Advanced DC zonal marine power system protection
Open Access
- 1 February 2014
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 8 (2) , 301-309
Abstract
A new active impedance estimation based protection strategy which is suitable for utilisation in a DC zonal marine power distribution system is presented. This method uses two triangular current ‘spikes’ injections for system impedance estimation and protection when faults are detected. By comparing the estimated impedance with the pre‐calibrated value, the fault location can be predicted and fault can be isolated without requiring communication between two injection units. Using co‐ordinated double injections and line current measurement (directional fault detection), faults in the system with same impedance and different fault positions can be distinguished, located and isolated. The proposed method is validated using experimental test results derived from a 30 kW, 400 V, twin bus DC marine power system demonstrator. The experimental tests were applied to both faults during normal operation and faults that occur during system restoration.Keywords
This publication has 14 references indexed in Scilit:
- The impact of incorporating skin effect on the fault analysis and protection system performance of DC marine and aerospace power systems2010
- Mitigation against overvoltages on a DC marine electrical system2009
- Power electronics and future marine electrical systemsIEEE Transactions on Industry Applications, 2006
- System reconfiguration on shipboard DC zonal electrical system2005
- Impedance Measurement for Improved Power Quality—Part 1: The Measurement TechniqueIEEE Transactions on Power Delivery, 2004
- Impedance Measurement for Improved Power Quality—Part 2: A New Technique for Stand-Alone Active Shunt Filter ControlIEEE Transactions on Power Delivery, 2004
- Protection of modern marine power systems: challenges and solutions2004
- Single ended travelling wave fault location scheme based on wavelet analysis2004
- Validation of a novel unit protection scheme based on superimposed fault currents2001
- Selection and stability issues associated with a navy shipboard DC zonal electric distribution systemIEEE Transactions on Power Delivery, 2000