Efficient HVRT Scheme of DFIG Using a SSFCL-Chopper Considering Grid Voltage Recovery
Authors:
- 8 September 2021
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Applied Superconductivity
- Vol. 31 (8) , 1-3
Abstract
To enhance the dynamic high-voltage ride-through (HVRT) performance of doubly fed induction generator (DFIG) considering both the grid voltage swell and recovery influences, an efficient HVRT scheme is proposed by integrating a stator-side superconducting fault current limiter (SSFCL) with a dc-link chopper. The basic principle, circuit modeling, resistance setting, current-limiting characteristics design and coordinated control strategy of the SSFCL and chopper are presented to form an integrated protection scheme. As compared to a SSFCL or chopper-based HVRT scheme, the results obtained in the proposed SSFCL-chopper-based scheme show that the amplitudes of external and internal electromagnetic transient oscillations of the DFIG are largely reduced with shorter recovery time. This enhances significantly the HVRT behaviors in the DFIG considering grid voltage recovery.Keywords
Funding Information
- National Natural Science Foundation of China (51977019)
This publication has 4 references indexed in Scilit:
- Postfault LVRT Performance Enhancement of DFIG Using a Stage-Controlled SSFCL-RSDRIEEE Transactions on Applied Superconductivity, 2019
- Improved ride-through control of DFIG during grid voltage swellIEEE Transactions on Industrial Electronics, 2014
- Fast Coordinated Control of DFIG Wind Turbine Generators for Low and High Voltage Ride-ThroughEnergies, 2014
- Application of SMES to Enhance the Dynamic Performance of DFIG During Voltage Sag and SwellIEEE Transactions on Applied Superconductivity, 2012