Energy and Exergy Analyses of a New Triple-Staged Refrigeration Cycle Using Solar Heat Source
- 2 July 2013
- journal article
- Published by ASME International in Journal of Solar Energy Engineering
- Vol. 136 (1) , 011004
Abstract
In this paper, energy and exergy analyses of a new solar-driven triple-staged refrigeration cycle using Duratherm 600 oil as the heat transfer fluid are performed. The proposed cycle is an integration of absorption refrigeration cycle (ARC), ejector (EJE) refrigeration cycle (ERC), and ejector expansion Joule–Thomson (EJT) refrigeration cryogenic cycles which could produce refrigeration output of different magnitude at different temperature simultaneously. Both exergy destruction and losses in each component and hence in the overall system are determined to identify the causes and locations of the thermodynamic imperfection. Several design parameters, including the hot oil outlet temperature, refrigerant turbine inlet pressure, and the evaporator temperature of ERC and EJT cycle are also tested to evaluate their effects on energy and exergy performance. It is observed that largest contribution to cycle irreversibility comes from the central receiver and heliostat field with the heat recovery vapor generator (HRVG), condenser, and ejector of ERC itself also contributing considerably. The exergy efficiency of the solar-driven triple-staged refrigeration cycle is 4% which is much lower than its energy efficiency of 10%, respectively. The results clearly reveal that thermodynamic investigations based on energy analysis alone cannot legitimately be complete unless the exergy concept becomes a part of the analysis.Keywords
This publication has 22 references indexed in Scilit:
- Analysis of a solar-assisted ejector cooling system for air conditioningInternational Journal of Low-Carbon Technologies, 2009
- New deep-freezing process using renewable low-grade heat: From the conceptual design to experimental resultsEnergy, 2007
- Study of a Solar Booster Assisted Ejector Refrigeration System With R134aJournal of Solar Energy Engineering, 2005
- Performance characteristics of a methanol ejector refrigeration unitEnergy Conversion and Management, 2004
- An exergy analysis of a solar-driven ejector refrigeration systemSolar Energy, 2004
- Solar thermal collectors and applicationsProgress in Energy and Combustion Science, 2004
- Simulation of solar-powered absorption cooling systemRenewable Energy, 2003
- A Simulation Study of Performance Evaluation of Single-Glazed and Double-Glazed Collectors/Regenerators for an Open-Cycle Absorption Solar Cooling SystemSolar Energy, 2001
- Investigation of thermal performance of a solar powered absorption refrigeration systemEnergy Conversion and Management, 1996
- Comparative study of cycle performance for a two stage intermittent solar refrigerator working with R22-absorbent combinationsEnergy Conversion and Management, 1996