Audible Noise and Corona Discharge From Water Droplets on Superhydrophobic HVAC Conductors
- 12 July 2023
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 38 (6) , 3771-3781
Abstract
Audible noise from transmission lines is mainly generated by corona discharge from defects and water droplets on the conductors’ surface. Applying a superhydrophobic coating to the conductors can reduce corona discharge, thereby reducing the level of audible noise produced. In this article, corona discharge and noise measurements from an untreated conductor and a conductor coated with superhydrophobic coatings were carried out in AC electric fields and continuous water spray. The coated conductors show higher partial discharge inception voltages (PDIV) than uncoated ones. PD magnitude and PD per cycle of the coated conductors are lower compared with uncoated conductors, especially at electric fields above 14 kV/cm. A linear correlation between overall sound pressure and total PD magnitude is established. The behavior of corona discharges from single droplets with various sizes and positions and associated droplet vibration were investigated and the local electric field enhancement was analyzed by finite element analysis to examine the influence of droplet size and position on electric field distribution. Superhydrophobic coatings result in reduced PD magnitude and number and therefore reduce audible noise generated. This is attributed to small sessile droplets forming rather than large pendant droplets.Keywords
Funding Information
- Ministry of Science and Technology of the People's Republic of China (G20200022003, G2022165026L)
- University of Manchester
This publication has 46 references indexed in Scilit:
- Partial discharge investigation and electric field analysis of different oscillation modes of water droplets on the surface of polymeric insulator under tangential AC electric field stress2013
- Vibrational Modes of Elongated Sessile Liquid DropletsLangmuir, 2013
- Mechanism of the tonal emission from ac high voltage overhead transmission linesJournal of Physics D: Applied Physics, 2011
- Evaluation of audible noise from surface processing conductors for AC overhead transmission lineElectrical Engineering in Japan, 2007
- Design of Systems of Covered Overhead Conductors by Means of Electric Field CalculationIEEE Transactions on Power Delivery, 2005
- Vibrated sessile drops: Transition between pinned and mobile contact line oscillationsThe European Physical Journal E, 2004
- Origin and abatement of tonal emission from high voltage transmission linese+i Elektrotechnik und Informationstechnik, 2002
- Overhead line design in relation to electric and magnetic field limitsPower Engineering Journal, 1992
- Environmental aspects of route selection for overhead lines in the U.S.A.Electric Power Systems Research, 1989