Reduced Order Thermal Modeling of Data Centers via Distributed Sensor Data
- 13 February 2012
- journal article
- Published by Wiley in Journal of Heat Transfer
- Vol. 134 (4) , 041401
Abstract
In this paper, an effective and computationally efficient proper orthogonal decomposition (POD) based reduced order modeling approach is presented, which utilizes selected sets of observed thermal sensor data inside the data centers to help predict the data center temperature field as a function of the air flow rates of computer room air conditioning (CRAC) units. The approach is demonstrated through application to an operational data center of 102.2 m2 (1100 square feet) with a hot and cold aisle arrangement of racks cooled by one CRAC unit. While the thermal data throughout the facility can be collected in about 30 min using a 3D temperature mapping tool, the POD method is able to generate temperature field throughout the data center in less than 2 s on a high end desktop personal computer (PC). Comparing the obtained POD temperature fields with the experimentally measured data for two different values of CRAC flow rates shows that the method can predict the temperature field with the average error of 0.68 °C or 3.2%. The maximum local error is around 8 °C, but the total number of points where the local error is larger than 1 °C, is only ∼6% of the total domain points.Keywords
This publication has 25 references indexed in Scilit:
- Numerical Modeling of Perforated Tile Flow Distribution in a Raised-Floor Data CenterJournal of Electronic Packaging, 2010
- Proper Orthogonal Decomposition for Reduced Order Thermal Modeling of Air Cooled Data CentersJournal of Heat Transfer, 2010
- Multi-parameter model reduction in multi-scale convective systemsInternational Journal of Heat and Mass Transfer, 2010
- The Thermal Design of a Next Generation Data Center: A Conceptual ExpositionJournal of Electronic Packaging, 2008
- Reduced-order modeling of turbulent forced convection with parametric conditionsInternational Journal of Heat and Mass Transfer, 2007
- Use of Computational Fluid Dynamics for Calculating Flow Rates Through Perforated Tiles in Raised-Floor Data CentersHVAC&R Research, 2003
- A methodology for the design of perforated tiles in raised floor data centers using computational flow analysisIEEE Transactions on Components and Packaging Technologies, 2001
- Extensions to Karhunen-Loève based approximation of complicated phenomenaComputer Methods in Applied Mechanics and Engineering, 1998
- A numerical study of droplet-vortex interactions in an evaporating sprayInternational Journal of Heat and Mass Transfer, 1996
- The use of the Karhunen-Loève decomposition for the modeling of distributed parameter systemsChemical Engineering Science, 1996