Abstract
Since its introduction in 1973, the Davisson Offset Limit has been widely used in the United States for interpretation of axial compressive load tests on pile foundations and is one of three methods explicitly accepted by the 2006 International Building Code. An examination of the fundamental assumptions of the DOL shows that its application to cast-in-place piles lacks scientific basis and leads to over conservatism. Interestingly, these are the same reasons given by Davisson for its development. The results of the examination indicate that there are notable fallacies in the Davisson Offset Limit, including the assumptions that: (1) the cast-in-place pile behaves as a "fixed-base, free-standing column.", (2) an elastic line is a dependable reference line for interpretation of load tests on cast-in-place piles, and; (3) an offset of 3.8 mm + D (inches)/120 from the elastic line represents the movement necessary to mobilize toe resistance of cast-in-place piles. Considering these results, the authors present suggestions ranging from modifications to the Davison Offset Limit that recognizes the greater movement required to mobilize the toe resistance to codification of a more rational criterion better suited to interpret the axial compressive capacity of cast-in-place piles.

This publication has 2 references indexed in Scilit: