  • Open Access

    Research on Temperature Distribution of Cable Fire in Utility Tunnel and Fire Extinguishing Efficiency of High-Pressure Water Mist Fire Extinguishing System

    by Kun Xiang, Peng Du, Hongrun Liu, Yaojia Fu, Taoran Li

    Utility tunnels concentrate various important urban engineering pipelines within a shared underground space, which poses significant fire risks, particularly from cable fires. In this study, a full-scale fire experiment was conducted to investigate the temperature distribution characteristics of cable fires in utility tunnels, along with the effects of spray intensity, cable fullness, and longitudinal ventilation on the extinguishing efficiency of a high-pressure water mist fire extinguishing system (HWMFES). The results show that the maximum heating area of a cable fire in a utility tunnel is localized to the three cable trays nearest to and directly above the fire source, with a peak temperature of 825 °C, while the impact on other areas is negligible. Increasing the spray intensity from 0.7 to 1.0 L/(min·m2) reduced the time required to lower temperatures to 50 °C by 40.8%, while reducing cable fullness from 12 to 6 cables per tray shortened extinguishing time by 22.5%. Additionally, applying a ventilation speed of 2 m/s enhanced cooling efficiency, reducing the time to reach 50 °C by 67.5% compared to still air conditions. These findings provide practical insights and data support for optimizing the design and application of HWMFES in enhancing fire safety in utility tunnels.


  • Open Access

    Research on Temperature Distribution of Cable Fire in Utility Tunnel and Fire Extinguishing Efficiency of High-Pressure Water Mist Fire Extinguishing System

    by Kun Xiang, Peng Du, Hongrun Liu, Yaojia Fu, Taoran Li

    Utility tunnel plays a critical role in concentrating various important urban engineering pipelines but faces severe fire risks and safety threats. In this study, the temperature distribution characteristics of cable fire in utility tunnel were studied by means of full-scale fire experiment, and the effects of spray intensity, cable fullness and ambient wind speed on fire extinguishing efficiency of high-pressure water mist fire extinguishing system (HWMFES) were investigated. The results show that the maximum heating area of cable fire in utility tunnel is localized to the three cable bridges nearest to and directly above the fire source, with a highest temperature exceeding 800°C, while other areas on the same side and the opposite side are negligibly affected. Increasing spray intensity significantly enhances the fire extinguishing efficiency of HWMFES. Reducing cable fullness can effectively shortens the fire extinguishing time of HWMFES. providing longitudinal ventilation of 2 m/s in utility tunnel can significantly improve the fire extinguishing efficiency of HWMFES. The results of this research can provide a theoretical foundation and data support for the engineering application of HWMFES in utility tunnels.