Abstract
Faulted phase selection (FPS) is critical for the proper operation of protection systems. FPS is performed after fault detection, during which the relay observes signals whose characteristics vary depending on the fault detection time (FDT), including different levels of decaying induced transients mixed with the post‐fault cosine signal. However, numerous existing FPS methods overlook that fixed post‐fault sampling windows implicitly assume a known or fixed FDT and therefore do not address the variation or uncertainty in FDT encountered in relays. In this paper, it is demonstrated that the difference between the post‐fault and pre‐fault energy of voltage signals effectively represents the voltage drop component, based on which the voltage drop index (VDI) is proposed. Additionally, the induced transient index (ITI) is introduced based on the variance of the post‐fault voltage energy to estimate induced transients. By combining VDI and ITI, an adaptive fault classification index (AFCI) is proposed, in which the contribution of each index is adaptively adjusted using the Chatterjee correlation. By incorporating both aspects of fault characteristics, AFCI demonstrates the ability to classify faults across varying FDTs. The results indicate that the method accurately classifies faults across varying FDTs, even under noise and power swing conditions.

This publication has 28 references indexed in Scilit: