Abstract
Characteristic gases released by the thermal decomposition of high-voltage cable outer sheaths can provide early warning of fire, but their dispersion in power tunnels remains insufficiently understood. This study combined computational fluid dynamics simulations with realistically configured cable tunnel experiments to investigate the transport of C2H2, C2H4, and C3H6. Immediately after release, thermal buoyancy drove the gases upwards, after which they were transported towards the far end of the tunnel. A Péclet number of approximately 75,000 indicated that long-range transport was dominated by airflow near the tunnel ceiling. Marked differences were observed among the gases. The maximum mass fraction of C2H2 reached 8 × 10-4, and its maximum one-sided propagation distance was approximately 40 m. C2H4 propagated more slowly and exhibited concentration stratification, whereas C3H6 showed the weakest ceiling accumulation and the slowest long-range transport, with a dispersion range below 8 m. The experimental observations were consistent with the simulated dispersion trends. Source height mainly affected concentrations during the initial release but had limited influence on overall dispersion. C2H2 is therefore recommended as the primary monitoring target, with sensors installed near the ceiling–sidewall junction. These results provide a fluid-dynamic basis for positioning early-warning sensors in power tunnels.

This publication has 28 references indexed in Scilit: