Impact of noise related waveforms on long term field leakage current measurements
- 31 January 2011
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 18 (1) , 122-129
Abstract
Leakage current (LC) monitoring is widely employed in order to investigate electrical surface activity on high voltage (HV) insulators. Long term field monitoring is required in order to obtain an actual view of the phenomena. Therefore any monitoring system is bound to encounter data size problems. A number of solutions have been proposed to address this problem by extracting different values from the measured waveforms as a performance indication. However, a parameter that is fully representative of the waveform is yet to be determined. Hence, measuring and storing of the actual LC waveform is still required on sites for research and monitoring purposes. In addition, field related noise can result to misinterpretation of the actual activity. In this paper, a number of 26089 waveforms, recorded in a 150 kV Substation on four different post insulators that are part of the grid, are investigated. The monitoring period exceeded six years. Different techniques are applied and evaluated on the data set, employing simple numeric criteria and more advanced techniques such as Fourier and Wavelet analysis. Results are presented towards addressing the problems of noise and data size. The study objective is the incorporation of the results in improved leakage current monitoring systems.Keywords
This publication has 20 references indexed in Scilit:
- Recurrent plot analysis of leakage current for monitoring outdoor insulator performanceIEEE Transactions on Dielectrics and Electrical Insulation, 2009
- Diagnostic study of the surface condition of the insulation structure using wavelet transform and neural networksElectric Power Systems Research, 2004
- Fundamental and low frequency harmonic components of leakage current as a diagnostic tool to study aging of RTV and HTV silicone rubber in salt-fogIEEE Transactions on Dielectrics and Electrical Insulation, 2003
- Linear stochastic analysis of polluted insulator leakage currentIEEE Transactions on Power Delivery, 2002
- A method for detecting the transition from corona from water droplets to dry-band arcing on silicone rubber insulatorsIEEE Transactions on Dielectrics and Electrical Insulation, 2002
- Spectral analysis of leakage current on contaminated insulators by auto regressive method2002
- Leakage current and charge in RTV coated insulators under pollution conditionsIEEE Transactions on Dielectrics and Electrical Insulation, 2002
- Leakage current monitoring and outdoor degradation of silicone rubberIEEE Transactions on Dielectrics and Electrical Insulation, 2001
- Leakage current patterns on contaminated polymeric surfacesIEEE Transactions on Dielectrics and Electrical Insulation, 1999