Flexible Noncontact Approach for Fault Location of Transmission Lines Using Electro-Optic Field Sensors
- 23 September 2021
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Electromagnetic Compatibility
- Vol. 63 (6) , 2151-2158
Abstract
Locating faults in transmission lines is important for the safety and continuous operation of power systems. The existing fault location methods based on traveling waves mostly use current transformers to obtain the transient signals, which requires a direct connection with the live lines and therefore brings inconvenience to the installation, debugging, and maintenance. In this article, we propose a flexible noncontact approach for locating faults in transmission lines based on broadband electro-optic field sensors, where the noncontact fault location system can be easily installed, debugged, and maintained. The approach uses an electric field sensor to directly measure the quasi-static electric field generated by the faults, and then the associated time difference of arrival of the transients at two ends of a transmission line can be obtained. The approach is validated and tested by experiments both in laboratory and real 500 kV transmission lines. The artificial fault experiment shows a location error of approximately 200 m on a 177-km- long 500 kV power transmission line.Keywords
Funding Information
- National Natural Science Foundation of China (52022044, 51921005)
This publication has 23 references indexed in Scilit:
- Dual LiNbO3 Crystal-Based Batteryless and Contactless Optical Transient Overvoltage Sensor for Overhead Transmission Line and Substation ApplicationsIEEE Transactions on Industrial Electronics, 2017
- Assessment of the Influence of Losses on the Performance of the Electromagnetic Time Reversal Fault Location MethodIEEE Transactions on Power Delivery, 2016
- Non-contact measurement of lightning and switching transient overvoltage based on capacitive coupling and pockels effectsElectric Power Systems Research, 2016
- Application of an analysis technique to characterise impulse response of grounding systems2016
- Traveling-Wave-Based Fault-Location Algorithm for Hybrid Multiterminal CircuitsIEEE Transactions on Power Delivery, 2016
- Fault location method applied to transmission lines of general configurationInternational Journal of Electrical Power & Energy Systems, 2015
- Development and Application of Integrated Optical Sensors for Intense E-Field MeasurementSensors, 2012
- Fault Location for Single-Circuit Line Based on Bus-Impedance Matrix Utilizing Voltage MeasurementsIEEE Transactions on Power Delivery, 2008
- Noncontact Probes for Wire FaultLocation With ReflectometryIEEE Sensors Journal, 2006
- Fault location using waveletsIEEE Transactions on Power Delivery, 1998