Vacuum arc behavior and its voltage characteristics in drawing process controlled by composite magnetic fields along axial and transverse directions
Authors:
- 1 October 2015
- journal article
- conference paper
- Published by AIP Publishing in Physics of Plasmas
- Vol. 22 (10) , 103512
Abstract
In this research, drawing vacuum arc (VA) experiments were conducted using composite contacts under currents ranging from 5 kA to 20 kA root mean square (rms). The new type of contact comprised an axial magnetic field (AMF) configuration and a transverse magnetic field (TMF) configuration. The TMF plate was in the center, surrounded by the AMF plate. The contact generated both AMFs and TMFs simultaneously. VA appearances and arc voltages were recorded, and the VA was modeled as a conductor for electromagnetic force analysis in ANSYS software. The results showed that the coaxiality of operating mechanisms significantly influenced arc behavior just as the arc was ignited. When arc brightness did not increase after ignition, there was a voltage drop accompanied with diffusion of the VA. As to VA development, when an arc was ignited on an AMF plate, it spread on the plate and rotated. Over time the arc current increased, the constricting arc forms, and the arc column rotated on the TMF plate under the action of Ampere's force. With regard to the influence of a magnetic field on a VA at different stages, in the initial drawing arc stage the TMF was dominant, and the arc started to rotate under the action of Ampere's force. Afterwards, the AMF was dominant, with a steadily burning arc. As for contact melting, in the initial arcing period, a contracted short arc caused severe melting and erosion of the contact plate. When the ignition spot or root was close to the slot of plate, the electromagnetic force pushed the arc toward slot and contact edge, resulting in local erosion of the slot region.Keywords
Funding Information
- State Key Laboratory of Electrical Insulation and Power Equipment Fund (EIPE14130)
- National Natural Science Foundation of China (50907045, 51325705, 51221005)
This publication has 19 references indexed in Scilit:
- 3D Numerical simulation of high current vacuum arc in realistic magnetic fields considering anode evaporationJournal of Applied Physics, 2015
- Theoretical and Experimental Investigation of New Innovative TMF–AMF Contacts for High-Current Vacuum Arc InterruptionIEEE Transactions on Plasma Science, 2013
- Three-Dimensional Time-Dependent Model and Simulation of High-Current Vacuum Arc in Commercial Axial Magnetic Fields Vacuum InterruptersIEEE Transactions on Plasma Science, 2013
- Three-dimensional model and simulation of vacuum arcs under axial magnetic fieldsPhysics of Plasmas, 2012
- Numerical simulation of high-current vacuum arc characteristics under combined action of axial magnetic field and external magnetic field from bus barPhysics of Plasmas, 2009
- High-current vacuum arc under axial magnetic field: Numerical simulation and comparisons with experimentsJournal of Applied Physics, 2006
- Numerical simulation of vacuum arc under different axial magnetic fieldsJournal of Physics D: Applied Physics, 2005
- Motion of high-current vacuum arcs on spiral-type contactsIEEE Transactions on Plasma Science, 1989
- The Vacuum Interrupter ContactIEEE Transactions on Components, Hybrids, and Manufacturing Technology, 1984
- Magnetic constriction effects in high-current vacuum arcs prior to the release of anode vaporJournal of Applied Physics, 1977