Experimental determination and computational fluid dynamics predictions of pressure loss in close-coupled elbows (RP-1682)
Authors:
Open Access
- 17 February 2017
- journal article
- research article
- Published by Taylor & Francis in Science and Technology for the Built Environment
- Vol. 23 (7) , 1132-1141
Abstract
An experimental program was implemented to study pressure losses in HVAC duct systems associated with 305 mm (12 in.) diameter close-coupled round five-gore elbows. The goal of this program was to experimentally verify a computational fluid dynamics model to accurately predict pressure losses in order to design duct systems more effectively. The results of this study showed that the loss coefficient increased as a function of separation distance between the elbows in a Z-configuration and decreased in a U-configuration. For both 305 mm (12 in.) and 203 mm (8 in.) diameter elbows, power law expressions correlating the combination loss coefficient data as a function of intermediate length for close-coupled elbows arranged in a Z-configuration or a U-configuration were presented. Computational fluid dynamics modeling with enhanced wall treatment using the k-ϵ method was generally able to correctly predict elbow loss coefficients with an error of less than 15%.Keywords
This publication has 3 references indexed in Scilit:
- Pressure Loss Coefficient Measurements of Two Close-Coupled HVAC ElbowsHVAC&R Research, 2005
- Analytical determination of duct fitting loss-coefficientsApplied Energy, 1998
- k-factors for HVAC ducts: Numerical and experimental determinationBuilding Services Engineering Research & Technology, 1995