Abstract
Transformerless grid-connected inverters (TLI) feature high efficiency, low cost, low volume and weight due to using neither line-frequency transformers nor high-frequency transformers. Therefore, TLIs have been extensively investigated in academic community and popularly installed in distributed photovoltaic grid-connected systems during the past decade. This paper analyzes and summarizes the state of the art of TLI techniques, three rules of maintaining constant common-mode voltage (CMV) of TLIs at switching frequency have been concluded from a generic CMV analysis model at the beginning. Secondly, suppression methods of leakage current (LC) and DC current injection (DCCI), so called as two key challenges for first generation TLIs, have been classified and discussed in detail, respectively. Finally, future trends and some challenges of TLIs based on wide bandgap devices named as second generation TLIs in this paper have been presented.
Funding Information
  • National Natural Science Foundation of China (51577033)
  • Natural Science Foundation of Jiangsu Province (BK20171360)
  • Jiangsu Provincial Key Laboratory of Smart Grid Technology and Equipment, Jiangsu Provincial Department of Science and Technology

This publication has 75 references indexed in Scilit: