Experimental Determination of Diagnostic Signs of Damage to the Rotor Windings of High-Voltage Power Plant Motors in Startup Mode
- 1 May 2020
- journal article
- research article
- Published by Pleiades Publishing Ltd in Russian Journal of Nondestructive Testing
- Vol. 56 (5) , 408-416
Abstract
Induction electric motors are widely used as drives of various mechanisms in power engineering and industry. Their failure can lead to costly repairs, to a reduction in power, or, for example, to a complete shutdown of a power plant unit. One of the reasons for the failure of high-voltage induction motors operating under severe starting conditions is damage to the squirrel-cage rotor winding. Existing methods for monitoring the breakage of the winding bars of such electric motors are ineffective due to the peculiarities of their operating modes. Therefore, monitoring the condition of the bars of high-voltage motors at startup and searching for diagnostic signs is an urgent task. Initially, the studies were carried out with a model of a high-voltage induction motor, developed in the ANSYS software package. To confirm the results obtained for a real motor, research has also been conducted on the developed experimental bench. The recorded signals were processed based on the method of short-time Fourier transform in the MatLab environment. In the course of the study, it was shown that, in the presence of bar breaks, the spectrum of an induction motor exhibits sharply increased amplitudes of harmonic components of the dummy rotor winding at the lower side frequencies of the first orders; this confirms the possibility of using external magnetic field signal at startup to detect the presence of bar breaks in the squirrel-cage rotor winding of high-voltage induction motors with heavy prolonged starts.Keywords
This publication has 8 references indexed in Scilit:
- Method of condition monitoring of rotor windings of the medium voltage induction motors of power plant auxiliaries in start-up modesVestnik IGEU, 2019
- An Improved 2-D Subdomain Model of Squirrel-Cage Induction Machine Including Winding and Slotting Harmonics at Steady StateIEEE Transactions on Magnetics, 2018
- Experimental and analytical determination of the diagnostic feature of induction motor rotor winding defectsVestnik IGEU, 2018
- Evaluation of the possibility of using the radial component of external magnetic field for induction motor diagnosticsVestnik IGEU, 2018
- Vibration signature analysis for rotor broken bar diagnosis in double cage induction motor drives2013
- FINITE ELEMENT ANALYSIS AND EXPERIMENTAL STUDY OF THE NEAR-MAGNETIC FIELD FOR DETECTION OF ROTOR FAULTS IN INDUCTION MOTORSProgress In Electromagnetics Research B, 2013
- Instantaneous Frequency of the Left Sideband Harmonic During the Start-Up Transient: A New Method for Diagnosis of Broken BarsIEEE Transactions on Industrial Electronics, 2009
- Noninvasive detection of broken rotor bars in operating induction motorsIEEE Transactions on Energy Conversion, 1988