Hamidreza Besharatifard
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Hamidreza Besharatifard has a total of 8 co-authors. Here are the top co-authors by number of shared publications:
- Saeed Hasanzadeh
Department of Electrical and Computer Engineering, Qom University of Technology, Qom, Iran
4 shared publications - Ehsan Heydarian-Forushani
Department of Electrical and Computer Engineering Qom University of Technology Qom Iran
2 shared publications - S. M. Muyeen
Qatar University
2 shared publications - Hassan Haes Alhelou
School of Engineering, Massachusetts Institute of Technology (MIT), Cambridge, MA, USA
1 shared publication - Innocent Kamwa
Université Laval
1 shared publication Karen Besharatifard
Qom University of Technology
1 shared publication
Latest Publications
- Open Access
- 27 October 2026
- Published by Wiley
An Interpretable Acoustic Partial Discharge Detection Framework for Oil Filled Power Transformers Using Multiphysics Modeling and Machine Learning
This paper presents an interpretable framework for acoustic partial discharge (PD) detection in oil-filled power transformers by integrating experimental field measurements, physics-based signal modeling, multi-domain feature extraction, and machine learning-based classification. Partial discharge is a critical indicator of insulation degradation, and reliable detection under noisy operating conditions remains a major challenge in transformer condition monitoring. In this study, a hybrid dataset is constructed by synergizing authentic field measurements from high-voltage transformer testbeds with multiphysics finite element simulations. To address the limitations of experimental testing, diverse environmental and operational disturbances are systematically synthesized to emulate realistic, complex noise scenarios. The resulting comprehensive dataset enables robust evaluation of the proposed detection approach. After wavelet-based denoising, each signal is represented using a set of statistical, temporal, spectral, and wavelet domain features. Two complementary descriptors, the Wavelet Scale Centroid (WSC) and the Wavelet Domain Cross Correlation Index (WD CCI), are incorporated to better characterize the energy distribution and structural similarity of transient signals. Classification is performed using a support vector machine (SVM) with probabilistic output, and the decision reliability is further assessed using distance-based validation metrics in the feature space. The results demonstrate that the proposed framework effectively distinguishes PD signals from non-PD disturbances, providing a robust and interpretable solution for transformer condition monitoring. This approach contributes to improving the reliability of acoustic PD diagnostics and supports the development of intelligent monitoring systems for power equipment.
- 27 October 2026
- Published by Wiley
Open AccessAn Interpretable Acoustic Partial Discharge Detection Framework for Oil Filled Power Transformers Using Multiphysics Modeling and Machine Learning
This paper presents an interpretable framework for acoustic partial discharge (PD) detection in oil-filled power transformers by integrating experimental field measurements, physics-based signal modeling, multi-domain feature extraction, and machine learning-based classification. Partial discharge is a critical indicator of insulation degradation, and reliable detection under noisy operating conditions remains a major challenge in transformer condition monitoring. In this study, a hybrid dataset is constructed by synergizing authentic field measurements from high-voltage transformer testbeds with multiphysics finite element simulations. To address the limitations of experimental testing, diverse environmental and operational disturbances are systematically synthesized to emulate realistic, complex noise scenarios. The resulting comprehensive dataset enables robust evaluation of the proposed detection approach. After wavelet-based denoising, each signal is represented using a set of statistical, temporal, spectral, and wavelet domain features. Two complementary descriptors, the Wavelet Scale Centroid (WSC) and the Wavelet Domain Cross Correlation Index (WD CCI), are incorporated to better characterize the energy distribution and structural similarity of transient signals. Classification is performed using a support vector machine (SVM) with probabilistic output, and the decision reliability is further assessed using distance-based validation metrics in the feature space. The results demonstrate that the proposed framework effectively distinguishes PD signals from non-PD disturbances, providing a robust and interpretable solution for transformer condition monitoring. This approach contributes to improving the reliability of acoustic PD diagnostics and supports the development of intelligent monitoring systems for power equipment.
- Open Access
- 17 October 2024
- Published by Institution of Engineering and Technology (IET) in IET Science, Measurement & Technology
- Vol. 18 (9) , 647-666
In situ monitoring of defects in steel structures using a robot‐assisted ultrasonic inspection technique
Incidents in extreme environments can bring unprecedented consequences that would endanger the lives of many humans. Real‐time and early detection of cracks and defects in the steel used for the construction of industrial sites can bring many benefits to remote operators and site managers. Although different methods and systems have been proposed in the past, they are not suitable for real‐time fault detection or long‐term operation in harsh environments. Therefore, this paper proposes a low‐power robotic platform with a magnetic actuator mechanism which is capable of wireless inspection of steel structures using the ultrasonic method. The proposed magnetic motion uses the inertia force generated by the piston vibration and the difference in frictional force during movement. The paper evaluates the performance of the steel structure defect detection system from four different perspectives: sensing principle, wireless communication network, driving part, and power supply.
- 17 October 2024
- Published by Institution of Engineering and Technology (IET) in IET Science, Measurement & Technology
- Vol. 18 (9) , 647-666
Open AccessIn situ monitoring of defects in steel structures using a robot‐assisted ultrasonic inspection technique
Incidents in extreme environments can bring unprecedented consequences that would endanger the lives of many humans. Real‐time and early detection of cracks and defects in the steel used for the construction of industrial sites can bring many benefits to remote operators and site managers. Although different methods and systems have been proposed in the past, they are not suitable for real‐time fault detection or long‐term operation in harsh environments. Therefore, this paper proposes a low‐power robotic platform with a magnetic actuator mechanism which is capable of wireless inspection of steel structures using the ultrasonic method. The proposed magnetic motion uses the inertia force generated by the piston vibration and the difference in frictional force during movement. The paper evaluates the performance of the steel structure defect detection system from four different perspectives: sensing principle, wireless communication network, driving part, and power supply.
- Open Access
- 29 November 2022
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 17 (3) , 706-715
Evaluation of a calibration technique in measuring partial discharges inside mineral oils with a high‐frequency current transformer (HFCT) sensor: A case study
Partial discharge is one of the main reasons for insulation degradation in high‐voltage apparatuses. Partial discharge is an ineluctable phenomenon that happens when a high electrical field is adjacent to an insulator. High‐frequency current transformers are widely used for detecting partial discharge current in high‐voltage equipment. Determination of the apparent charge in pico coulombs is essential for having a common understanding of results and verifying that the measuring system can obtain specified partial discharge magnitude correctly. To this end, a high‐frequency current transformer sensor and a partial discharge calibrator have been prepared to measure the current of the partial discharge (PD) pulses inside mineral oil. The constructed PD calibrator has been evaluated. The high‐frequency current transformer (HFCT) sensor has been simulated using a mathematical model‐based AC analysis and has been characterized and then calibrated using a calibration technique to measure the apparent charge of the PD pulses. Experimental results show the effectiveness of the HFCT sensor and the proposed calibration method.
- 29 November 2022
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 17 (3) , 706-715
Open AccessEvaluation of a calibration technique in measuring partial discharges inside mineral oils with a high‐frequency current transformer (HFCT) sensor: A case study
Partial discharge is one of the main reasons for insulation degradation in high‐voltage apparatuses. Partial discharge is an ineluctable phenomenon that happens when a high electrical field is adjacent to an insulator. High‐frequency current transformers are widely used for detecting partial discharge current in high‐voltage equipment. Determination of the apparent charge in pico coulombs is essential for having a common understanding of results and verifying that the measuring system can obtain specified partial discharge magnitude correctly. To this end, a high‐frequency current transformer sensor and a partial discharge calibrator have been prepared to measure the current of the partial discharge (PD) pulses inside mineral oil. The constructed PD calibrator has been evaluated. The high‐frequency current transformer (HFCT) sensor has been simulated using a mathematical model‐based AC analysis and has been characterized and then calibrated using a calibration technique to measure the apparent charge of the PD pulses. Experimental results show the effectiveness of the HFCT sensor and the proposed calibration method.
- Open Access
- 23 May 2022
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Access
- Vol. 10, 55288-55297
Acoustic Based Localization of Partial Discharge Inside Oil-Filled Transformers
This paper addresses the localization of Partial Discharge through a 3D Finite Element Method analysis of acoustic wave propagation inside a 3-phase 35kV transformer with the help of COMSOL Multiphysics software. Due to the complexity inside transformers, acoustic waves generated by PDs cannot simply be detected with typical acoustic sensors, especially when PDs happen inside inner windings. These waves are distorted and attenuated along with their propagation. The type, number, and position of sensors are essential factors in PD localization inside a transformer. A new installation arrangement of fiber-optic acoustic sensors inside the transformers is proposed with this information. This array of acoustic sensors has significant effects on PD localization accuracy and has immunity from on-site noise and interference; more importantly, they can be installed after transformer manufacturing. They are reachable if needed to be repaired or replaced. Several numerical studies have been carried out considering different PD source positions, and the Levenberge-Marquardt algorithm is employed for solving localization equations.
- 23 May 2022
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Access
- Vol. 10, 55288-55297
Open AccessAcoustic Based Localization of Partial Discharge Inside Oil-Filled Transformers
This paper addresses the localization of Partial Discharge through a 3D Finite Element Method analysis of acoustic wave propagation inside a 3-phase 35kV transformer with the help of COMSOL Multiphysics software. Due to the complexity inside transformers, acoustic waves generated by PDs cannot simply be detected with typical acoustic sensors, especially when PDs happen inside inner windings. These waves are distorted and attenuated along with their propagation. The type, number, and position of sensors are essential factors in PD localization inside a transformer. A new installation arrangement of fiber-optic acoustic sensors inside the transformers is proposed with this information. This array of acoustic sensors has significant effects on PD localization accuracy and has immunity from on-site noise and interference; more importantly, they can be installed after transformer manufacturing. They are reachable if needed to be repaired or replaced. Several numerical studies have been carried out considering different PD source positions, and the Levenberge-Marquardt algorithm is employed for solving localization equations.
- Open Access
- 16 March 2022
- Published by MDPI AG in Applied Sciences
- Vol. 12 (6) , 3010
Detection and Analysis of Partial Discharges in Oil-Immersed Power Transformers Using Low-Cost Acoustic Sensors
Partial Discharge (PD) is one of the symptoms of an electrical insulation problem, and its permanence can lead to the complete deterioration of the electrical insulation in high-voltage equipment such as power transformers. The acoustic emission (AE) method is a well-known technique used to detect and localize PD activity inside oil-filled transformers. However, the commercially available monitoring systems based on acoustic sensors still have a high cost. This paper analyses the ability of low-cost piezoelectric sensors to identify PDs within oil-filled power transformers. To this end, two types of low-cost piezoelectric sensors were fully investigated using time-domain, frequency-domain, and time-frequency analysis, separately. Thereafter, the effectiveness of these sensors for PD detection and monitoring was studied. A three-phase distribution transformer filled with oil was examined. PDs were produced inside an oil-immersed transformer by applying a high voltage over two copper electrodes, and the AE sensors were coupled to the housing of the transformer. By extracting typical features from the AE signals, the PD signals were differentiated from on-site noise and interference. The AE signals were analyzed using acoustic signal metrics such as peak value, energy criterion, and other statistical parameters. The obtained results indicated that the used low-cost piezoelectric sensors have the capability of PD monitoring within power transformers.
- 16 March 2022
- Published by MDPI AG in Applied Sciences
- Vol. 12 (6) , 3010
Open AccessDetection and Analysis of Partial Discharges in Oil-Immersed Power Transformers Using Low-Cost Acoustic Sensors
Partial Discharge (PD) is one of the symptoms of an electrical insulation problem, and its permanence can lead to the complete deterioration of the electrical insulation in high-voltage equipment such as power transformers. The acoustic emission (AE) method is a well-known technique used to detect and localize PD activity inside oil-filled transformers. However, the commercially available monitoring systems based on acoustic sensors still have a high cost. This paper analyses the ability of low-cost piezoelectric sensors to identify PDs within oil-filled power transformers. To this end, two types of low-cost piezoelectric sensors were fully investigated using time-domain, frequency-domain, and time-frequency analysis, separately. Thereafter, the effectiveness of these sensors for PD detection and monitoring was studied. A three-phase distribution transformer filled with oil was examined. PDs were produced inside an oil-immersed transformer by applying a high voltage over two copper electrodes, and the AE sensors were coupled to the housing of the transformer. By extracting typical features from the AE signals, the PD signals were differentiated from on-site noise and interference. The AE signals were analyzed using acoustic signal metrics such as peak value, energy criterion, and other statistical parameters. The obtained results indicated that the used low-cost piezoelectric sensors have the capability of PD monitoring within power transformers.