Abstract
This paper introduces a characterization of a single Grounding System (GS) or a set of interconnected GSs, according to their safety level and defines their condition of “conventionally safe” and “intrinsically safe”. GSs or a set of them are intrinsically safe, if they guarantee safe touch/step voltages permanently permissible for an assigned ground fault value. It is proposed a new definition of Global Grounding Systems (GGSs) revising that offered by the Standards IEC 61936-1/EN 50522. The paper suggests a safety criterion, useful for urban and industrial areas with reduced accessibility, that allows to identify the safety zone of influence and the intrinsically safe condition of a single GS and of a GGS, constituted by a set of interconnected single GSs.

This publication has 7 references indexed in Scilit: