheath currents. We examine them by comparing with verified analytical solutions and find significant discrepancies in a wide range of typical parameters of high-voltage three-phase cable line. So the formulas in the current regulatory document have a narrow range of applicability, and the engineering calculations based on them may lead to significant inaccuracies and incorrect decisions. Goal. The paper aims to develop novel formulas for the RMS values of sheath currents in high-voltage three-phase cable lines with flat and trefoil arrangements of power cables, ensuring the accuracy required for engineering calculations across a wide range of cable line parameters. Methodology. This study is grounded on the previously developed and experimentally verified analytical model and corresponding formulas for calculating sheath currents and cable line magnetic field. These verified formulas for sheath currents are too cumbersome, so an approximation technique is used to find compact ones. Results. A novel approximation for sheath current in the flat cable line is developed. The discrepancy between the approximation and the verified formulas is within 5 %. Additionally, a new form of the formula for sheath current in the trefoil cable line is proposed. Scientific novelty. To perform the approximation, an original quality index is proposed. It is derived from the heat output of metal sheaths of cables. Practical value. The developed approximation for sheath current can be directly applied to the design of high-voltage cable lines, the analysis of the operating modes, and the control of the compliance of existing cable lines with actual operating conditions. References 20, table 1, figures 4.
- 2 March 2026
- Published by National Technical University Kharkiv Polytechnic Institute in Electrical Engineering & Electromechanics
- No. 2,p. 89-92
Open AccessHighly accurate approximation for sheath currents in high-voltage three-phase cable line
Introduction. This study focuses on sheath currents in high-voltage single-core XLPE-insulated power cables with solid bonding. The analysis covers flat and trefoil three-phase cable lines. Sheath current calculation is essential for evaluating thermal conditions, losses, and overall cable performance. Problem. The regulatory documents of the Ministry of Energy of Ukraine provide formulas for sheath currents. We examine them by comparing with verified analytical solutions and find significant discrepancies in a wide range of typical parameters of high-voltage three-phase cable line. So the formulas in the current regulatory document have a narrow range of applicability, and the engineering calculations based on them may lead to significant inaccuracies and incorrect decisions. Goal. The paper aims to develop novel formulas for the RMS values of sheath currents in high-voltage three-phase cable lines with flat and trefoil arrangements of power cables, ensuring the accuracy required for engineering calculations across a wide range of cable line parameters. Methodology. This study is grounded on the previously developed and experimentally verified analytical model and corresponding formulas for calculating sheath currents and cable line magnetic field. These verified formulas for sheath currents are too cumbersome, so an approximation technique is used to find compact ones. Results. A novel approximation for sheath current in the flat cable line is developed. The discrepancy between the approximation and the verified formulas is within 5 %. Additionally, a new form of the formula for sheath current in the trefoil cable line is proposed. Scientific novelty. To perform the approximation, an original quality index is proposed. It is derived from the heat output of metal sheaths of cables. Practical value. The developed approximation for sheath current can be directly applied to the design of high-voltage cable lines, the analysis of the operating modes, and the control of the compliance of existing cable lines with actual operating conditions. References 20, table 1, figures 4.
- 27 February 2026
- Published by Elsevier in Electric Power Systems Research
- Vol. 256
Energy-efficient active shield for substation magnetic field mitigation
- 27 February 2026
- Published by Elsevier in Electric Power Systems Research
- Vol. 256
Energy-efficient active shield for substation magnetic field mitigation
- 27 December 2022
- Published by National Academy of Sciences of Ukraine (Co. LTD Ukrinformnauka) (Publications) in System Research in Energy
- Vol. 2022 (2) , 73-84
Review of passive loop systems for normalization of high-voltage cable line magnetic field
The paper is devoted to the review of known passive loop systems that can be used to normalize the high-voltage cable line magnetic field. The purpose is to identify the most promising systems. We review the most cited scientific papers and patents about the reduction of the power line magnetic field. We identify the top research groups engaged in the design of passive loop systems. The two groups are from Italy, the one each is from Spain and Ukraine. The passive loop systems developed by each group have their own features. We classify the systems according to the following characteristics: the number of passive loops in the shielding system, the shape of passive loops used in the shielding system, and the way to increase the shielding efficiency of cable line magnetic field. According to the number of passive loops, the systems can be divided into three types: single-element, double-element and multi-element. According to the shape of passive loops, two types of shielding systems can be distinguished, namely, the systems using rectangular passive loops and the systems using passive loops made of three cables connected in parallel. According to the method of the shielding efficiency increasing, the system can be divided into four types: the first use ferromagnetic cores covering power and shield cables, the second use additional capacitors connected to shield cables, the third use a unique arrangement of loops between the cable line and the shielding area, the fourth use an increase in the cross-section of shield cables, respectively, an increase in the quantity of metal. The review shows the most promising passive loop systems for normalizing the high-voltage cable line magnetic field are single-element systems with additional cores, namely «High Magnetic Coupling Passive Loop» and «Single-loop shield with ferromagnetic cores and asymmetric magnetic coupling». Keywords: magnetic field, shielding, cable line, reference level, power frequency
- 27 December 2022
- Published by National Academy of Sciences of Ukraine (Co. LTD Ukrinformnauka) (Publications) in System Research in Energy
- Vol. 2022 (2) , 73-84
Review of passive loop systems for normalization of high-voltage cable line magnetic field
The paper is devoted to the review of known passive loop systems that can be used to normalize the high-voltage cable line magnetic field. The purpose is to identify the most promising systems. We review the most cited scientific papers and patents about the reduction of the power line magnetic field. We identify the top research groups engaged in the design of passive loop systems. The two groups are from Italy, the one each is from Spain and Ukraine. The passive loop systems developed by each group have their own features. We classify the systems according to the following characteristics: the number of passive loops in the shielding system, the shape of passive loops used in the shielding system, and the way to increase the shielding efficiency of cable line magnetic field. According to the number of passive loops, the systems can be divided into three types: single-element, double-element and multi-element. According to the shape of passive loops, two types of shielding systems can be distinguished, namely, the systems using rectangular passive loops and the systems using passive loops made of three cables connected in parallel. According to the method of the shielding efficiency increasing, the system can be divided into four types: the first use ferromagnetic cores covering power and shield cables, the second use additional capacitors connected to shield cables, the third use a unique arrangement of loops between the cable line and the shielding area, the fourth use an increase in the cross-section of shield cables, respectively, an increase in the quantity of metal. The review shows the most promising passive loop systems for normalizing the high-voltage cable line magnetic field are single-element systems with additional cores, namely «High Magnetic Coupling Passive Loop» and «Single-loop shield with ferromagnetic cores and asymmetric magnetic coupling». Keywords: magnetic field, shielding, cable line, reference level, power frequency
- 1 March 2021
- Published by Institute of Power Engineering in Problems of the Regional Energetics
- No. 1(49),p. 1-11
Thermal Effect of Single Loop Shield on High-Voltage Cable Line Capacity
The paper deals with a single-loop shield with an asymmetric magnetic coupling used for a magnetic field mitigation of a high-voltage three-phase cable line. The goal is to evaluate a thermal effect of this shield on a cable line capacity. To calculate the flat cable line capacity in the nonshielded case, we use a standard IEC 60287. To achieve the goal we carry out a numerical simulation of the thermal field when the shield is installed. Wherein, we deal with two specific sections. One is a long section with the shield being distant from the cable line. The other is a relatively short section where the shield is located near the power cables. The thermal field is applied for a long section in a two-dimensional formulation, and a three-dimensional formulation is used for the short section. Hence, we have obtained the dependences of the maximum temperature of the power cables on parameters of the shield and its location height above the cable line. The most significant allowable cross-sections of the shield cable and their location height have been determined, when the thermal effect of the shield does not decrease the cable line capacity. These results have ensured the maximum cable line capacity while shielding. The shield temperature is shown to exceed the allowable level in the short section. To reduce it the thermal backfill has been used. We recommend the values of its thermal resistivity to be used for different parameters of the single-loop shield.
- 1 March 2021
- Published by Institute of Power Engineering in Problems of the Regional Energetics
- No. 1(49),p. 1-11
Thermal Effect of Single Loop Shield on High-Voltage Cable Line Capacity
The paper deals with a single-loop shield with an asymmetric magnetic coupling used for a magnetic field mitigation of a high-voltage three-phase cable line. The goal is to evaluate a thermal effect of this shield on a cable line capacity. To calculate the flat cable line capacity in the nonshielded case, we use a standard IEC 60287. To achieve the goal we carry out a numerical simulation of the thermal field when the shield is installed. Wherein, we deal with two specific sections. One is a long section with the shield being distant from the cable line. The other is a relatively short section where the shield is located near the power cables. The thermal field is applied for a long section in a two-dimensional formulation, and a three-dimensional formulation is used for the short section. Hence, we have obtained the dependences of the maximum temperature of the power cables on parameters of the shield and its location height above the cable line. The most significant allowable cross-sections of the shield cable and their location height have been determined, when the thermal effect of the shield does not decrease the cable line capacity. These results have ensured the maximum cable line capacity while shielding. The shield temperature is shown to exceed the allowable level in the short section. To reduce it the thermal backfill has been used. We recommend the values of its thermal resistivity to be used for different parameters of the single-loop shield.
- Open Access
- 1 January 2021
- Published by National Technical University Kharkiv Polytechnic Institute in Electrical Engineering & Electromechanics
- No. 3,p. 38-41
NORMALIZATION OF DOUBLE-CIRCUIT OVERHEAD LINE MAGNETIC FIELD INSIDE KHRUSHCHEV BUILDING
This paper deals with the mitigation of 110 kV double-circuit overhead line magnetic field inside five-story Khrushchev buildings. We show that the magnetic field can exceed the reference level 0.5 mu T in 90 % part of living space. To mitigate the magnetic field, we propose the inverted L-shaped grid shield with conductors on the wall and in the attic of the building. Using the analytical model of the grid shield and the numerical simulation, we determine the parameters of the L-shaped grid shield which provides the magnetic field normalization in 97 % part of living space. Further improvement of the grid shield profile, in particular, the placement of some conductors in the basement, allows to reduce the quantity of metal of the shield by 15 % while maintaining the shielding efficiency. Also we consider the magnetic field normalization for the overhead line with a rated current of 500 A. In this case, the quantity of metal of the grid shield increases 2.74 times. References 19, table 1, figures 5.
- 1 January 2021
- Published by National Technical University Kharkiv Polytechnic Institute in Electrical Engineering & Electromechanics
- No. 3,p. 38-41
Open AccessNORMALIZATION OF DOUBLE-CIRCUIT OVERHEAD LINE MAGNETIC FIELD INSIDE KHRUSHCHEV BUILDING
This paper deals with the mitigation of 110 kV double-circuit overhead line magnetic field inside five-story Khrushchev buildings. We show that the magnetic field can exceed the reference level 0.5 mu T in 90 % part of living space. To mitigate the magnetic field, we propose the inverted L-shaped grid shield with conductors on the wall and in the attic of the building. Using the analytical model of the grid shield and the numerical simulation, we determine the parameters of the L-shaped grid shield which provides the magnetic field normalization in 97 % part of living space. Further improvement of the grid shield profile, in particular, the placement of some conductors in the basement, allows to reduce the quantity of metal of the shield by 15 % while maintaining the shielding efficiency. Also we consider the magnetic field normalization for the overhead line with a rated current of 500 A. In this case, the quantity of metal of the grid shield increases 2.74 times. References 19, table 1, figures 5.
- Open Access
- 26 October 2020
- Published by National Technical University Kharkiv Polytechnic Institute in Electrical Engineering & Electromechanics
- No. 5,p. 38-43
MAGNETIC FIELD NORMALIZATION IN RESIDENTIAL BUILDING LOCATED NEAR OVERHEAD LINE BY GRID SHIELD
НОРМАЛИЗАЦИЯ МАГНИТНОГО ПОЛЯ В ЖИЛЫХ ДОМАХ, РАСПОЛОЖЕННЫХ ВБЛИЗИ ВОЗДУШНЫХ ЛИНИЙ ЭЛЕКТРОПЕРЕДАЧИ, РЕШЕТЧАТЫМИ ЭКРАНАМИ
- 26 October 2020
- Published by National Technical University Kharkiv Polytechnic Institute in Electrical Engineering & Electromechanics
- No. 5,p. 38-43
Open AccessMAGNETIC FIELD NORMALIZATION IN RESIDENTIAL BUILDING LOCATED NEAR OVERHEAD LINE BY GRID SHIELD
НОРМАЛИЗАЦИЯ МАГНИТНОГО ПОЛЯ В ЖИЛЫХ ДОМАХ, РАСПОЛОЖЕННЫХ ВБЛИЗИ ВОЗДУШНЫХ ЛИНИЙ ЭЛЕКТРОПЕРЕДАЧИ, РЕШЕТЧАТЫМИ ЭКРАНАМИ
- Open Access
- 25 August 2020
- Published by National Academy of Sciences of Ukraine (Co. LTD Ukrinformnauka) (Publications) in Tekhnichna Elektrodynamika
- Vol. 2020 (5) , 5-9
MITIGATION OF OVERHEAD LINE MAGNETIC FIELD BY GRID SHIELD WITH ELECTRICALLY SEPARATED SECTIONS
Joomla! - the dynamic portal engine and content management system
- 25 August 2020
- Published by National Academy of Sciences of Ukraine (Co. LTD Ukrinformnauka) (Publications) in Tekhnichna Elektrodynamika
- Vol. 2020 (5) , 5-9
Open AccessMITIGATION OF OVERHEAD LINE MAGNETIC FIELD BY GRID SHIELD WITH ELECTRICALLY SEPARATED SECTIONS
Joomla! - the dynamic portal engine and content management system
- 1 July 2018
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 358-361
Analytical Calculation of Magnetic Field Shielding Factor for Cable Line with Two-Point Bonded Shields
In this paper we present an analytical model of the magnetic field of a high-voltage three-phase cable line with two-point bonded shields. The cable line is assumed to consist of three single-core XLPE insulated cables. The represented analytical model allows to calculate the electric currents induced in shields of cables and to determine the magnetic field distribution for the arbitrary layout of cables. We obtain an exact compact expression for the magnetic field shielding factor for the trefoil cable line with two-point bonded shields. Also we obtain a simplified compact expression for the magnetic field shielding factor for the flat cable line with two-point bonded shields. We show that the difference of the simplified expression with the exact analytical expression and experimental results is within 4 %.
- 1 July 2018
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 358-361
Analytical Calculation of Magnetic Field Shielding Factor for Cable Line with Two-Point Bonded Shields
In this paper we present an analytical model of the magnetic field of a high-voltage three-phase cable line with two-point bonded shields. The cable line is assumed to consist of three single-core XLPE insulated cables. The represented analytical model allows to calculate the electric currents induced in shields of cables and to determine the magnetic field distribution for the arbitrary layout of cables. We obtain an exact compact expression for the magnetic field shielding factor for the trefoil cable line with two-point bonded shields. Also we obtain a simplified compact expression for the magnetic field shielding factor for the flat cable line with two-point bonded shields. We show that the difference of the simplified expression with the exact analytical expression and experimental results is within 4 %.
- 15 May 2018
- Published by National Academy of Sciences of Ukraine (Co. LTD Ukrinformnauka) (Publications) in Tekhnichna Elektrodynamika
- Vol. 2018 (4) , 29-32
MITIGATION OF THREE-PHASE POWER LINE MAGNETIC FIELD BY GRID ELECTROMAGNETIC SHIELD
Joomla! - the dynamic portal engine and content management system
- 15 May 2018
- Published by National Academy of Sciences of Ukraine (Co. LTD Ukrinformnauka) (Publications) in Tekhnichna Elektrodynamika
- Vol. 2018 (4) , 29-32
MITIGATION OF THREE-PHASE POWER LINE MAGNETIC FIELD BY GRID ELECTROMAGNETIC SHIELD
Joomla! - the dynamic portal engine and content management system
- Open Access
- 20 October 2017
- Published by National Technical University Kharkiv Polytechnic Institute in Electrical Engineering & Electromechanics
- No. 5,p. 41-44
CALCULATION OF MAGNETIC FIELD OF THREE-PHASE CABLE LINES WITH TWO-POINT BONDED CABLE SHIELDS COVERED BY FERROMAGNETIC CORES
Анотація Получены компактные соотношения для расчета эффективности экранирования магнитного поля высоковольтной трехфазной кабельной линии, состоящей из одножильных кабелей, которые охвачены ферромагнитными сердечниками, при двустороннем замыкании собственных экранов. Рассмотрены кабельные линии с укладкой кабелей треугольником и в плоскости. Предложенные соотношения для расчета эффективности экранирования магнитного поля верифицированы экспериментально.
- 20 October 2017
- Published by National Technical University Kharkiv Polytechnic Institute in Electrical Engineering & Electromechanics
- No. 5,p. 41-44
Open AccessCALCULATION OF MAGNETIC FIELD OF THREE-PHASE CABLE LINES WITH TWO-POINT BONDED CABLE SHIELDS COVERED BY FERROMAGNETIC CORES
Анотація Получены компактные соотношения для расчета эффективности экранирования магнитного поля высоковольтной трехфазной кабельной линии, состоящей из одножильных кабелей, которые охвачены ферромагнитными сердечниками, при двустороннем замыкании собственных экранов. Рассмотрены кабельные линии с укладкой кабелей треугольником и в плоскости. Предложенные соотношения для расчета эффективности экранирования магнитного поля верифицированы экспериментально.