Abstract
The grounding of low frequency distribution transformer is a critical concern which ensures the proper operation and protection of the distribution system. The power electronic transformer (PET), as a future alternative of low frequency distribution transformer, also needs to consider the grounding. This paper is studying the operation of PET with arc suppression coil(ASC) grounding in the Y-connected medium-voltage(MV) stage. The study focus on two aspects: 1. The MV stage current stress brought by ASC is analyzed and a negative sequence current compensation method is proposed to reduce the MV stage current stress; 2. The ASC impedance adjustment range that MV stage can provide is analyzed and a virtual impedance method is proposed to achieve this adjustment. The effectiveness of the proposed ASC-PET as well as its control strategy is verified by both simulation and experiment results.Keywords
Funding Information
- State Key Laboratory of Electrical Insulation and Power Equipment (EIPE14112)
This publication has 19 references indexed in Scilit:
- Theoretical Comparison in Energy-Balancing Capability Between Star- and Delta-Configured Modular Multilevel Cascade Inverters for Utility-Scale Photovoltaic SystemsIEEE Transactions on Power Electronics, 2015
- Cascaded multilevel SST medium voltage converter for solar applications2015
- Solid-State Transformer and MV Grid Tie Applications Enabled by 15 kV SiC IGBTs and 10 kV SiC MOSFETs Based Multilevel ConvertersIEEE Transactions on Industry Applications, 2015
- Reactive Power Compensation and Optimization Strategy for Grid-Interactive Cascaded Photovoltaic SystemsIEEE Transactions on Power Electronics, 2014
- Analysis of Temporary Overvoltages During Open-Phase Faults in Distribution Networks With Resonant GroundingIEEE Transactions on Power Delivery, 2014
- A three-phase 10 kVAC-750 VDC power electronic transformer for smart distribution grid2013
- A Modular multilevel converter-based power electronic transformer2013
- Improvement in the continuity of supply due to a large introduction of Petersen coils in HV/MV substations2005
- Improving UK power quality with arc suppression coils2001
- Prony's method: an efficient tool for the analysis of earth fault currents in Petersen-coil-protected networksIEEE Transactions on Power Delivery, 1995