Behavior Comparison of Metal Oxide Arrester Blocks When Excited by VFTO and Lightning
Authors:
- 14 July 2015
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Electromagnetic Compatibility
- Vol. 57 (6) , 1608-1615
Abstract
With the development of the ultrahigh voltage (UHV) and extra high voltage (EHV) electric power industry in China, gas insulated substation (GIS) is applied widely. Very fast transient overvoltage (VFTO) caused by disconnector operations in GIS may damage the insulation of equipment due to its high frequency and amplitude. As one of the main overvoltage protection equipments, the protection behavior of surge arresters has received extensive attention. In this paper, the residual voltage behavior, the impedance behavior, and the response behavior of five different representative arrester blocks when excited by VFTO and lightning are investigated, respectively. Experimental results present that when the current peak keeps constant, the residual voltage under VFTO is approximately 14.7%–18.2% higher than under the standard lightning impulse voltage (8/20 μs, LI). The arrester block presents different impedance behavior under VFTO and LI. It behaves dominantly inductively under LI and expresses an impedance converting behavior under VFTO. Furthermore, the diameter and the shape of arrester blocks have little impact on the ratio of $V_{0}$ to $V_{{\rm 1mA}}$ under VFTO. Therefore, the protective effect of arresters varies slightly under VFTO and LI. Investigating behavior of arrester blocks under VFTO in comparison with under LI could be applied not only in VFTO simulation and insulation coordination but also in the design and the operating of metal oxide surge arrester in GIS.Keywords
Funding Information
- National Key Research and Development Program of China (2011CB209400)
- State Grid Corporation of China
This publication has 11 references indexed in Scilit:
- Research of Flashover of Power Line Insulators Due to High-Voltage Pulses With Power ON and Power OFFIEEE Transactions on Electromagnetic Compatibility, 2013
- Analysis of very fast transient overvoltages (VFTO) from onsite measurements on 800 kV GISIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- Experimental Research on Very-Fast Transient Overvoltage in 1100-kV Gas-Insulated SwitchgearIEEE Transactions on Power Delivery, 2012
- Response of metal oxide arrester in gas-insulated substation and methods to improve its dynamic characteristicsIET Science, Measurement & Technology, 2012
- Insulation characteristics of 1100 kV GIS under very fast transient overvoltage and lightning impulseIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- Parameter Determination for Modeling Systems Transients—Part V: Surge Arresters IEEE PES Task Force on Data for Modeling System Transients of IEEE PES Working Group on Modeling and Analysis of System Transients Using Digital Simulation (General Systems Subcommittee)IEEE Transactions on Power Delivery, 2005
- A parameter identification technique for metal-oxide surge arrester modelsIEEE Transactions on Power Delivery, 2002
- A simplified model for zinc oxide surge arrestersIEEE Transactions on Power Delivery, 1999
- Study of ZnO arrester model for steep front waveIEEE Transactions on Power Delivery, 1996
- Behaviour of MO-surge-arrester blocks to fast transientsIEEE Transactions on Power Delivery, 1989