Dwijasish Das
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Previous Organizations / Institutes
The organizations / institutes from the scholar's other articles in the past ten years
Dwijasish Das has a total of 17 co-authors. Here are the top co-authors by number of shared publications:
- Chandan Kumar
Electronics and Electrical Engineering Department, Indian Institute of Technology Guwahati, Assam, India
10 shared publications - V. M. Hrishikesan
Electronics and Electrical Engineering Department, Indian Institute of Technology Guwahati, Guwahati, India
3 shared publications - Marco Liserre
Kiel University
2 shared publications Anup Kumar Deka
Wright Electric Inc., Malta, NY, USA
1 shared publication- Devendra Kumar
Electronics and Electrical Engineering Department, Indian Institute of Technology Guwahati, Guwahati, Assam, India
1 shared publication - Hoay Beng Gooi
Nanyang Technological University
1 shared publication
Latest Publications
- 29 January 2025
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Journal of Emerging and Selected Topics in Power Electronics
- Vol. 13 (2) , 2489-2499
A Meshed Hybrid Microgrid Configuration With Unified Power Quality Conditioner
The distribution grid is under major transformation due to the increasing dependency on renewable energy resources (RES) and electric vehicle (EV) charging stations. For accommodating such sources and loads in an existing AC distribution system without violating the voltage and current quality limits, various strategies such as modifying the control methodologies, structural reconfiguration of the grids, etc., are identified as suitable options. The power electronic converters play a significant role in integrating these features to the distribution grid. Unified power quality conditioner (UPQC) is a preferred choice to control quality of both currents and voltages. In this paper, the operation of a meshed hybrid microgrid is realized using UPQC. The DC link of UPQC is used to form a low voltage (LV) DC line. This LVDC line is connected parallel to the LVAC lines. The loads and distribution generation units are integrated to AC and DC lines using power electronic converters. The improved performance during adverse operating conditions show the superior reliability for the proposed system. In addition, the analysis verifies the enhanced capability of the proposed system in accommodating new DC loads to the existing system. Both simulation and experimental results are demonstrated to evaluate the performance of the proposed system.
- 29 January 2025
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Journal of Emerging and Selected Topics in Power Electronics
- Vol. 13 (2) , 2489-2499
A Meshed Hybrid Microgrid Configuration With Unified Power Quality Conditioner
The distribution grid is under major transformation due to the increasing dependency on renewable energy resources (RES) and electric vehicle (EV) charging stations. For accommodating such sources and loads in an existing AC distribution system without violating the voltage and current quality limits, various strategies such as modifying the control methodologies, structural reconfiguration of the grids, etc., are identified as suitable options. The power electronic converters play a significant role in integrating these features to the distribution grid. Unified power quality conditioner (UPQC) is a preferred choice to control quality of both currents and voltages. In this paper, the operation of a meshed hybrid microgrid is realized using UPQC. The DC link of UPQC is used to form a low voltage (LV) DC line. This LVDC line is connected parallel to the LVAC lines. The loads and distribution generation units are integrated to AC and DC lines using power electronic converters. The improved performance during adverse operating conditions show the superior reliability for the proposed system. In addition, the analysis verifies the enhanced capability of the proposed system in accommodating new DC loads to the existing system. Both simulation and experimental results are demonstrated to evaluate the performance of the proposed system.
- 11 July 2023
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Journal of Emerging and Selected Topics in Industrial Electronics
- Vol. 4 (4) , 1255-1264
Stabilization of Smart Transformer Based Islanded Meshed Hybrid Microgrid During Electric Vehicle Charging Transients
Smart transformer (ST) based meshed hybrid microgrid is an attractive solution for interfacing various energy sources and loads, while achieving improved power management features. In the islanded operation of such ST based meshed grid, battery energy storage system (BESS) maintains the low voltage (LV) dc link voltage and acts like a slack bus. During sudden changes in load like charging of electric vehicles (EVs), such a system can become unstable due to slower system response owing to right half plane zero which is inherently present in BESS converters. This paper proposes a method of stabilizing an ST based islanded meshed hybrid microgrid during transients arising from EV charging. To maintain the system stability during such load transients, the meshed nature of the system is exploited by controlling the LVac voltage using ST LV converter operating in grid forming mode. This in turn enables a control of the total load in the LVac grid. The proposed scheme provides a simple yet effective method to stabilize meshed islanded system in-spite of slower system dynamics. The design and stability analysis of the converters are presented to study the system performance with the proposed method. Simulation and experimental results verify the proposed control scheme.
- 11 July 2023
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Journal of Emerging and Selected Topics in Industrial Electronics
- Vol. 4 (4) , 1255-1264
Stabilization of Smart Transformer Based Islanded Meshed Hybrid Microgrid During Electric Vehicle Charging Transients
Smart transformer (ST) based meshed hybrid microgrid is an attractive solution for interfacing various energy sources and loads, while achieving improved power management features. In the islanded operation of such ST based meshed grid, battery energy storage system (BESS) maintains the low voltage (LV) dc link voltage and acts like a slack bus. During sudden changes in load like charging of electric vehicles (EVs), such a system can become unstable due to slower system response owing to right half plane zero which is inherently present in BESS converters. This paper proposes a method of stabilizing an ST based islanded meshed hybrid microgrid during transients arising from EV charging. To maintain the system stability during such load transients, the meshed nature of the system is exploited by controlling the LVac voltage using ST LV converter operating in grid forming mode. This in turn enables a control of the total load in the LVac grid. The proposed scheme provides a simple yet effective method to stabilize meshed islanded system in-spite of slower system dynamics. The design and stability analysis of the converters are presented to study the system performance with the proposed method. Simulation and experimental results verify the proposed control scheme.
- Open Access
- 21 November 2022
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Access
- Vol. 10, 123259-123270
Power Loss Minimization in Smart Transformer Enabled Low Voltage Islanded Meshed Hybrid Microgrid
The smart transformer (ST) offers several features in a hybrid microgrid due to the presence of both ac and dc links while providing various power flow paths. For ST based meshed microgrid, continuous operation is highly important and one of the effective ways to achieve it is by minimizing line losses. This paper proposes a power loss minimization strategy which is specific for an ST based islanded meshed hybrid microgrid. In such an islanded system, a battery energy storage system (BESS) is used for maintaining the low voltage (LV) dc bus voltage of ST. The hybrid microgrid consists of renewable energy sources, electric vehicles (EV) charging stations, storage, etc. The minimization of total distribution line power loss is chosen as objective function of optimization problem. The active power references of distributed generation converters and charge or discharge schedules of EVs are optimally controlled using genetic algorithm while satisfying the various constraints of the system. Further, a smart LV load shedding is also incorporated to the power management. This is activated on crossing the lower critical state of charge of the BESS. It is used as a final measure to increase BESS discharge time resulting in prolonged operation of the islanded system. Simulation and experimental results verify the performance of the proposed scheme. For the various cases considered, the proposed system is compared with conventional power management strategies. It was observed that while in a particular case, the conventional method incurred 1.337 kW losses, the proposed method was able to reduce the line losses to 1.0487 kW. This shows a 22% reduction in line losses with proposed method as compared to conventional method.
- 21 November 2022
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Access
- Vol. 10, 123259-123270
Open AccessPower Loss Minimization in Smart Transformer Enabled Low Voltage Islanded Meshed Hybrid Microgrid
The smart transformer (ST) offers several features in a hybrid microgrid due to the presence of both ac and dc links while providing various power flow paths. For ST based meshed microgrid, continuous operation is highly important and one of the effective ways to achieve it is by minimizing line losses. This paper proposes a power loss minimization strategy which is specific for an ST based islanded meshed hybrid microgrid. In such an islanded system, a battery energy storage system (BESS) is used for maintaining the low voltage (LV) dc bus voltage of ST. The hybrid microgrid consists of renewable energy sources, electric vehicles (EV) charging stations, storage, etc. The minimization of total distribution line power loss is chosen as objective function of optimization problem. The active power references of distributed generation converters and charge or discharge schedules of EVs are optimally controlled using genetic algorithm while satisfying the various constraints of the system. Further, a smart LV load shedding is also incorporated to the power management. This is activated on crossing the lower critical state of charge of the BESS. It is used as a final measure to increase BESS discharge time resulting in prolonged operation of the islanded system. Simulation and experimental results verify the performance of the proposed scheme. For the various cases considered, the proposed system is compared with conventional power management strategies. It was observed that while in a particular case, the conventional method incurred 1.337 kW losses, the proposed method was able to reduce the line losses to 1.0487 kW. This shows a 22% reduction in line losses with proposed method as compared to conventional method.
- 4 November 2021
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 58 (1) , 142-151
Partial Startup Scheme for Smart Transformer in Meshed Hybrid Islanded Grid Operation
Smart transformer (ST)-based low-voltage (LV) meshed hybrid grids provide various power flow paths and ensure continuous power supply to loads. The meshed hybrid microgrid can continue supplying to LV loads even during islanding operation. In such a case, the ST LV converter is operational while its medium voltage (MV) converter as well as the isolated dc–dc converter are shut down. This article proposes a step-by-step startup method for these two converters of the ST to establish reconnection of the meshed hybrid LV microgrid to the MVac grid while keeping the ST LV converter functional. The proposed method involves charging the MVdc bus to 85% of the nominal value from the LVdc bus, which is already energized. Next, the ST MV converter is energized to build the MVdc voltage to the final value. Once it is established, the power flow is started, and the transition from islanded to grid-connected mode of the meshed hybrid microgrid is established. To realize the entire starting process, a centralized controller is proposed. This controller gives the on / off commands to the various converters and circuit breakers in the system as per the proposed partial startup algorithm. Stability studies of the ST isolated dc–dc converter are carried out to ensure that the system maintains stability during the starting process. Simulation studies and experimental validation have been performed to verify the proposed starting scheme.
- 4 November 2021
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 58 (1) , 142-151
Partial Startup Scheme for Smart Transformer in Meshed Hybrid Islanded Grid Operation
Smart transformer (ST)-based low-voltage (LV) meshed hybrid grids provide various power flow paths and ensure continuous power supply to loads. The meshed hybrid microgrid can continue supplying to LV loads even during islanding operation. In such a case, the ST LV converter is operational while its medium voltage (MV) converter as well as the isolated dc–dc converter are shut down. This article proposes a step-by-step startup method for these two converters of the ST to establish reconnection of the meshed hybrid LV microgrid to the MVac grid while keeping the ST LV converter functional. The proposed method involves charging the MVdc bus to 85% of the nominal value from the LVdc bus, which is already energized. Next, the ST MV converter is energized to build the MVdc voltage to the final value. Once it is established, the power flow is started, and the transition from islanded to grid-connected mode of the meshed hybrid microgrid is established. To realize the entire starting process, a centralized controller is proposed. This controller gives the on / off commands to the various converters and circuit breakers in the system as per the proposed partial startup algorithm. Stability studies of the ST isolated dc–dc converter are carried out to ensure that the system maintains stability during the starting process. Simulation studies and experimental validation have been performed to verify the proposed starting scheme.
- 16 December 2020
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-6
Partial Start-up Scheme for ST to Reconnect to MV Grid from LV Side Islanded Operation
This paper proposes a partial start-up procedure for a smart transformer (ST) to changeover from low voltage (LV) side islanded operation to grid connected mode. In the islanded operation of ST LV side, the ST LV converter is operational but the other two converters of the ST namely the ST medium voltage (MV) converter and ST isolated dc-dc converter are shut down. For the reconnection to the MV grid, these converters have to be switched on to enable power flow. Thus while one portion of the ST is already operational, the non-operational parts have to be started without affecting or interrupting the operation of the LV grid. This calls for a proper stage by stage start-up procedure to ensure that the converters become operational maintaining the staring inrush currents within rated limits of the converters. A reverse start up scheme is proposed where the ST MVdc bus is charged by drawing power from the battery energy storage system connected to the LVdc bus. Subsequently the ST MV converter is started to connect the LV side to the MV grid. Simulation results are incorporated which verify the proposed start-up scheme.
- 16 December 2020
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-6
Partial Start-up Scheme for ST to Reconnect to MV Grid from LV Side Islanded Operation
This paper proposes a partial start-up procedure for a smart transformer (ST) to changeover from low voltage (LV) side islanded operation to grid connected mode. In the islanded operation of ST LV side, the ST LV converter is operational but the other two converters of the ST namely the ST medium voltage (MV) converter and ST isolated dc-dc converter are shut down. For the reconnection to the MV grid, these converters have to be switched on to enable power flow. Thus while one portion of the ST is already operational, the non-operational parts have to be started without affecting or interrupting the operation of the LV grid. This calls for a proper stage by stage start-up procedure to ensure that the converters become operational maintaining the staring inrush currents within rated limits of the converters. A reverse start up scheme is proposed where the ST MVdc bus is charged by drawing power from the battery energy storage system connected to the LVdc bus. Subsequently the ST MV converter is started to connect the LV side to the MV grid. Simulation results are incorporated which verify the proposed start-up scheme.
- 8 December 2020
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Electronics
- Vol. 68 (12) , 12364-12374
Increasing Voltage Support Using Smart Power Converter Based Energy Storage System and Load Control
Voltage sag and swell affect the normal operation of loads as well as distributed generating sources and reduce the overall reliability of the system. For improving the voltage at point of common coupling, different grid code requires control of active and reactive powers through power electronic solutions. In this article, a smart power converter (SPC) is introduced in the distribution grid, and different from the existing voltage support solutions, this article utilizes control and coordination capabilities of SPC to provide medium voltage (MV) grid voltage support during voltage sag/swell. The proposed control scheme aims to improve the voltage support capability of SPC in the MV grid by the coordinated operation of SPC MV converter, low voltage converter, and battery energy storage system (BESS). For achieving the same voltage support capability, the proposed method requires lower rated BESS as compared to existing solutions. Simulation and experimental results show the effectiveness of the proposed scheme.
- 8 December 2020
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Electronics
- Vol. 68 (12) , 12364-12374
Increasing Voltage Support Using Smart Power Converter Based Energy Storage System and Load Control
Voltage sag and swell affect the normal operation of loads as well as distributed generating sources and reduce the overall reliability of the system. For improving the voltage at point of common coupling, different grid code requires control of active and reactive powers through power electronic solutions. In this article, a smart power converter (SPC) is introduced in the distribution grid, and different from the existing voltage support solutions, this article utilizes control and coordination capabilities of SPC to provide medium voltage (MV) grid voltage support during voltage sag/swell. The proposed control scheme aims to improve the voltage support capability of SPC in the MV grid by the coordinated operation of SPC MV converter, low voltage converter, and battery energy storage system (BESS). For achieving the same voltage support capability, the proposed method requires lower rated BESS as compared to existing solutions. Simulation and experimental results show the effectiveness of the proposed scheme.
- 15 January 2020
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Electronics
- Vol. 68 (1) , 282-292
Smart Transformer-Enabled Meshed Hybrid Distribution Grid
- 15 January 2020
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Electronics
- Vol. 68 (1) , 282-292
Smart Transformer-Enabled Meshed Hybrid Distribution Grid
- 1 December 2018
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-6
A Flexible and Coordinated Voltage Control Strategy for Smart Transformer
Grid voltage sags are considered to be a critical problem in power distribution system with high penetration of renewable energy resources. These voltage sags propagate through conventional power transformers (CPTs) and affect the normal operation of loads, distributed generating (DG) sources and thereby decreasing the overall reliability of the system. In this paper, a flexible and coordinated control scheme for smart transformer (ST) is proposed to regulate voltage at the medium voltage (MV) grid during both symmetrical and unsymmetrical voltage sags. The proposed scheme improves the reactive power injection capability of ST MV converter by the coordinated control of ST low voltage (LV) converter and battery energy storage system (BESS). This also isolates the ST LVAC side from the grid voltage sags and therefore, the loads and sources connected through ST are unaffected by the MV side faults. Simulation and experimental results are provided to show the efficacy of method.
- 1 December 2018
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-6
A Flexible and Coordinated Voltage Control Strategy for Smart Transformer
Grid voltage sags are considered to be a critical problem in power distribution system with high penetration of renewable energy resources. These voltage sags propagate through conventional power transformers (CPTs) and affect the normal operation of loads, distributed generating (DG) sources and thereby decreasing the overall reliability of the system. In this paper, a flexible and coordinated control scheme for smart transformer (ST) is proposed to regulate voltage at the medium voltage (MV) grid during both symmetrical and unsymmetrical voltage sags. The proposed scheme improves the reactive power injection capability of ST MV converter by the coordinated control of ST low voltage (LV) converter and battery energy storage system (BESS). This also isolates the ST LVAC side from the grid voltage sags and therefore, the loads and sources connected through ST are unaffected by the MV side faults. Simulation and experimental results are provided to show the efficacy of method.
- 1 December 2018
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-7
Smart Transformer-based Hybrid LVAC and LVDC Interconnected Microgrid
Increasing integration of renewable energy sources into the electric grid makes it necessary to develop new efficient solutions for interfacing such sources in the grid. The smart transformer (ST) is a promising solution for such a changing grid scenario. This paper proposes an ST-based hybrid low voltage AC (LVAC) and low voltage DC (LVDC) interconnected microgrid system. The available LVDC link of ST is extended in the distribution grid to realize an LVDC distribution line and the grid connected converters are connected to this proposed LVDC line. The power flow in the proposed system is investigated and a detailed performance comparison between conventional and proposed system is carried out. The proposed restructuring in the distribution grid ensures reduction in ST LV converter size, distribution losses, converter losses and control complexity of the DG converters. This scheme also helps in achieving improved voltage regulation in the LVAC line. Simulation and experimental results verify the proposed scheme.
- 1 December 2018
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-7
Smart Transformer-based Hybrid LVAC and LVDC Interconnected Microgrid
Increasing integration of renewable energy sources into the electric grid makes it necessary to develop new efficient solutions for interfacing such sources in the grid. The smart transformer (ST) is a promising solution for such a changing grid scenario. This paper proposes an ST-based hybrid low voltage AC (LVAC) and low voltage DC (LVDC) interconnected microgrid system. The available LVDC link of ST is extended in the distribution grid to realize an LVDC distribution line and the grid connected converters are connected to this proposed LVDC line. The power flow in the proposed system is investigated and a detailed performance comparison between conventional and proposed system is carried out. The proposed restructuring in the distribution grid ensures reduction in ST LV converter size, distribution losses, converter losses and control complexity of the DG converters. This scheme also helps in achieving improved voltage regulation in the LVAC line. Simulation and experimental results verify the proposed scheme.
- 1 December 2017
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 135-140
Operation and control of smart transformer based distribution grid in a microgrid system
The smart transformer (ST) has been studied extensively in recent years exploring its capabilities in the modern electric grid. Concentrating on the low voltage (LV) side of an ST, this paper proposes a grid structure where a photovoltaic (PV) system and battery energy storage system (BESS) are interfaced to the ST LV DC link. The LV AC grid consists of AC loads and a microgrid with a PV unit and DC loads. Investigation is done on how an ST can achieve proper power management, in addition to carrying out the functions of a conventional transformer on the LV side. A PSCAD simulation of the proposed grid structure is carried out and the operation of the system in the various power flow scenarios is verified. The paper also emphasizes the capability of ST to eliminate the need of other power quality improvement devices in the distribution grid by maintaining the appropriate voltages in the LV grid.
- 1 December 2017
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 135-140
Operation and control of smart transformer based distribution grid in a microgrid system
The smart transformer (ST) has been studied extensively in recent years exploring its capabilities in the modern electric grid. Concentrating on the low voltage (LV) side of an ST, this paper proposes a grid structure where a photovoltaic (PV) system and battery energy storage system (BESS) are interfaced to the ST LV DC link. The LV AC grid consists of AC loads and a microgrid with a PV unit and DC loads. Investigation is done on how an ST can achieve proper power management, in addition to carrying out the functions of a conventional transformer on the LV side. A PSCAD simulation of the proposed grid structure is carried out and the operation of the system in the various power flow scenarios is verified. The paper also emphasizes the capability of ST to eliminate the need of other power quality improvement devices in the distribution grid by maintaining the appropriate voltages in the LV grid.