    Effects of Quantity and Arrangement of a Flame-Retardant Cable on Burning Characteristics in Open and Compartment Environments

    by Hong-Seok Yun, Cheol-Hong Hwang

    The results of cable burning experiments conducted in a well-controlled or open environment may differ from fire phenomena in an actual installation environment of cables where the effects of ventilation conditions and thermal feedback exist. In order to prevent the misunderstanding of fire phenomena due to these differences, the changes in burning characteristics in open and compartment environments were investigated for a flame-retardant (TFR-8) cable and general PVC (VCTF) cable arranged on three-layer trays. As a result, it was confirmed that the fire scale, fire spread area, and cable damage varied greatly depending on the cable arrangement under the same cable quantity condition. Furthermore, the maximum heat release rate (HRR) and fire growth rate of TFR-8 in the compartment environment increased more than 3-times compared to the open environment, and showed a similar level of fire risk to VCTF even though it is a flame-retardant cable. Additional experiments using vertical and horizontal openings of various shapes were conducted to evaluate the individual contributions of thermal feedbacks from the wall and smoke layer to the changes in burning characteristics within the compartment. The results of this study can be used as basic data to reduce fire damage while providing an essential understanding of cable fire phenomena.


  • Open Access

    The Sinkhole Phenomenon—Changes in Compartment Fire Characteristics Due to Incomplete Combustion before Flame Ejection

    by Hong-Seok Yun, Sun-Yeo Mun, Cheol-Hong Hwang

    In this study, experiments and numeric studies were conducted to analyze the causes of abnormal behavior in temperature, heat flux, and combustion efficiency that occurred before a compartment fire was converted to the under-ventilated condition. The fire experiments were performed using a 1/4 reduced-scale ISO 9705 compartment and propane fuel. Considering that the occurrence and termination of abnormal behavior are related to ventilation conditions, vertical openings of various shapes designed to have the identical ventilation factor (0.52Ah) were used. As a result, an abnormal phenomenon was observed in which the measured heat release rate did not increase despite the increase in the fuel flow rate under the over-ventilation condition in all opening shapes. Due to this phenomenon, the combustion efficiency was reduced to 70% regardless of the opening shape. In order to understand these abnormal behaviors and to analyze the causes of their occurrence, the temperature and chemical species concentrations of the opening discharge flow were measured. The results indicated that the abnormal behavior of thermal physical quantities, HRR, and combustion efficiency occurred because fuel that was not burned inside the compartment did not reach the lower combustion limit even outside the compartment and was discharged.


  • Open Access

    An Experimental Study on the Fire Spread Rate and Separation Distance between Facing Stores in Passage-Type Traditional Markets

    by Hong-Seok Yun, Dong-Gun Nam, Cheol-Hong Hwang

    Real-scale fire experiments were conducted to understand the fire spread characteristics of the major combustibles handled in traditional markets, a space with high fire risk. The major combustibles were selected through field surveys administered at a number of traditional markets. Through real-scale fire experiments, the horizontal fire spread rate according to the maximum heat release rate of major combustibles was examined. In addition, the separation distance to prevent fire spread to the facing store by radiant heat transfer was examined. As a result of the experiments, it was confirmed that the arrangement method of the combustibles causes a large change in the maximum heat release rate, fire growth rate, and fire spread rate. The horizontal fire spread rate showed a linear proportional relationship with respect to the maximum heat release rate regardless of the type of combustibles, and a correlation to define the relationship was proposed. A correlation equation for predicting the separation distance that can prevent fire spread by radiant heat transfer was proposed, and the curve by the correlation equation was in good agreement with the experimental results. Through this study, it is expected that the correlation proposed to examine the horizontal fire spread rate and the separation distance of major combustibles in a traditional market can be usefully used in the design of fire protection systems to reduce fire damage in the traditional market.