Jonathan Griener
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Jonathan Griener has a total of 6 co-authors. Here are the top co-authors by number of shared publications:
- Arno Dentel
Institute for Energy and Building (ieg), Technische Hochschule Nürnberg Georg Simon Ohm, Keßlerplatz 12, 90489 Nuremberg, Germany
2 shared publications - Arnulf Hartl
Institute of Ecomedicine, Paracelsus Medical University, 5020 Salzburg, Austria
2 shared publications - Renate Weisböck-Erdheim
Institute of Ecomedicine, Paracelsus Medical University, Strubergasse 21, 5020 Salzburg, Austria
2 shared publications - Sebastian Hummel
Institute for Energy and Building (ieg), Technische Hochschule Nürnberg Georg Simon Ohm, Keßlerplatz 12, 90489 Nuremberg, Germany
2 shared publications - Susanna Bordin
Institute for Energy and Building (ieg), Technische Hochschule Nürnberg Georg Simon Ohm, Keßlerplatz 12, 90489 Nuremberg, Germany
2 shared publications - Barbara Fixl
Institute of Ecomedicine, Paracelsus Medical University, Strubergasse 21, 5020 Salzburg, Austria
1 shared publication
Latest Publications
- Open Access
Linking Health, Comfort and Indoor Environmental Quality in Classrooms with Mechanical Ventilation or Window Airing: A Controlled Observational Study
Effective classroom ventilation is essential for indoor environmental quality (IEQ), comfort and health of schoolchildren, who spend substantial time indoors. This controlled observational study compared manual window airing (WA) with decentralized mechanical ventilation (DV) in six classrooms of two elementary schools during the winter infection period. Symptoms of upper respiratory tract infections, salivary biomarkers, well-being, perceived comfort, and classroom-level IEQ were assessed through questionnaires, saliva samples and long-term monitoring. Ninety-eight schoolchildren participated (64 WA, 34 DV). Symptom-based outcomes of the WURSS-K questionnaire showed consistently lower illness burden in group DV, with several parameters reaching statistical significance and an absolute risk reduction of 7.8%. Salivary immunoglobulin A (sIgA) concentrations were also significantly lower in group DV (approximately 39–59%, p ≤ 0.01). Sensitivity analyses showed positive associations of CO2 and PM2.5 with sIgA and indicated that PM2.5 exposure accounted for group differences. Comfort perceptions mirrored measured IEQ: DV classrooms exhibited warmer, more stable thermal conditions, lower CO2 and PM2.5, and slightly better thermal and draught-related impressions. Overall, decentralized mechanical ventilation supported favorable IEQ and comfort and may influence mucosal immune activity through reduced particulate exposure, complementing the observed reduction in symptom burden. A multidimensional approach integrating medical outcomes with continuous IEQ monitoring proved valuable and should be expanded in larger, balanced cohort studies.
Open AccessLinking Health, Comfort and Indoor Environmental Quality in Classrooms with Mechanical Ventilation or Window Airing: A Controlled Observational Study
Effective classroom ventilation is essential for indoor environmental quality (IEQ), comfort and health of schoolchildren, who spend substantial time indoors. This controlled observational study compared manual window airing (WA) with decentralized mechanical ventilation (DV) in six classrooms of two elementary schools during the winter infection period. Symptoms of upper respiratory tract infections, salivary biomarkers, well-being, perceived comfort, and classroom-level IEQ were assessed through questionnaires, saliva samples and long-term monitoring. Ninety-eight schoolchildren participated (64 WA, 34 DV). Symptom-based outcomes of the WURSS-K questionnaire showed consistently lower illness burden in group DV, with several parameters reaching statistical significance and an absolute risk reduction of 7.8%. Salivary immunoglobulin A (sIgA) concentrations were also significantly lower in group DV (approximately 39–59%, p ≤ 0.01). Sensitivity analyses showed positive associations of CO2 and PM2.5 with sIgA and indicated that PM2.5 exposure accounted for group differences. Comfort perceptions mirrored measured IEQ: DV classrooms exhibited warmer, more stable thermal conditions, lower CO2 and PM2.5, and slightly better thermal and draught-related impressions. Overall, decentralized mechanical ventilation supported favorable IEQ and comfort and may influence mucosal immune activity through reduced particulate exposure, complementing the observed reduction in symptom burden. A multidimensional approach integrating medical outcomes with continuous IEQ monitoring proved valuable and should be expanded in larger, balanced cohort studies.
- Open Access
Long-Term Monitoring of Mechanical Ventilation and Window Airing in Classrooms: A Controlled Observational Study
Indoor environmental quality is essential for pupils‘ health, comfort, and academic performance. However, recent studies indicate that indoor air quality (IAQ) in classrooms is often inadequate. This observational study examines the impact of three ventilation concepts on IAQ and thermal comfort under real-life school conditions: manual window airing combined with CO2 traffic lights, decentralized mechanical ventilation, and centralized mechanical ventilation. Eight classrooms in three elementary schools were monitored from October 2023 to April 2024. Continuous long-term measurements covered CO2, PM2.5, VOCs, indoor air temperature, relative humidity and window opening states in the classrooms, and ambient data including PM2.5 at each school. Significant differences were found in all five indoor parameters across the three ventilation concepts. The decentralized ventilation group achieved the lowest CO2 concentrations (18–22% lower), while the window airing group showed the highest PM2.5 levels (mean of 6 µg/m3) and the lowest temperatures (21% of the time below 20 °C). Relative humidity tended to be too low for all concepts, particularly with mechanical ventilation (medians below 40%). Windows in the window airing group were opened approximately twice as long. The findings highlight the benefits of well-operated mechanical ventilation systems and underscore the importance of user awareness and system management.
Open AccessLong-Term Monitoring of Mechanical Ventilation and Window Airing in Classrooms: A Controlled Observational Study
Indoor environmental quality is essential for pupils‘ health, comfort, and academic performance. However, recent studies indicate that indoor air quality (IAQ) in classrooms is often inadequate. This observational study examines the impact of three ventilation concepts on IAQ and thermal comfort under real-life school conditions: manual window airing combined with CO2 traffic lights, decentralized mechanical ventilation, and centralized mechanical ventilation. Eight classrooms in three elementary schools were monitored from October 2023 to April 2024. Continuous long-term measurements covered CO2, PM2.5, VOCs, indoor air temperature, relative humidity and window opening states in the classrooms, and ambient data including PM2.5 at each school. Significant differences were found in all five indoor parameters across the three ventilation concepts. The decentralized ventilation group achieved the lowest CO2 concentrations (18–22% lower), while the window airing group showed the highest PM2.5 levels (mean of 6 µg/m3) and the lowest temperatures (21% of the time below 20 °C). Relative humidity tended to be too low for all concepts, particularly with mechanical ventilation (medians below 40%). Windows in the window airing group were opened approximately twice as long. The findings highlight the benefits of well-operated mechanical ventilation systems and underscore the importance of user awareness and system management.