Water and energy conservation for a counterflow cooling tower using UV light disinfection and variable speed fan
Authors:
- 8 August 2014
- journal article
- research article
- Published by SAGE Publications in Proceedings of the Institution of Mechanical Engineers, Part E: Journal of Process Mechanical Engineering
- Vol. 230 (3) , 235-243
Abstract
The present study proposes a new water and energy conservation method for a counterflow cooling tower by using UV light disinfection and variable speed fan. In the proposed approach, the constant speed tower fan was modified to become a variable speed fan by installing an inverter on the fan’s motor such that the air flow rate of the cooling tower could be reduced to properly match the partial load operation. Furthermore, a by-pass loop with microfilters and UV lights was also added to our test rig to investigate the elimination effectiveness of tower-related bacteria and to reduce the blowdown loss. The experimental results reveal that for 50% load tests, the energy savings was about 76% and the overall water saving was about 23%. Moreover, from our tests we found that with a daily one-hour disinfection, the population of bacteria can be greatly suppressed to far below infection levels, and an increase in water conservation can be achieved. In addition, the possibility of human infection by bacteria originating from cooling towers should thus be greatly reduced.Keywords
This publication has 15 references indexed in Scilit:
- Enhancement of cooling capacity in a hybrid closed circuit cooling towerApplied Thermal Engineering, 2009
- Effects of alternative control strategies of water-evaporative cooling systems on energy efficiency and plume control: A case studyBuilding and Environment, 2008
- Energy performance of a cooling plant system using the inverter chiller for industrial buildingEnergy and Buildings, 2007
- Cooling Tower Performance Evaluation: Merkel, Poppe, and e-NTU Methods of AnalysisJournal of Engineering for Gas Turbines and Power, 2005
- Toward to the control system of mechanical draft cooling tower of film typeInternational Journal of Heat and Mass Transfer, 2005
- Evaporative cooling of water in a mechanical draft cooling towerInternational Journal of Heat and Mass Transfer, 2004
- A numerical analysis of heat and mass transfer inside a reversibly used water cooling towerBuilding and Environment, 2003
- A comprehensive approach to cooling tower designApplied Thermal Engineering, 2001
- On the optimum sizing of cooling towersEnergy Conversion and Management, 2001
- An Improved Design and Rating Analyses of Counter Flow Wet Cooling TowersJournal of Heat Transfer, 2001