Abstract
The virtual synchronous generator (VSG) is a power-electronic controller that mimics the dynamic behaviour of synchronous generators. It is a promising technology to enable integration of renewable energy conversion systems under weak-grid conditions. By providing virtual inertia, the VSG improves system stability. However, under weak-grid conditions, system stability may also be adversely affected by the VSG exceeding its active-power transfer capacity, leading to a phenomenon known as voltage instability. In this paper, we highlight this problem via simulations conducted for a microgrid test system. Then, we offer analytical justification for the mechanism and root cause of the observed voltage instability. We further propose two countermeasures to improve the active-power transfer capacity. The first is based on existing VSG capabilities so that no new components are needed in the controller, and the second requires additional components but enables full use of the VSG capacity.

This publication has 14 references indexed in Scilit: