Accurate Noniterative Fault Location Algorithm Utilizing Two-End Unsynchronized Measurements
Authors:
- 4 December 2009
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 25 (1) , 72-80
Abstract
This paper presents a new two-terminal impedance-based fault location algorithm, which takes into account the distributed parameter line model. The algorithm utilizes unsynchronized measurements of voltages and currents from two ends of a line and is formulated in terms of the fundamental frequency phasors of symmetrical components of the measured signals. First, an analytical synchronization of the unsynchronized measurements is performed with use of the determined synchronization operator. Then, the distance to fault is calculated as for the synchronized measurements. Simultaneous usage of two kinds of symmetrical components for determining the synchronization operator makes that the calculations are simple, noniterative and at the same time highly accurate. The developed fault location algorithm has been thoroughly tested using signals of ATP-EMTP versatile simulations of faults on a transmission line. The presented evaluation shows the validity of the developed fault location algorithm and its high accuracy.Keywords
This publication has 17 references indexed in Scilit:
- An Iterative Two-Terminal Fault-Location Method Based on Unsynchronized PhasorsIEEE Transactions on Power Delivery, 2008
- Optimal Estimate of Transmission Line Fault Location Considering Measurement ErrorsIEEE Transactions on Power Delivery, 2007
- Unsynchronized Fault Location Based on Distributed Parameter Line ModelElectric Power Components and Systems, 2007
- Transmission Line Fault Location Using Two-Terminal Data Without Time SynchronizationIEEE Transactions on Power Systems, 2007
- Postfault Analysis of Operation of Distance Protective Relays of Power Transmission LinesIEEE Transactions on Power Delivery, 2006
- Accurate Location of Faults on Power Transmission Lines With Use of Two-End Unsynchronized MeasurementsIEEE Transactions on Power Delivery, 2006
- Unsynchronised two-terminal transmission-line fault-location without using line parametersIEE Proceedings - Generation, Transmission and Distribution, 2006
- Differential protection of multi-terminal lines without synchronization2001
- Automated transmission line fault analysis using synchronized sampling at two endsIEEE Transactions on Power Systems, 1996
- A technique for estimating transmission line fault locations from digital impedance relay measurementsIEEE Transactions on Power Delivery, 1988