Abstract
The research on partial discharge detection using high-sensitivity fiber-optic Mach-Zehnder interferometer (MZI) sensing technology for cable accessory defect recognition is insufficient, which restricts its engineering applications. This paper established a sensitivity frequency-domain model for the acoustic-enhanced structure. Then, an acoustic-enhanced optical fiber MZI sensing system was constructed and the anti-interference capability of the sensing system was analyzed. Finally, the system was used to conduct experimental tests on four types of simulated defects in Cross-linked polyethylene (XLPE) cable accessories, including air gap defects, impurity defects, scratch defects, and moisture defects. The results show that the acoustic-enhanced structure has acoustic amplification capability in the 20-200 kHz frequency range, and acoustic waves can be concentrated at the end of the structure. The acoustic-enhanced fiber-optic MZI sensing system can resist environmental temperature changes and low-frequency vibration interference. It can effectively recognize four types of simulated defects in XLPE cable accessories and outperforms cylindrical fiber-optic MZI sensing systems and piezoelectric transducers sensor. For impurity and moisture defects, the acoustic-enhanced fiber-optic MZI sensing system can detect partial discharges with a minimum charge of 32.0 pC and 54.6 pC, respectively. For air gap and scratch defects, the system has better defect detection ability than high-frequency current transformer, with the initial discharge voltage being 10.0% and 6.8% lower, respectively.

This publication has 30 references indexed in Scilit: