Xingle Gao
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Previous Organizations / Institutes
The organizations / institutes from the scholar's other articles in the past ten years
Xingle Gao has a total of 19 co-authors. Here are the top co-authors by number of shared publications:
- Chang Li
School of Electrical and Automation Engineering, Hefei University of Technology, Hefei, China
3 shared publications - Frede Blaabjerg
Aalborg University
3 shared publications - Yaqian Yang
Department of Electrical Engineering, School of Engineering, Anhui Agricultural University, Hefei, Anhui, China
3 shared publications - Long Cheng
Department of electrical engineering, Anhui Agricultural University, Hefei, China
2 shared publications - Chi Kong Tse
City University of Hong Kong
1 shared publication - Haiyan Zhang
College of Electrical and Information Engineering, Hunan University, Changsha 410082, China
1 shared publication
Latest Publications
- Open Access
- 31 December 2025
- Published by MDPI AG in Technologies
- Vol. 14 (1) , 22
Robustness Assessment of Cyber-Physical Power Systems Considering Cyber Network Performance
The integration of cyber and physical networks in modern power system introduces complex interdependencies that necessitate effective robustness assessment frameworks. In this paper, we propose a novel robustness assessment method for cyber-physical power systems (CPPS), which integrates structural and functional robustness. Firstly, an interdependent dynamic hierarchical network model that accounts for static topological structure, functional attributes and dynamic operational characteristics of cyber-physical power system is established. Based on the model, a probabilistic cascading failure model considering topological connectivity loss, power flow overload, cyber functional failures, and cyber-physical dependence is proposed. The proposed model quantifies the cross-layer impact of cyber-layer impairments (such as communication delay and data loss) on physical-layer operation. Finally, the impacts of cyber network performance and initial failure modes on the robustness of the coupled system are analyzed. The results show that an excellent processing performance and topological connectivity of cyber network can enhance the robustness of the coupled system, and the failure of high-degree nodes is more likely to trigger more severe cascading failure results than the failure of high-betweenness nodes.
- 31 December 2025
- Published by MDPI AG in Technologies
- Vol. 14 (1) , 22
Open AccessRobustness Assessment of Cyber-Physical Power Systems Considering Cyber Network Performance
The integration of cyber and physical networks in modern power system introduces complex interdependencies that necessitate effective robustness assessment frameworks. In this paper, we propose a novel robustness assessment method for cyber-physical power systems (CPPS), which integrates structural and functional robustness. Firstly, an interdependent dynamic hierarchical network model that accounts for static topological structure, functional attributes and dynamic operational characteristics of cyber-physical power system is established. Based on the model, a probabilistic cascading failure model considering topological connectivity loss, power flow overload, cyber functional failures, and cyber-physical dependence is proposed. The proposed model quantifies the cross-layer impact of cyber-layer impairments (such as communication delay and data loss) on physical-layer operation. Finally, the impacts of cyber network performance and initial failure modes on the robustness of the coupled system are analyzed. The results show that an excellent processing performance and topological connectivity of cyber network can enhance the robustness of the coupled system, and the failure of high-degree nodes is more likely to trigger more severe cascading failure results than the failure of high-betweenness nodes.
- 4 September 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Electronics
- Vol. 72 (3) , 3233-3240
A New Perspective for Frequency and DC Voltage Stability Comprehension in Two-Terminal VSC-HVDC Systems With Virtual Inertia Control
This letter proposes a new perspective for the interactive stability mechanism between frequency and dc voltage in a voltage-source converter-based high-voltage direct current (VSC-HVDC) system with virtual inertia control. The system model is first established, providing a new physical insight into dc voltage and frequency stability. It is found that the frequency instability may be caused by the control loop of virtual inertia or the oscillation transfer of dc voltage. Similarly, the dc voltage oscillation can be induced by the inappropriate design of dc voltage control loop or the transfer of the frequency. The complex oscillation coupling mechanism as well as the oscillation transfer essence is clarified physically. Finally, the correctness as well as the feasibility of the theoretical analysis is verified by the hardware-in-loop experiment.
- 4 September 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Electronics
- Vol. 72 (3) , 3233-3240
A New Perspective for Frequency and DC Voltage Stability Comprehension in Two-Terminal VSC-HVDC Systems With Virtual Inertia Control
This letter proposes a new perspective for the interactive stability mechanism between frequency and dc voltage in a voltage-source converter-based high-voltage direct current (VSC-HVDC) system with virtual inertia control. The system model is first established, providing a new physical insight into dc voltage and frequency stability. It is found that the frequency instability may be caused by the control loop of virtual inertia or the oscillation transfer of dc voltage. Similarly, the dc voltage oscillation can be induced by the inappropriate design of dc voltage control loop or the transfer of the frequency. The complex oscillation coupling mechanism as well as the oscillation transfer essence is clarified physically. Finally, the correctness as well as the feasibility of the theoretical analysis is verified by the hardware-in-loop experiment.
- 9 July 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Informatics
- Vol. 20 (10) , 12328-12338
Self-Stability and Induced-Stability Analysis for Frequency and Voltage in Grid-Forming VSG System With Generic Magnitude–Phase Model
The frequency and voltage stability of grid-forming virtual synchronous generator (GFM-VSG) grid-tied system becomes significant in inertia and damping support when GFM-VSG is attached to the power network. In this article, we propose a generic open-loop system model for the frequency–voltage induced-stability analysis, where the dynamics of rate of change of frequency (RoCoF) is a dynamic process that acts on the rate of change of voltage and then, in turn, reacts on RoCoF. In addition, frequency self-stability is evaluated by magnitude–phase feedback analytical model, where the frequency dynamics are identified by the interaction between RoCoF and frequency bias (FB). Also, it is found that inertia is the origin of occurrence of low-frequency oscillation, which induces a natural phase bias between RoCoF and FB. It is found that GFM-VSG can operate stably in weak grid but cannot operate well in ultrastrong grid condition. Finally, theoretical analysis is validated by simulations and experiments.
- 9 July 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Informatics
- Vol. 20 (10) , 12328-12338
Self-Stability and Induced-Stability Analysis for Frequency and Voltage in Grid-Forming VSG System With Generic Magnitude–Phase Model
The frequency and voltage stability of grid-forming virtual synchronous generator (GFM-VSG) grid-tied system becomes significant in inertia and damping support when GFM-VSG is attached to the power network. In this article, we propose a generic open-loop system model for the frequency–voltage induced-stability analysis, where the dynamics of rate of change of frequency (RoCoF) is a dynamic process that acts on the rate of change of voltage and then, in turn, reacts on RoCoF. In addition, frequency self-stability is evaluated by magnitude–phase feedback analytical model, where the frequency dynamics are identified by the interaction between RoCoF and frequency bias (FB). Also, it is found that inertia is the origin of occurrence of low-frequency oscillation, which induces a natural phase bias between RoCoF and FB. It is found that GFM-VSG can operate stably in weak grid but cannot operate well in ultrastrong grid condition. Finally, theoretical analysis is validated by simulations and experiments.
- 27 December 2023
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Electronics
- Vol. 71 (9) , 10908-10918
A Generic Power Compensation Control for Grid Forming Virtual Synchronous Generator With Damping Correction Loop
Insufficient damping and inertia are the one of the most tough challenges in the grid-connected power system with high penetration of renewable energy resources. Damping correction loop of virtual synchronous generator (VSG) connected to weak damping and high R/X ratio condition is introduced to solve the issues. First, the scheme of the proposed control is implemented in various system operating conditions, and the small-signal model of the proposed control is established. Subsequently, the influence of the damping correction loop on small-signal stability is demonstrated by Bode diagram analysis, and the interaction between reshaped VSG control and power compensation capacity is clarified in three aspects of damping, inertia and synchronization. Furthermore, the optimal design of additional damping and inertia support is provided to suppress the subsynchronous frequency fluctuation of the system, the proposed control method can be easily implemented by directly inserting it into active power control loop of VSG. Finally, the efficiency of the damping correction loop is verified by experiments, the results indicate that 70% reduction of maximum frequency deviation with the proposed control under 20% active power reference step.
- 27 December 2023
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Electronics
- Vol. 71 (9) , 10908-10918
A Generic Power Compensation Control for Grid Forming Virtual Synchronous Generator With Damping Correction Loop
Insufficient damping and inertia are the one of the most tough challenges in the grid-connected power system with high penetration of renewable energy resources. Damping correction loop of virtual synchronous generator (VSG) connected to weak damping and high R/X ratio condition is introduced to solve the issues. First, the scheme of the proposed control is implemented in various system operating conditions, and the small-signal model of the proposed control is established. Subsequently, the influence of the damping correction loop on small-signal stability is demonstrated by Bode diagram analysis, and the interaction between reshaped VSG control and power compensation capacity is clarified in three aspects of damping, inertia and synchronization. Furthermore, the optimal design of additional damping and inertia support is provided to suppress the subsynchronous frequency fluctuation of the system, the proposed control method can be easily implemented by directly inserting it into active power control loop of VSG. Finally, the efficiency of the damping correction loop is verified by experiments, the results indicate that 70% reduction of maximum frequency deviation with the proposed control under 20% active power reference step.
- 8 April 2021
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Circuits and Systems II: Express Briefs
- Vol. 70 (1) , 136-140
Cascading Failure Analysis of Cyber–Physical Power Systems Considering Routing Strategy
In this brief, we develop a novel model to study the cascading failure in cyber-physical power systems. We use a discrete packet traffic model that follows a specific routing strategy to describe the dynamic data transmission in the information network. Moreover, the dynamic load flow model that takes into account the power-frequency characteristics of loads and generators is applied to describe the dynamic flow process of the power network. Our proposed model allows to consider the impacts of data packet transmission failures and voltage-related failures in the cascading process. Furthermore, we analyze the effects of routing strategy and information network topology on the severity of cascading failure. Simulation results verify the applicability of the proposed model and reveal the way in which routing strategy affects the cascading failure of cyber-coupled systems. In addition, we show that when the main hub in the information network is used as a dispatching center, a spreadout degree distribution of the information network reduces the severity of cascading failure in the cyber-coupled system.
- 8 April 2021
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Circuits and Systems II: Express Briefs
- Vol. 70 (1) , 136-140
Cascading Failure Analysis of Cyber–Physical Power Systems Considering Routing Strategy
In this brief, we develop a novel model to study the cascading failure in cyber-physical power systems. We use a discrete packet traffic model that follows a specific routing strategy to describe the dynamic data transmission in the information network. Moreover, the dynamic load flow model that takes into account the power-frequency characteristics of loads and generators is applied to describe the dynamic flow process of the power network. Our proposed model allows to consider the impacts of data packet transmission failures and voltage-related failures in the cascading process. Furthermore, we analyze the effects of routing strategy and information network topology on the severity of cascading failure. Simulation results verify the applicability of the proposed model and reveal the way in which routing strategy affects the cascading failure of cyber-coupled systems. In addition, we show that when the main hub in the information network is used as a dispatching center, a spreadout degree distribution of the information network reduces the severity of cascading failure in the cyber-coupled system.
- Open Access
Modelling and Vulnerability Analysis of Cyber-Physical Power Systems Based on Interdependent Networks
The strong coupling between the power grid and communication systems may contribute to failure propagation, which may easily lead to cascading failures or blackouts. In this paper, in order to quantitatively analyse the impact of interdependency on power system vulnerability, we put forward a “degree–electrical degree” independent model of cyber-physical power systems (CPPS), a new type of assortative link, through identifying the important nodes in a power grid based on the proposed index–electrical degree, and coupling them with the nodes in a communication system with a high degree, based on one-to-one correspondence. Using the double-star communication system and the IEEE 118-bus power grid to form an artificial interdependent network, we evaluated and compare the holistic vulnerability of CPPS under random attack and malicious attack, separately based on three kinds of interdependent models: “degree–betweenness”, “degree–electrical degree” and “random link”. The simulation results demonstrated that different link patterns, coupling degrees and attack types all can influence the vulnerability of CPPS. The CPPS with a “degree–electrical degree” interdependent model proposed in this paper presented a higher robustness in the face of random attack, and moreover performed better than the degree–betweenness interdependent model in the face of malicious attack.
Open AccessModelling and Vulnerability Analysis of Cyber-Physical Power Systems Based on Interdependent Networks
The strong coupling between the power grid and communication systems may contribute to failure propagation, which may easily lead to cascading failures or blackouts. In this paper, in order to quantitatively analyse the impact of interdependency on power system vulnerability, we put forward a “degree–electrical degree” independent model of cyber-physical power systems (CPPS), a new type of assortative link, through identifying the important nodes in a power grid based on the proposed index–electrical degree, and coupling them with the nodes in a communication system with a high degree, based on one-to-one correspondence. Using the double-star communication system and the IEEE 118-bus power grid to form an artificial interdependent network, we evaluated and compare the holistic vulnerability of CPPS under random attack and malicious attack, separately based on three kinds of interdependent models: “degree–betweenness”, “degree–electrical degree” and “random link”. The simulation results demonstrated that different link patterns, coupling degrees and attack types all can influence the vulnerability of CPPS. The CPPS with a “degree–electrical degree” interdependent model proposed in this paper presented a higher robustness in the face of random attack, and moreover performed better than the degree–betweenness interdependent model in the face of malicious attack.