Gang Wei
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Research Subjects
Gang Wei has a total of 71 co-authors. Here are the top co-authors by number of shared publications:
- Zhengqin Cao
Chongqing University of Science and Technology
19 shared publications Xiaoyu Wu
Chongqing University of Science and Technology
5 shared publicationsHui Zhong
4 shared publications- Jia Wang
College of Medical Informatics, Chongqing Medical University, Chongqing 400016, China
4 shared publications Qiang Yao
Electric Power Research Institute, State Grid Chongqing Electric Power Company, Chongqing 400022, People's Republic of China
4 shared publicationsHaiyan Zhang
College of Electrical Engineering, Chongqing University of Science and Technology, Chongqing 401331, China
3 shared publications
Latest Publications
- 18 September 2026
- Published by American Chemical Society (ACS) in Langmuir
- Vol. 42  (39) , 29441-29455
Pt- and Pd-Modified Two-Dimensional GeSe for Ethylene and Acetylene Sensing during Poly(vinyl chloride) Cable Overheating
Poly(vinyl chloride) (PVC) outer sheaths undergo pyrolysis during thermal faults or partial discharges in high-voltage cables, releasing marker gases such as ethylene (C2H4) and acetylene (C2H2). Developing sensing materials capable of sensitively identifying these gases is important for early safety monitoring of high-voltage cable outer sheaths. To address the limited interaction of weakly polar C2H2 and C2H4 with GeSe surfaces and the difficulty of regulating gas adsorption and charge transfer, Pd-GeSe and Pt-GeSe sensing materials were prepared by combining density functional theory (DFT) screening with hydrothermal synthesis, and the effects of the two noble-metal modification routes on structural changes and sensing performance were compared. Gas-sensing measurements showed that the response/recovery times of Pd-GeSe toward 100 ppm of acetylene and ethylene were 104/84 and 92/72 s, respectively; the corresponding values for Pt-GeSe were 73/76 and 63/91 s, with higher overall response magnitudes. Structural characterization showed that both materials retained the principal GeSe structure. Pd-GeSe exhibited Pd-related diffraction features and more evident surface roughening, whereas Pt-GeSe showed slight changes in the GeSe diffraction peaks, indicating that Pd and Pt affect the GeSe structure and interface differently. Under the same idealized models and computational conditions, DFT calculations showed that Pd and Pt incorporation altered the adsorption energies, Mulliken charge transfer, and electronic structures of GeSe interacting with C2H2/C2H4. These theoretical results are broadly consistent with the experimentally observed sensing differences between the two modified materials and provide a possible explanation for their performance variations. This study provides theoretical and experimental guidance for interfacial regulation of GeSe-based sensing materials and detection of marker gases from PVC thermal degradation.
- 18 September 2026
- Published by American Chemical Society (ACS) in Langmuir
- Vol. 42  (39) , 29441-29455
Pt- and Pd-Modified Two-Dimensional GeSe for Ethylene and Acetylene Sensing during Poly(vinyl chloride) Cable Overheating
Poly(vinyl chloride) (PVC) outer sheaths undergo pyrolysis during thermal faults or partial discharges in high-voltage cables, releasing marker gases such as ethylene (C2H4) and acetylene (C2H2). Developing sensing materials capable of sensitively identifying these gases is important for early safety monitoring of high-voltage cable outer sheaths. To address the limited interaction of weakly polar C2H2 and C2H4 with GeSe surfaces and the difficulty of regulating gas adsorption and charge transfer, Pd-GeSe and Pt-GeSe sensing materials were prepared by combining density functional theory (DFT) screening with hydrothermal synthesis, and the effects of the two noble-metal modification routes on structural changes and sensing performance were compared. Gas-sensing measurements showed that the response/recovery times of Pd-GeSe toward 100 ppm of acetylene and ethylene were 104/84 and 92/72 s, respectively; the corresponding values for Pt-GeSe were 73/76 and 63/91 s, with higher overall response magnitudes. Structural characterization showed that both materials retained the principal GeSe structure. Pd-GeSe exhibited Pd-related diffraction features and more evident surface roughening, whereas Pt-GeSe showed slight changes in the GeSe diffraction peaks, indicating that Pd and Pt affect the GeSe structure and interface differently. Under the same idealized models and computational conditions, DFT calculations showed that Pd and Pt incorporation altered the adsorption energies, Mulliken charge transfer, and electronic structures of GeSe interacting with C2H2/C2H4. These theoretical results are broadly consistent with the experimentally observed sensing differences between the two modified materials and provide a possible explanation for their performance variations. This study provides theoretical and experimental guidance for interfacial regulation of GeSe-based sensing materials and detection of marker gases from PVC thermal degradation.
- Open Access
- 16 August 2026
- Published by Elsevier in SSRN Electronic Journal
Dispersion Characteristics of Gases Generated from the Thermal Decomposition of High-Voltage Cable Outer Sheaths in Power Tunnels
Characteristic gases released by the thermal decomposition of high-voltage cable outer sheaths can provide early warning of fire, but their dispersion in power tunnels remains insufficiently understood. This study combined computational fluid dynamics simulations with realistically configured cable tunnel experiments to investigate the transport of C2H2, C2H4, and C3H6. Immediately after release, thermal buoyancy drove the gases upwards, after which they were transported towards the far end of the tunnel. A Péclet number of approximately 75,000 indicated that long-range transport was dominated by airflow near the tunnel ceiling. Marked differences were observed among the gases. The maximum mass fraction of C2H2 reached 8 × 10-4, and its maximum one-sided propagation distance was approximately 40 m. C2H4 propagated more slowly and exhibited concentration stratification, whereas C3H6 showed the weakest ceiling accumulation and the slowest long-range transport, with a dispersion range below 8 m. The experimental observations were consistent with the simulated dispersion trends. Source height mainly affected concentrations during the initial release but had limited influence on overall dispersion. C2H2 is therefore recommended as the primary monitoring target, with sensors installed near the ceiling–sidewall junction. These results provide a fluid-dynamic basis for positioning early-warning sensors in power tunnels.
- 16 August 2026
- Published by Elsevier in SSRN Electronic Journal
Open AccessDispersion Characteristics of Gases Generated from the Thermal Decomposition of High-Voltage Cable Outer Sheaths in Power Tunnels
Characteristic gases released by the thermal decomposition of high-voltage cable outer sheaths can provide early warning of fire, but their dispersion in power tunnels remains insufficiently understood. This study combined computational fluid dynamics simulations with realistically configured cable tunnel experiments to investigate the transport of C2H2, C2H4, and C3H6. Immediately after release, thermal buoyancy drove the gases upwards, after which they were transported towards the far end of the tunnel. A Péclet number of approximately 75,000 indicated that long-range transport was dominated by airflow near the tunnel ceiling. Marked differences were observed among the gases. The maximum mass fraction of C2H2 reached 8 × 10-4, and its maximum one-sided propagation distance was approximately 40 m. C2H4 propagated more slowly and exhibited concentration stratification, whereas C3H6 showed the weakest ceiling accumulation and the slowest long-range transport, with a dispersion range below 8 m. The experimental observations were consistent with the simulated dispersion trends. Source height mainly affected concentrations during the initial release but had limited influence on overall dispersion. C2H2 is therefore recommended as the primary monitoring target, with sensors installed near the ceiling–sidewall junction. These results provide a fluid-dynamic basis for positioning early-warning sensors in power tunnels.
- Open Access
- 21 May 2026
- Published by Association for Computing Machinery (ACM)
- p. 203-208
Study on the Effect of Contact Force on Joule Heating in High-Voltage Disconnectors Based on COMSOL Multiphysics Simulation
Abnormal heating caused by changes in contact conditions is a critical issue affecting the safe operation of high-voltage disconnectors. Contact force, as the key factor influencing contact resistance, lacks systematic investigation regarding its coupled multiphysics heating mechanism. In this paper, a GW4-type 110 kV disconnector is taken as the research object. A coupled electromagnetic-thermal-mechanical multiphysics simulation model is established using COMSOL Multiphysics to analyze the temperature field distribution of contacts under varying contact pressure and insertion depth. Results show that as the insertion depth of the moving contact increases, the contact pressure rises nonlinearly with a faster growth rate near the standard closing position. A reduction in contact pressure leads to decreased contact area and increased contact resistance, thereby significantly elevating heat generation. The findings provide a theoretical basis for structural optimization and operation-maintenance strategies of disconnectors.
- 21 May 2026
- Published by Association for Computing Machinery (ACM)
- p. 203-208
Open AccessStudy on the Effect of Contact Force on Joule Heating in High-Voltage Disconnectors Based on COMSOL Multiphysics Simulation
Abnormal heating caused by changes in contact conditions is a critical issue affecting the safe operation of high-voltage disconnectors. Contact force, as the key factor influencing contact resistance, lacks systematic investigation regarding its coupled multiphysics heating mechanism. In this paper, a GW4-type 110 kV disconnector is taken as the research object. A coupled electromagnetic-thermal-mechanical multiphysics simulation model is established using COMSOL Multiphysics to analyze the temperature field distribution of contacts under varying contact pressure and insertion depth. Results show that as the insertion depth of the moving contact increases, the contact pressure rises nonlinearly with a faster growth rate near the standard closing position. A reduction in contact pressure leads to decreased contact area and increased contact resistance, thereby significantly elevating heat generation. The findings provide a theoretical basis for structural optimization and operation-maintenance strategies of disconnectors.
- 1 April 2026
- Published by Springer Nature
- p. 26-33
Simulation Study on the Hydrogen Generation Pathways in the Pyrolysis of PVC Cable Sheaths
- 1 April 2026
- Published by Springer Nature
- p. 26-33
Simulation Study on the Hydrogen Generation Pathways in the Pyrolysis of PVC Cable Sheaths
- 10 February 2026
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. PP  (10709878) , 1
Early Fire-Warning Strategy for High Voltage Cables Based on Pyrolysis Characteristics of PE Outer Sheath at Different Temperatures
With the widespread application of high-voltage power cables in urban power grids, the fire risk associated with these cables poses an increasing threat to the safe operation of power systems. Pyrolysis gases emitted from the cable’s outer sheath serve as critical indicators of early-stage thermal anomalies, acting as diagnostic signals rather than direct ignition sources. To investigate the gas generation characteristics for fault diagnosis and to develop a robust early warning method, this study conducted pyrolysis experiments on polyethylene (PE) outer sheaths across a temperature range of 90–250 °C. An optimized Random Forest (RF) early-warning model was established, underpinned by multi-dimensional feature engineering and the Synthetic Minority Over-sampling Technique (SMOTE) to address data imbalance. Experimental results reveal that the pyrolysis products primarily consist of alkanes, alkenes, alkynes, CO, and CO2, exhibiting distinct non-linear trends with increasing temperature. Based on these characteristics, the cable condition was categorized into three warning levels: Attention, Alert, and Alarm. The proposed RF-based model achieved a mean stratified 5-fold cross-validation accuracy of 92.28%, with an independent test accuracy of 93.75%, demonstrating superior stability and generalization capability compared with Support Vector Machine (SVM) and Logistic Regression (LR) classifiers. This study provides a reliable, data-driven strategy for identifying incipient thermal faults and preventing fire accidents in high-voltage power cables.
- 10 February 2026
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. PP  (10709878) , 1
Early Fire-Warning Strategy for High Voltage Cables Based on Pyrolysis Characteristics of PE Outer Sheath at Different Temperatures
With the widespread application of high-voltage power cables in urban power grids, the fire risk associated with these cables poses an increasing threat to the safe operation of power systems. Pyrolysis gases emitted from the cable’s outer sheath serve as critical indicators of early-stage thermal anomalies, acting as diagnostic signals rather than direct ignition sources. To investigate the gas generation characteristics for fault diagnosis and to develop a robust early warning method, this study conducted pyrolysis experiments on polyethylene (PE) outer sheaths across a temperature range of 90–250 °C. An optimized Random Forest (RF) early-warning model was established, underpinned by multi-dimensional feature engineering and the Synthetic Minority Over-sampling Technique (SMOTE) to address data imbalance. Experimental results reveal that the pyrolysis products primarily consist of alkanes, alkenes, alkynes, CO, and CO2, exhibiting distinct non-linear trends with increasing temperature. Based on these characteristics, the cable condition was categorized into three warning levels: Attention, Alert, and Alarm. The proposed RF-based model achieved a mean stratified 5-fold cross-validation accuracy of 92.28%, with an independent test accuracy of 93.75%, demonstrating superior stability and generalization capability compared with Support Vector Machine (SVM) and Logistic Regression (LR) classifiers. This study provides a reliable, data-driven strategy for identifying incipient thermal faults and preventing fire accidents in high-voltage power cables.
- 1 January 2026
- Published by Royal Society of Chemistry (RSC) in Reaction Chemistry & Engineering
Shear-assisted interlocking of functionalized carbon nanotubes on PVDF membranes for emulsified oil separation
Prolonged hydrodynamic shear interlocks acidified CNTs with PVDF nanofibers, creating a robust hydrophilic network for efficient separation of SDS-stabilized oil-in-water emulsions.
- 1 January 2026
- Published by Royal Society of Chemistry (RSC) in Reaction Chemistry & Engineering
Shear-assisted interlocking of functionalized carbon nanotubes on PVDF membranes for emulsified oil separation
Prolonged hydrodynamic shear interlocks acidified CNTs with PVDF nanofibers, creating a robust hydrophilic network for efficient separation of SDS-stabilized oil-in-water emulsions.
- 29 November 2025
- Published by Elsevier in Physica E: Low-dimensional Systems and Nanostructures
- Vol. 177
Theoretical study on adsorption and gas-sensing behavior of 2,3-butanediol on Ni- and Co-doped WSe2 monolayers based on DFT
- 29 November 2025
- Published by Elsevier in Physica E: Low-dimensional Systems and Nanostructures
- Vol. 177
Theoretical study on adsorption and gas-sensing behavior of 2,3-butanediol on Ni- and Co-doped WSe2 monolayers based on DFT
- Open Access
- 3 September 2025
- Published by American Chemical Society (ACS) in ACS Omega
- Vol. 10  (36) , 41124-41135
Adsorption and Gas Sensing Properties of SF6/N2 Decomposition Components (NF3,SO2) on Pt-Doped MoSe2 Monolayer: A DFT Study
SF6/N2 gas mixtures tend to decompose under faults such as partial discharges and overheating in electrical equipment, producing large amounts of toxic and hazardous gases, particularly NF3 and SO2. These decomposition products compromise insulation and pose serious risks to maintenance personnel, making their detection essential. In this work, density functional theory (DFT) is employed to investigate the adsorption behavior of SO2 and NF3 gases on pristine MoSe2 and Pt-doped MoSe2 monolayers by analyzing the adsorption energy, adsorption distance, charge transfer, band structure, and density of states. The results reveal that the Pt-doped MoSe2 system exhibits a higher structural stability and significantly enhanced adsorption capability. It demonstrates high sensitivity to NF3 and SO2 gases, highlighting its potential application in the detection of these gas species.
- 3 September 2025
- Published by American Chemical Society (ACS) in ACS Omega
- Vol. 10  (36) , 41124-41135
Open AccessAdsorption and Gas Sensing Properties of SF6/N2 Decomposition Components (NF3,SO2) on Pt-Doped MoSe2 Monolayer: A DFT Study
SF6/N2 gas mixtures tend to decompose under faults such as partial discharges and overheating in electrical equipment, producing large amounts of toxic and hazardous gases, particularly NF3 and SO2. These decomposition products compromise insulation and pose serious risks to maintenance personnel, making their detection essential. In this work, density functional theory (DFT) is employed to investigate the adsorption behavior of SO2 and NF3 gases on pristine MoSe2 and Pt-doped MoSe2 monolayers by analyzing the adsorption energy, adsorption distance, charge transfer, band structure, and density of states. The results reveal that the Pt-doped MoSe2 system exhibits a higher structural stability and significantly enhanced adsorption capability. It demonstrates high sensitivity to NF3 and SO2 gases, highlighting its potential application in the detection of these gas species.
- 11 July 2025
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 32  (5) , 2840-2848
Insight Into the Distribution of Pyrolysis Gaseous Products From the PE Outer Sheath of 110-kV High-Voltage Cable
Polyethylene (PE) is widely used in the preparation of high-voltage power cable sheathing due to its excellent electrical properties. Electrical fires occur frequently in recent years. This study evaluates the status of PE sheathing on high-voltage cables by analyzing the distribution of PE pyrolysis gas products and provides a theoretical and experimental basis for fire warning techniques. Using large-scale ReaxFF molecular dynamics simulations, we study the gas production characteristics of PE pyrolysis. The simulation results indicate that the main pyrolysis products are H2, CO, CH4, C2H4, and C2H2, with an analysis of the pyrolysis kinetics and gas formation mechanism through molecular dynamics calculations. Through the aging experiment, it is found that with the increase of aging time, the contents of C2H4, C2H2, H2 and CO in the pyrolysis gas of the PE outer sheath show a significant downward trend. Furthermore, through pyrolysis experiments at different times, the impact of pyrolysis time on gas product distribution is analyzed using Fourier transform infrared spectroscopy and gas chromatography. Overall, with longer pyrolysis times, there is a greater variety and quantity of gas products. Only C2H4, C2H2, and CO2 are generated after 15 and 30 minutes of pyrolysis, with H2 produced after 180 minutes of heating. The simulated and experimental gas generation components are in good agreement. Lastly, the evaluation of the overheating state of high-voltage cable PE sheathing is based on the characteristic gas differences produced.
- 11 July 2025
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 32  (5) , 2840-2848
Insight Into the Distribution of Pyrolysis Gaseous Products From the PE Outer Sheath of 110-kV High-Voltage Cable
Polyethylene (PE) is widely used in the preparation of high-voltage power cable sheathing due to its excellent electrical properties. Electrical fires occur frequently in recent years. This study evaluates the status of PE sheathing on high-voltage cables by analyzing the distribution of PE pyrolysis gas products and provides a theoretical and experimental basis for fire warning techniques. Using large-scale ReaxFF molecular dynamics simulations, we study the gas production characteristics of PE pyrolysis. The simulation results indicate that the main pyrolysis products are H2, CO, CH4, C2H4, and C2H2, with an analysis of the pyrolysis kinetics and gas formation mechanism through molecular dynamics calculations. Through the aging experiment, it is found that with the increase of aging time, the contents of C2H4, C2H2, H2 and CO in the pyrolysis gas of the PE outer sheath show a significant downward trend. Furthermore, through pyrolysis experiments at different times, the impact of pyrolysis time on gas product distribution is analyzed using Fourier transform infrared spectroscopy and gas chromatography. Overall, with longer pyrolysis times, there is a greater variety and quantity of gas products. Only C2H4, C2H2, and CO2 are generated after 15 and 30 minutes of pyrolysis, with H2 produced after 180 minutes of heating. The simulated and experimental gas generation components are in good agreement. Lastly, the evaluation of the overheating state of high-voltage cable PE sheathing is based on the characteristic gas differences produced.