Abstract
This paper presents a novel multi-loop control strategy for Vienna rectifiers that eliminates coordinate transformations while achieving superior performance under adverse grid conditions. Unlike conventional dq-frame controllers that suffer from computational complexity and degraded performance during unbalanced conditions, the proposed abc-frame scheme achieves a power factor of 98% with total harmonic distortion (THD) below 5% across all operating conditions. The system exhibits a settling time under 120 μs for 90% load transients and ensures robust operation during Type A voltage sags while maintaining a 94% power factor. Furthermore, it guarantees zero steady-state neutral point deviation. The controller employs a dual-loop architecture with high-gain current tracking and PI-based voltage regulation, validated through extensive PSIM/C++ co-simulations at 120 kw. Comparative analysis demonstrates a 35% reduction in computational burden relative to dq-frame alternatives, while fully complying with IEEE-519:2022 standards. These results highlight the proposed method as a practical and robust solution for industrial rectification applications requiring grid-fault tolerance.

This publication has 34 references indexed in Scilit: