Abstract
Parameters from piezocone test (CPTU) are commonly used for soil profiling and geostratigraphy, along with the parameters used for assessment of geotechnical design. CPTU provides near-continuous measurements of tip resistance, sleeve friction and pore pressure at the shoulder, or face, or shaft of the cone. The dissipation results in CPTU soundings are used to evaluate the coefficient of consolidation and permeability of soil at intermittent depth. Recently, however, several approaches based on CPTU data to assessing the hydraulic conductivity of soils continuously are developed to avoid the time-consuming dissipation of excess pore pressure. This paper presents an experiment, centered on the use of piezocone tests, to determine the flow characteristics of cohesive soils on the engineering background of design of a transformer substation in Lianyungang, China. Three methods (two continuous and one discontinuous) are applied to obtain the coefficient of permeability of soils, and the results are compared with those from laboratory tests. This study confirmed the potential for use of piezocone tests to obtain valid predictions for flow characteristics of soils.