A Test Method for Response Behavior of Metal-Oxide Arrester Subjected to Transient Electromagnetic Disturbances
- 9 March 2022
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 37 (6) , 4749-4756
Abstract
Metal-oxide arresters (MOA) are widely used to protect equipment against transient electromagnetic disturbances (TED) like very fast transient overvoltage (VFTO), high-altitude electromagnetic pulse (HEMP), lightning pulse, et al. Researches on the performance of MOA under microsecond level rise-time TED are abundant, such as lightning pulse. However, when MOA is subjected to TED of rise-time at nanosecond level, the voltage/current responses of MOA are not fully studied due to the lack of a standardized and reliable test setup. In this paper, a test setup is proposed for acquiring the response behavior of MOA under nanosecond level pulse. The setup is comprised of a pulse generator, a two-branch transmission line system and a high voltage power divider. The generator can provide stable double exponential pulse with tunable rise-time ranging from 5 ns to 100 ns. The divider ensures an even distribution of voltage/current surge wave along the two-branch line. Through the numerical analysis, both impinging and residual surge waveforms could be retrieved from measurements. The proposed method has been applied to investigate response behavior of MOA subjected to nanosecond level rise-time pulses.Keywords
Funding Information
- Science and technology Project of State Grid Corporation of China (5500-202099502A-0-0-00)
This publication has 22 references indexed in Scilit:
- Behavior Comparison of Metal Oxide Arrester Blocks When Excited by VFTO and LightningIEEE Transactions on Electromagnetic Compatibility, 2015
- New Methods of Damping Very Fast Transient Overvoltages in Gas-Insulated SwitchgearIEEE Transactions on Power Delivery, 2014
- Response of metal oxide arrester in gas-insulated substation and methods to improve its dynamic characteristicsIET Science, Measurement & Technology, 2012
- Modelling of metal oxide arrester for very fast transientsIET Science, Measurement & Technology, 2011
- Computation of very fast transient overvoltages in transformer windingsIEEE Transactions on Power Delivery, 2003
- Performance of MOV arresters during very close, direct lightning strikes to a power distribution systemIEEE Transactions on Power Delivery, 1999
- A simplified model for zinc oxide surge arrestersIEEE Transactions on Power Delivery, 1999
- Study of ZnO arrester model for steep front waveIEEE Transactions on Power Delivery, 1996
- On the HEMP environment for protective relaysIEEE Transactions on Power Delivery, 1994
- Flashover vulnerability of transmission and distribution lines to high-altitude electromagnetic pulse (HEMP)IEEE Transactions on Power Delivery, 1990