Greg Shoukas
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Greg Shoukas has a total of 6 co-authors. Here are the top co-authors by number of shared publications:
Ian Doebber
National Renewable Energy Laboratory (NREL), Golden, CO (United States)
1 shared publicationJal Desai
National Renewable Energy Laboratory (NREL), Golden, CO (United States)
1 shared publicationJimmy Salasovich
National Renewable Energy Laboratory (NREL), Golden, CO (United States)
1 shared publication- Jon Winkler
National Laboratory of the Rockies, Golden, CO 80401, USA
1 shared publication Khanh Nguyen Cu
National Renewable Energy Laboratory (NREL), Golden, CO (United States)
1 shared publicationUsdod
1 shared publication
Latest Publications
- Open Access
- 9 September 2025
- Published by Office of Scientific and Technical Information (OSTI)
Laboratory Testing and Performance Characterization of the High Efficiency Dehumidification System (HEDS) Technology
The high efficiency dehumidification system (HEDS) is a unique air handling unit (AHU) design with two water coils. Connected in series, these water coils can sensibly reheat the airstream after it is cooled and dehumidified, thereby mitigating (or sometimes eliminating) the need for conventional sensible reheat with additional energy from hot water, electric resistance or steam coils. Another unique design feature is the size of the HEDS primary cooling coil. While typical AHU cooling coils have a 6-row geometry, the HED's cooling coil has a deeper 10-row geometry enabling discharge air dew point temperatures at or below 55 degrees F despite warmer chilled water supply temperatures approaching (sometimes exceeding) 50 degrees F. The ability to meet acceptable discharge air dew points with warmer chilled water supply temperatures improves both operational efficiency and system resilience against chilled water plant operational or control issues. This report summarizes the 59 steady-state test results that form a comprehensive performance map of the HEDS technology including its reheat capability. The breadth of outdoor air conditions and flow rates over which the HEDS technology was tested and characterized encompasses the unit 1) operating as a dedicated outdoor air system or mixed air system and 2) controlled with constant air volume or variable air volume fan control.
- 9 September 2025
- Published by Office of Scientific and Technical Information (OSTI)
Open AccessLaboratory Testing and Performance Characterization of the High Efficiency Dehumidification System (HEDS) Technology
The high efficiency dehumidification system (HEDS) is a unique air handling unit (AHU) design with two water coils. Connected in series, these water coils can sensibly reheat the airstream after it is cooled and dehumidified, thereby mitigating (or sometimes eliminating) the need for conventional sensible reheat with additional energy from hot water, electric resistance or steam coils. Another unique design feature is the size of the HEDS primary cooling coil. While typical AHU cooling coils have a 6-row geometry, the HED's cooling coil has a deeper 10-row geometry enabling discharge air dew point temperatures at or below 55 degrees F despite warmer chilled water supply temperatures approaching (sometimes exceeding) 50 degrees F. The ability to meet acceptable discharge air dew points with warmer chilled water supply temperatures improves both operational efficiency and system resilience against chilled water plant operational or control issues. This report summarizes the 59 steady-state test results that form a comprehensive performance map of the HEDS technology including its reheat capability. The breadth of outdoor air conditions and flow rates over which the HEDS technology was tested and characterized encompasses the unit 1) operating as a dedicated outdoor air system or mixed air system and 2) controlled with constant air volume or variable air volume fan control.
- 15 May 2024
- Published by Office of Scientific and Technical Information (OSTI)
Cold Climate Air-Source Heat Pump Demonstration and Analysis: Experimental Study on Cold Temperature Performance
Under Technical Service Agreement TSA-21-17917 with Xcel Energy, NREL conducted laboratory and field research activities to evaluate the performance of current residential ASHP technologies in support of Xcel Energy's carbon-free electricity goals. Results from this research will be used by Xcel Energy to understand the impacts that equipment, environment, and installation choices have on field operation and performance of residential air-source heat pumps. This report focuses on the laboratory experiments. The overall goal of the laboratory evaluation was to measure heat pump performance under a range of real-world heating mode operating conditions. Laboratory characterization was completed on one centrally ducted heat pump and one two-zone MSHP (i.e. a multi-split heat pump).
- 15 May 2024
- Published by Office of Scientific and Technical Information (OSTI)
Cold Climate Air-Source Heat Pump Demonstration and Analysis: Experimental Study on Cold Temperature Performance
Under Technical Service Agreement TSA-21-17917 with Xcel Energy, NREL conducted laboratory and field research activities to evaluate the performance of current residential ASHP technologies in support of Xcel Energy's carbon-free electricity goals. Results from this research will be used by Xcel Energy to understand the impacts that equipment, environment, and installation choices have on field operation and performance of residential air-source heat pumps. This report focuses on the laboratory experiments. The overall goal of the laboratory evaluation was to measure heat pump performance under a range of real-world heating mode operating conditions. Laboratory characterization was completed on one centrally ducted heat pump and one two-zone MSHP (i.e. a multi-split heat pump).