Abstract
Offshore flexible low-frequency AC transmission (OFLFAC) systems face unique protection challenges due to full-power electronic interfaces and 20 Hz operation modes. To address these challenges, a novel non-unit transient protection method is proposed, utilizing the boundary characteristics of modular multilevel matrix converters (M3C). First, the parameters of three-core submarine cables are decoupled and modal decomposition is applied to analyze the strong attenuation characteristics of high-frequency waves at substation buses and M3C converter boundaries. Next, a noise-immune successive variational mode decomposition algorithm combined with mathematical morphology filtering is designed to separate low-frequency traveling waves from high-frequency transients. A hybrid criterion is proposed: the average slope ratio of low-frequency forward and backward traveling waves identifies the fault direction, while the inner product ratio of high-frequency peak operators distinguishes high-impedance internal faults from external low-impedance faults. Simulation results show that the proposed method can operate reliably within 2.4 ms, withstand transition resistances up to 1000 $\Omega$ and low signal-to-noise ratio environments of 10 dB, and remain unaffected by control strategies, thereby effectively addressing the reliability shortcomings of single-ended protection in complex fault scenarios.
Funding Information
  • National Natural Science Foundation of China (52377070)

This publication has 16 references indexed in Scilit: