Bao Doan Thanh
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Bao Doan Thanh has a total of 18 co-authors. Here are the top co-authors by number of shared publications:
- Vuong Dang Quoc
Hanoi University of Science and Technology
3 shared publications - Tuan-Ho Le
Quy Nhon University
2 shared publications - Dinh Bui Minh
School of Electrical Engineering, Hanoi University of Science and Technology, Vietnam
1 shared publication - Dinh Duong Le
University of Science and Technology, The University of Danang
1 shared publication - Doan Duc Tung
Faculty of Engineering and Technology, Quy Nhon University, Binh Dinh, Vietnam
1 shared publication - Duc-Quang Nguyen
Electric Power University,Department of Electrical Engineering,Hanoi,Vietnam
1 shared publication
Latest Publications
- Open Access
- 27 May 2026
- Published by Hanoi University of Science and Technology in Smart Systems and Devices
- Vol. 36 (3) , 038-047
Thermal Effects of Harmonics on Distribution Transformers: A Coupled Electromagnetic–Thermal Finite-Element-Based Approach
The growing demand for electrical energy, together with increasingly complex operating conditions caused by nonlinear loads and the widespread integration of renewable energy sources, has led to increased harmonic distortion in power systems. As critical assets in distribution networks, transformers are particularly vulnerable to harmonic-induced losses and thermal stress, which can accelerate insulation aging and reduce service life. This study investigates the thermal effects of harmonics on a medium-voltage distribution transformer using a coupled electromagnetic–thermal approach based on the finite element method. In the proposed workflow, ANSYS Maxwell is used to compute electromagnetic quantities and harmonic-dependent losses, and these losses are then used as inputs to an equivalent electro-thermal model to predict top-oil and winding hot-spot temperatures. The electromagnetic model is validated under no-load and short-circuit conditions, and simulations are conducted for linear and nonlinear loads at 50%, 100%, and 125% of rated load. The hybrid thermal prediction results show good agreement with detailed ANSYS Mechanical simulations, with a deviation of approximately 3% in the linear-load case and 0.016% in the nonlinear-load case. The results show that harmonic loading significantly increases load-related losses and hot-spot temperature, while also revealing a non-uniform temperature distribution that enables hot-spot localization. The obtained spatial hot-spot information supports insulation loss-of-life assessment and provides practical guidance for design improvement, sensor placement, periodic inspection/testing, spare-part planning, and condition-based maintenance under harmonic operating conditions.
- 27 May 2026
- Published by Hanoi University of Science and Technology in Smart Systems and Devices
- Vol. 36 (3) , 038-047
Open AccessThermal Effects of Harmonics on Distribution Transformers: A Coupled Electromagnetic–Thermal Finite-Element-Based Approach
The growing demand for electrical energy, together with increasingly complex operating conditions caused by nonlinear loads and the widespread integration of renewable energy sources, has led to increased harmonic distortion in power systems. As critical assets in distribution networks, transformers are particularly vulnerable to harmonic-induced losses and thermal stress, which can accelerate insulation aging and reduce service life. This study investigates the thermal effects of harmonics on a medium-voltage distribution transformer using a coupled electromagnetic–thermal approach based on the finite element method. In the proposed workflow, ANSYS Maxwell is used to compute electromagnetic quantities and harmonic-dependent losses, and these losses are then used as inputs to an equivalent electro-thermal model to predict top-oil and winding hot-spot temperatures. The electromagnetic model is validated under no-load and short-circuit conditions, and simulations are conducted for linear and nonlinear loads at 50%, 100%, and 125% of rated load. The hybrid thermal prediction results show good agreement with detailed ANSYS Mechanical simulations, with a deviation of approximately 3% in the linear-load case and 0.016% in the nonlinear-load case. The results show that harmonic loading significantly increases load-related losses and hot-spot temperature, while also revealing a non-uniform temperature distribution that enables hot-spot localization. The obtained spatial hot-spot information supports insulation loss-of-life assessment and provides practical guidance for design improvement, sensor placement, periodic inspection/testing, spare-part planning, and condition-based maintenance under harmonic operating conditions.
- Open Access
- 31 July 2025
- Published by Korean Institute of Electromagnetic Engineering and Science in Journal of Electromagnetic Engineering and Science
- Vol. 25 (4) , 361-370
A Combinatory Analytical and Finite Element Approach for Comparing Electromagnetic Performance in IPM and SPM Synchronous Motors
Permanent magnet synchronous motors (PMSMs) have been extensively adopted in a range of industrial applications, particularly in the electric vehicle industry, due to their high power and torque density, high efficiency, reliability, and excellent dynamic performance. Between the types of PMSMs, a surface-mounted PMSM (SPMSM) is characterized by identical d- and q-inductances, due to which it only generates magnetic torque. However, SPMSMs also exhibit higher flux density, since the air gap in these motors is smaller and the permanent magnets are located very close to the stator teeth. In contrast, an interior PMSM (IPMSMs) features different d-axis and q-axis inductance components, due to which it can create not only magnetic torque but also reluctance torque. In this paper, two processes are conducted to examine these motors. First, an analytical technique is proposed to design the required parameters for an SPMSM and an IPMSM, where the dimensions of the latter are defined using the fractional-slot concentrated winding configuration, and those of the former are designed based on the approach of keeping the rotor volume, permanent magnet volume, pole–slot combination, and power supply unchanged. Subsequently, a finite element method is presented for computing, simulating, and comparing the electromagnetic parameters of both proposed motors, including their back electromotive force, torque ripple, efficiency, and power factor. Finally, the proposed methods are validated using a 7.5 kW practical motor.
- 31 July 2025
- Published by Korean Institute of Electromagnetic Engineering and Science in Journal of Electromagnetic Engineering and Science
- Vol. 25 (4) , 361-370
Open AccessA Combinatory Analytical and Finite Element Approach for Comparing Electromagnetic Performance in IPM and SPM Synchronous Motors
Permanent magnet synchronous motors (PMSMs) have been extensively adopted in a range of industrial applications, particularly in the electric vehicle industry, due to their high power and torque density, high efficiency, reliability, and excellent dynamic performance. Between the types of PMSMs, a surface-mounted PMSM (SPMSM) is characterized by identical d- and q-inductances, due to which it only generates magnetic torque. However, SPMSMs also exhibit higher flux density, since the air gap in these motors is smaller and the permanent magnets are located very close to the stator teeth. In contrast, an interior PMSM (IPMSMs) features different d-axis and q-axis inductance components, due to which it can create not only magnetic torque but also reluctance torque. In this paper, two processes are conducted to examine these motors. First, an analytical technique is proposed to design the required parameters for an SPMSM and an IPMSM, where the dimensions of the latter are defined using the fractional-slot concentrated winding configuration, and those of the former are designed based on the approach of keeping the rotor volume, permanent magnet volume, pole–slot combination, and power supply unchanged. Subsequently, a finite element method is presented for computing, simulating, and comparing the electromagnetic parameters of both proposed motors, including their back electromotive force, torque ripple, efficiency, and power factor. Finally, the proposed methods are validated using a 7.5 kW practical motor.
- Open Access
- 1 December 2024
- Published by Institute of Advanced Engineering and Science in International Journal of Power Electronics and Drive Systems (IJPEDS)
- Vol. 15 (4) , 2105-2114
Design comparison of surface-mounted permanent magnet synchronous motors with inner and outer rotor configurations
The surface-mounted permanent magnet synchronous motor (SPMSM) is one of the electric machines applied widely in the fields of electric vehicles (EVs) and electrical drives due to their good characteristics such as high power density, lower mass, high efficiency, and lower torque. For the SPMSM, there are two types of SPMSM, i.e., the inner rotor SPMSM and the outer rotor SPMSM. To analyze and compute advantages and disadvantages, as well as to compare the performances of these two motor types, this research proposes an analytical model to design preliminarily the main/required parameters of the SPMSM with inner and outer rotor types. Subsequently, a finite element method is developed to simulate, analyze, and compare the electromagnetic parameters of the proposed motors. Via the developed methods, the obtained results will also indicate the performances of both types of motors. In particular, it will provide a good recommendation for choosing the SPMSM with an inner or outer rotor structure for traction applications.
- 1 December 2024
- Published by Institute of Advanced Engineering and Science in International Journal of Power Electronics and Drive Systems (IJPEDS)
- Vol. 15 (4) , 2105-2114
Open AccessDesign comparison of surface-mounted permanent magnet synchronous motors with inner and outer rotor configurations
The surface-mounted permanent magnet synchronous motor (SPMSM) is one of the electric machines applied widely in the fields of electric vehicles (EVs) and electrical drives due to their good characteristics such as high power density, lower mass, high efficiency, and lower torque. For the SPMSM, there are two types of SPMSM, i.e., the inner rotor SPMSM and the outer rotor SPMSM. To analyze and compute advantages and disadvantages, as well as to compare the performances of these two motor types, this research proposes an analytical model to design preliminarily the main/required parameters of the SPMSM with inner and outer rotor types. Subsequently, a finite element method is developed to simulate, analyze, and compare the electromagnetic parameters of the proposed motors. Via the developed methods, the obtained results will also indicate the performances of both types of motors. In particular, it will provide a good recommendation for choosing the SPMSM with an inner or outer rotor structure for traction applications.
- Open Access
- 20 March 2024
- Published by Can Tho University in CTU Journal of Innovation and Sustainable Development
- Vol. 16 (1) , 66-75
Calculation of electromagnetic force and temperature distribution of amorphous transformers in different operating modes by finite element method
The study used the Finite element method (FEM) by ANSYS 3D software to calculate the distribution of electromagnetic force (EMF) and temperature on the high voltage and low voltage windings (HLVWs) of the amorphous steel core 3 phase transformer (ASCT) which has a power of 1000kVA –22/0.4kV under different load cases: No load, full load and short circuit (SC). The obtained results show the exact temperature distribution and location where the highest temperature is found on the HLVWs of ASCT. From the analysis of the temperature distribution on the HLVWs, it is shown that when the transformer falls into an SC fault, it causes the greatest EMF and thermodynamic force, causing extremely heavy consequences for the transformers. The obtained results help designers, manufacturers, and operators have the most suitable options to improve strength of SC and increase the life of the transformer.
- 20 March 2024
- Published by Can Tho University in CTU Journal of Innovation and Sustainable Development
- Vol. 16 (1) , 66-75
Open AccessCalculation of electromagnetic force and temperature distribution of amorphous transformers in different operating modes by finite element method
The study used the Finite element method (FEM) by ANSYS 3D software to calculate the distribution of electromagnetic force (EMF) and temperature on the high voltage and low voltage windings (HLVWs) of the amorphous steel core 3 phase transformer (ASCT) which has a power of 1000kVA –22/0.4kV under different load cases: No load, full load and short circuit (SC). The obtained results show the exact temperature distribution and location where the highest temperature is found on the HLVWs of ASCT. From the analysis of the temperature distribution on the HLVWs, it is shown that when the transformer falls into an SC fault, it causes the greatest EMF and thermodynamic force, causing extremely heavy consequences for the transformers. The obtained results help designers, manufacturers, and operators have the most suitable options to improve strength of SC and increase the life of the transformer.
- Open Access
- 25 July 2023
- Published by Institute of Advanced Engineering and Science in International Journal of Applied Power Engineering (IJAPE)
- Vol. 12 (3) , 321-330
A 3D model of three phase shunt reactors by using a finite element technique with coupling to global quantities
The finite element technique is used widely for researchers and manufacturers to design and simulate electrical systems in general and electrical machines such as shunt reactors (SRs) and transformers in particular. Many papers have recently applied several methods to analyze magnetic fields, copper losses and joule power losses in the shunt reactors (SRs). In this research, the finite element technique with coupling to global quantities is proposed to investigate the voltage and current distributions in the windings, and compute the distribution of magnetic field in the air gap and along the air core of the SR, as well as copper and core losses. The developed method is directly applied to the practical SR of 91 MVAr and a rated voltage of 500 kV. The finite element method (FEM)-simulated results are validated with experimental results to ensure accuracy and reliability. This facilitate designing the reactor.
- 25 July 2023
- Published by Institute of Advanced Engineering and Science in International Journal of Applied Power Engineering (IJAPE)
- Vol. 12 (3) , 321-330
Open AccessA 3D model of three phase shunt reactors by using a finite element technique with coupling to global quantities
The finite element technique is used widely for researchers and manufacturers to design and simulate electrical systems in general and electrical machines such as shunt reactors (SRs) and transformers in particular. Many papers have recently applied several methods to analyze magnetic fields, copper losses and joule power losses in the shunt reactors (SRs). In this research, the finite element technique with coupling to global quantities is proposed to investigate the voltage and current distributions in the windings, and compute the distribution of magnetic field in the air gap and along the air core of the SR, as well as copper and core losses. The developed method is directly applied to the practical SR of 91 MVAr and a rated voltage of 500 kV. The finite element method (FEM)-simulated results are validated with experimental results to ensure accuracy and reliability. This facilitate designing the reactor.
- 19 June 2023
- Published by Polish Academy of Sciences Chancellery in Archives of Electrical Engineering
- Vol. 72 (2) , 521-539
Computation of electromagnetic forces in the windings of amorphous core transformers
Electromagnetic forces generated by the short circuit current and leakage flux in low- and high-voltage windings of distribution transformers as well as amorphous core transformers will cause the translation, destruction, and explosion of the windings. Thus, the investigation of these forces plays a significant role for researchers and manufacturers. Many authors have recently used the finite element method to analyze electromagnetic forces. In this paper, an analytic model is first developed for magnetic vector potential formulations to compute the electromagnetic forces (i.e., axial and radial forces) acting on the low- and high-voltage windings of an amorphous core transformer. The finite element technique is then presented to validate the results obtained from the analytical model. The developed model is applied to an actual problem.
- 19 June 2023
- Published by Polish Academy of Sciences Chancellery in Archives of Electrical Engineering
- Vol. 72 (2) , 521-539
Computation of electromagnetic forces in the windings of amorphous core transformers
Electromagnetic forces generated by the short circuit current and leakage flux in low- and high-voltage windings of distribution transformers as well as amorphous core transformers will cause the translation, destruction, and explosion of the windings. Thus, the investigation of these forces plays a significant role for researchers and manufacturers. Many authors have recently used the finite element method to analyze electromagnetic forces. In this paper, an analytic model is first developed for magnetic vector potential formulations to compute the electromagnetic forces (i.e., axial and radial forces) acting on the low- and high-voltage windings of an amorphous core transformer. The finite element technique is then presented to validate the results obtained from the analytical model. The developed model is applied to an actual problem.
- Open Access
- 1 June 2023
- Published by Institute of Advanced Engineering and Science in International Journal of Power Electronics and Drive Systems (IJPEDS)
- Vol. 14 (2) , 1238-1248
Impact of large-scale renewable power plants on the tie-line loadings of a Vietnamese power network
The rapid integration of wind power and power solar plants into the electrical power system has caused several operation issues in recent decades. To investigate the impact of large-scale renewable power plants on the tie-line loadings of a practical power grid, the 110 kV power network of Binh Dinh province, Vietnam is utilized in this paper. This power network with and without three solar power plants (including Fujiwara plant with a peak capacity of 50 MWp, Cat Hiep plant with a peak capacity of 49.5 MWp, and Dam Tra O plant with a peak capacity of 50 MWp) and three wind power plants (including Nhon Hoi plant with a capacity of 60MW, Phuong Mai 1 plant with a capacity of 26.4 MW, and Phuong Mai 3 plant with a capacity of 20.7 MW) is modeled by using the PSS/E software to examine the tie-line loadings capacity. The simulation results showed that the tie-line loadings of the current power network increase when six renewable power plants are integrated into this network. Therefore, three different scenarios to upgrade the existing power network are proposed. The final results demonstrated the efficiency of the proposed scenarios in solving the tie-line loadings issue of the practical power network.
- 1 June 2023
- Published by Institute of Advanced Engineering and Science in International Journal of Power Electronics and Drive Systems (IJPEDS)
- Vol. 14 (2) , 1238-1248
Open AccessImpact of large-scale renewable power plants on the tie-line loadings of a Vietnamese power network
The rapid integration of wind power and power solar plants into the electrical power system has caused several operation issues in recent decades. To investigate the impact of large-scale renewable power plants on the tie-line loadings of a practical power grid, the 110 kV power network of Binh Dinh province, Vietnam is utilized in this paper. This power network with and without three solar power plants (including Fujiwara plant with a peak capacity of 50 MWp, Cat Hiep plant with a peak capacity of 49.5 MWp, and Dam Tra O plant with a peak capacity of 50 MWp) and three wind power plants (including Nhon Hoi plant with a capacity of 60MW, Phuong Mai 1 plant with a capacity of 26.4 MW, and Phuong Mai 3 plant with a capacity of 20.7 MW) is modeled by using the PSS/E software to examine the tie-line loadings capacity. The simulation results showed that the tie-line loadings of the current power network increase when six renewable power plants are integrated into this network. Therefore, three different scenarios to upgrade the existing power network are proposed. The final results demonstrated the efficiency of the proposed scenarios in solving the tie-line loadings issue of the practical power network.