JZJiawang Zhou

Jiawang Zhou

*This is an algorithmically generated author record based on publicly available information.

Current Organizations / Institutes

The organizations/institutes from the scholar's latest article


Jiawang Zhou has a total of 17 co-authors. Here are the top co-authors by number of shared publications:


Latest Publications

  • Open Access

    Explainability Approach-Based Series Arc Fault Detection Method for Photovoltaic Systems

    by Yao Wang, Jiawang Zhou, Kamal Chandra Paul, Tiefu Zhao, Dejie Sheng

    Arc fault detection devices are mandatory worldwide for mitigating DC series arc faults in photovoltaic systems. However, they are prone to nuisance tripping. Artificial intelligence-based approaches can be a solution, but they are "black boxes" and challenging to modify. This paper proposes an explainability and attention-based method to investigate the intensive details of such an algorithm. The contributions of an arc feature to the proposed model can be visualized by the proposed interpretable methodology so that insensitive arc features can be removed to reduce the quantity of input data. Additionally, the structure of the proposed model can be optimized by cutting the redundant layers. Thus, an accuracy of 99.63% is achieved with only 48.48% of the parameters compared to the original model. Finally, the optimized model is implemented by a Cortex M7-based microprocessor with a runtime of only 7.8 ms, making it ready for industrial application.


  • Open Access

    Arc_EffNet: A Novel Series Arc Fault Detection Method Based on Lightweight Neural Network

    by Xin Ning, Dejie Sheng, Jiawang Zhou, Yuying Liu, Yao Wang, Hua Zhang, Xiao Lei

    Arc faults can cause a severe electric fire, especially series arc faults. Artificial intelligence (AI)-based arc fault detection methods can have a boasted detection accuracy. However, the complexity and large parameter quantity of the AI-based algorithm will hinder its real-time performance for detecting series arc faults. This paper proposes a lightweight arc fault detection method based on the EffNet module, which can make the algorithm less complex with the same detection accuracy level. An arc fault test platform was constructed to collect arc current data, covering eight types of loads required by the IEC 62606 standard. The raw arc current data are used directly as an input for the proposed algorithm, reducing the module’s complexity. According to features of arc current mainly represented in the time domain, the first and last convolution layers of the EffNet module can be improved. Additionally, the spatially separable convolution is well-tuned and trimmed to achieve a more lightweight and better-performance architecture for arc fault detection called Arc_EffNet. Remarkably, this model achieves an impressive arc detection accuracy of 99.75%. An arc fault detection prototype was built using the Raspberry Pi 4B to evaluate the real-time detecting performance of the proposed method. The experimental results show that the prototype takes a time of about 72 ms to respond to a series arc fault, which can fulfill the requirement of real-time detection for arc faults.


  • Open Access

    A DC Arc Fault Detection Method Based on AR Model for Photovoltaic Systems

    by Yao Wang, Xiang Li, Yunsheng Ban, Xiaochen Ma, Chenguang Hao, Jiawang Zhou, Huimao Cai

    DC arc faults are dangerous to photovoltaic (PV) systems and can cause serious electric fire hazards and property damage. Because the PV inverter works in a high−frequency pulse width modulation (PWM) control mode, the arc fault detection is prone to nuisance tripping due to PV inverter noises. An arc fault detection method based on the autoregressive (AR) model is proposed. A test platform collects the database of this research according to the UL1699B standard, in which three different types of PV inverters are taken into consideration to make it more generalized. The arc current can be considered a nonstationary random signal while the noise of the PV inverter is not. According to the difference in randomness features between an arc and the noise, a detection method based on the AR model is proposed. The Burg algorithm is used to determine model coefficients, while the Akaike Information Criterion (AIC) is applied to explore the best order of the proposed model. The correlation coefficient difference of the model coefficients plays a role as a criterion to identify if there is an arc fault. Moreover, a prototype circuit based on the TMS320F28033 MCU is built for algorithm verification. Test results show that the proposed algorithm can identify an arc fault without a false positive under different PV inverter conditions. The fault clearing time is between 60 ms to 80 ms, which can meet the requirement of 200 ms specified by the standard.


  • Open Access

    A Novel Series Arc Fault Detection Method Based on Mel-Frequency Cepstral Coefficients and Fully Connected Neural Network

    by Yao Wang, Dejie Sheng, Haiqing Hu, Kefan Han, Jiawang Zhou, Linming Hou

    Arc faults pose challenges to electric safety, which can cause serious fire hazards. However, the commonly used arc fault detection method is prone to nuisance tripping. This paper proposed a hybrid arc fault detection method based on the improved Mel-Frequency Ceptral Coefficients (MFCC) for preprocessing and a neural network model for arc identification called ARC_MFCC. As per the IEC 62606, twelve different loads/scenarios are considered for this research. An arc tangent-based core filter is employed to improve the MFCC to enhance the arc features within a bandwidth of 3 kHz to 7 kHz. A lightweight neural network model of fully connected cascaded with the MFCC-based preprocessing, which can distinguish the arc fault with normal operation under different test conditions. As a verification result, the ARC_ MFCC can achieve an accuracy of 99.34%. Moreover, the proposed method is implemented by Raspberry pie 4B. Test results show an average running time of about 4.2 ms per sample, which Ensures that the tripping time can meet IEC 62606.