Abstract
Treatment of urban stormwater by clarification, with and without flocculant addition, was investigated in Toronto, Ontario, Canada using a pilot-scale clarifier with removable lamellar plates. Almost 90 stormwater runoff events were characterized at the study site and found significantly polluted, in comparison to the U.S. NURP median site data. Earlier research results indicated good treatability of this stormwater by lamellar clarification with flocculant addition (total suspended solids, TSS, removal of 83%, at a total vessel surface-loading rate of 15–35 m/h), but there were concerns about laborious plate cleaning after storm events. With the aid of numerical modeling, hydraulic improvements to the clarifier inlet zone were retrofitted in 2004, which permitted the removal of the lamellar pack without a significant loss in treatment efficiency. In the modified clarifier without lamellas, addition of a cationic polymeric flocculant at 4 mg/L provided a TSS removal of 77%, at surface-loading rates up to 43 m/h. The use of the polymer did not increase the acute toxicity of the process effluent. The stormwater sediment and clarifier sludge at this site were severely polluted by several heavy metals (Cu, Mn, Zn), according to the Ontario aquatic sediment quality guidelines, and the clarifier sludge would require special disposal considerations. The treatment process tested appears to be applicable in projects requiring intensive stormwater treatment at compact sites.

This publication has 9 references indexed in Scilit: