Abstract
Medium frequency transformer would face transient overvoltage in the winding brought by fast rising edge of the PWM working voltage, which may cause partial discharge in the winding insulation structure. With temperature rise that is a common phenomenon for medium frequency transformer, this risk of partial discharge generation can even be greater. Changing of temperature also has impact on the partial discharge features and lead to different insulation endurance behavior. In this paper, a test system based on pulse voltage generator is built. By using this system, partial discharge inception voltage, partial discharge features and endurance lifetime experiments are conducted on a kind of medium frequency transformer’s insulation structure under different temperatures. The results show that with temperature rise, partial discharge is easier to be triggered, partial discharge intensity becomes stronger, partial discharge number grows, endurance lifetime reduces and the discharge eroded area becomes larger. Mechanisms of these results are discussed in details and some methods for improving the medium frequency transformer’s long term insulation reliability are suggested.

This publication has 23 references indexed in Scilit: