    The occurrence and mechanism of hysteresis between axial deformation and short‐circuit electromagnetic force during the vibration of power transformer windings

    by Mingkai Jin, Weijie Xu, Weijiang Chen, Qiaogen Zhang, Yi Zhao, Tao Wen

    Mechanical stability is one of the core capabilities of power transformers. External short‐circuit accidents are the main cause of winding instability. International Electrotechnical Commission 60076‐5 standard recommends a method to calculate the short‐circuit strength of power transformer windings by comparing the stress within windings under the effect of the maximum electromagnetic force with the critical stress of the winding. This method assumes that the maximum deformation will be produced by the maximum electromagnetic force, which corresponds to the first peak of the waveform. However, owing to the interactions between disks during the vibration process, the maximum deformation may occur after the occurrence of the maximum electromagnetic force. The hysteresis phenomenon between disk deformation and electromagnetic force is studied. The definition of the hysteresis phenomenon during the vibration process is first demonstrated, and the mechanism of the hysteresis phenomenon is investigated. The vibration model is established. By decoupling analysis, the conditions for the formation of hysteresis are proposed, and the mechanism of the hysteresis phenomenon is validated by the experiment, which is conducted on a winding sample. In the deformation formula, the term that determines the time‐varying characteristic is found. The waveform‐determining term is the difference between the two cosine components, whose frequencies are the natural vibration frequency and the electromagnetic force frequency. When the two frequencies are close, the maximum deformation lags behind the maximum force, and the hysteresis phenomenon occurs.


  • A path of power transformers failure under multiple short-circuit impacts

    by Mingkai Jin, Weijiang Chen, Weijie Xu, Jiaxun Li, Yi Zhao, Qiaogen Zhang, Tao Wen


  • Open Access

    Short‐circuit current difference of parallel strands in winding turns and its influence on the distribution of electromagnetic force

    by Yi Zhao, Jian Si, Mingkai Jin, Tao Wen, Penghong Guo, Weijiang Chen

    Transformer winding turns often consist of multiple parallel strands. The spatial position variation of each strand affects the leakage inductance of each branch, resulting in an uneven distribution of short‐circuit currents within the winding turns. And this unevenness persists even when transposition structures are implemented. Traditional methods in transformer analysis frequently overlooked the distribution characteristics of short‐circuit currents when calculating electromagnetic forces. A frequency‐domain calculation method for analysing the current distribution in winding turns was proposed, with a deviation of less than 3% compared to existing analysis methods. Two typical 110 kV transformer models were utilised to investigate the influence of uneven current distribution on the spatial distribution of electromagnetic forces. The spatial distribution of short‐circuit electromagnetic forces in low‐voltage (LV) windings exhibited significant changes, with maximum change rates of 10% and 61.2% for axial and radial electromagnetic force, respectively, in a LV winding with 4 parallel strands. The research also analysed how strand radial width and axial height affect current distribution unevenness and proposed specific design principles to mitigate these disparities in winding design. The findings offer valuable insights for selecting structural parameters and assessing short‐circuit stability during transformer design.


  • Open Access

    A peak time shifting phenomenon in transformer axial short‐circuit electromagnetic force due to the coupling of electromagnetic‐axial vibration

    by Yi Zhao, Mingkai Jin, Tao Wen, Penghong Guo, Weijiang Chen

    Accurately calculating axial electromagnetic force is essential to analyse transformer winding axial stability. Prior research has mainly focused on the effect of winding structure on static axial electromagnetic force and studying vibration by substituting the static force in a time‐varying function. However, the coupling effect between axial electromagnetic force and winding vibration has not been addressed, and no calculation method for the axial electromagnetic force that considers both winding meso‐structures and vibration coupling effects has been proposed. Previously the authors presented an electromagnetic force calculation model that considers winding structure characteristics, and an iterative algorithm for magnetic‐structure coupling calculation. Currently, the winding vibration model was first proposed and the dynamic calculation method was formulated. By applying the method to a typical 110kV transformer, the spatial‐temporal distribution of winding axial short‐circuit electromagnetic force was obtained. It was found that the peak value of the axial short‐circuit electromagnetic force of some windings appears at the second or third peak moment of the short‐circuit current, which is called as peak time shift phenomenon. Further stress analysis indicates that existing evaluation methods may overestimate the short‐circuit resistance of windings by only considering short‐circuit electromagnetic force under maximum peak of short‐circuit current.


  • Coupled Magnetic-Structural Modeling of Power Transformer for Axial Vibration Analysis Under Short-Circuit Condition

    by Mingkai Jin, Weijiang Chen, Yi Zhao, Tao Wen, Jie Wu, Xingwang Wu, Qiaogen Zhang

    When an external short circuit occurs, the axial electromagnetic force increases dozens of times. Under the effect of the axial short-circuit electromagnetic force, the transformer windings vibrate violently. The spatial distribution of the disks is constantly changing during vibration, which can change the temporal and spatial distributions of the leakage magnetic field and the axial electromagnetic force. This process is called the strong coupling phenomenon of the structural field and the leakage magnetic field. In this article, a strong coupled magnetic-structural model is proposed by using the analysis method. The strong coupling equations, where the independent variables are the axial position of the disks, are obtained. The vibration process with strong coupling phenomenon considered can be obtained. The accuracy of the strong coupling model is verified by the iterative method. By comparing the results calculated by the strong coupling model with those calculated by the weak coupling model, the influence of the strong coupling phenomenon on the vibration process is obtained. Due to the influence of the strong coupling phenomenon, the winding vibration intensity increases and the maximum displacement of the disks can be doubled, which implied that the strong coupling phenomenon cannot be ignored when investigating the short-circuit strength of power transformers.


  • Short-Circuit Electromagnetic Force Distribution Characteristics in Transformer Winding Transposition Structures

    by Yi Zhao, Weijiang Chen, Mingkai Jin, Tao Wen, Jiyin Xue, Qiaogen Zhang, Ming Chen

    For continuous or spiral windings which feature multiple continuously transposed conductors (CTC) wound in parallel, the transposition structure is commonly used to suppress circulation between conductors. This introduces a local asymmetry in transformer windings. Fault analyses have shown that building an asymmetric structure in transformers increases deformation risk in these windings. Researchers have yet to fully investigate this asymmetric structure. This study was conducted to observe the influence of transposition structure in a 110 kV transformer. The conductor's relative position forms three patterns during the transposition process; two parameters are established to describe the position-changing process. A finite-element method (FEM) model is built to investigate the magnetic field and electromagnetic force distributions. The results indicate that the transposition structure distorts the magnetic field distribution. The maximum distortion factor of the axial component of magnetic flux density (B z ) along the axial direction caused by the transposition structure is 14.6%. The transposition structure only changes the radial change slope of B z . The gap caused by the transposition process aggravates imbalance in the ampere-turns distribution, increasing the amplitude of the radial component of magnetic flux density (B r ) at the middle height of the transformer low voltage (LV) winding. The maximum amplitude of B r at the transposition structure increases by 513%. The Lorentz force over the CTCs remains constant from before to after the transposition process, though its linear density over the CTCs is unevenly distributed throughout. The axial component F z varies from -31 to 10 kN/m, while the radial component F r varies from -146 to -51 kN/m. The results show that the initial stage of the CTC height rising segment is a weak point and should be strengthened in the manufacturing process.