The vigorous development of renewable energy has induced multiple sources connected to regional distribution networks. However, the high impedance ground fault that appeared in the distribution network can induce an intermittent arc accompanied by extinction and reignition, which may damage renewable energy generation devices severely. Therefore, the detection of arcing faults is profoundly necessary for practice, but the high impedance arcing fault is easily confused with switches of motor or capacitor bank. In order to solve high impedance arcing fault detection, this paper proposes a high impedance arcing fault detection method that combines complete ensemble empirical mode decomposition with adaptive noise (CEEMDAN) and Teager energy operator (TEO). Firstly, CEEMDAN algorithm is used to extract the intrinsic mode function (IMF) of transient zero‐sequence current (TZSC). According to the correlation coefficient and waveform similarity, which can select maximum correlation coefficient value as the characteristic component of TZSC; Then, TEO is utilized to track the change of signal in real‐time, meanwhile, wavelet singular entropy (WSE) is applied to calculate the characteristic component of TZSC. In particular, high impedance arcing fault (HIAF), motor switching (MS), and capacitor bank switching (CBS) can be effectively identified by comparing WSE. The effectiveness of CEEMDAN‐TEO detection method is verified by simulation, which owns advantages in extraction accuracy, calculation efficiency, and detection accuracy of feature components.Keywords
Funding Information
- National Natural Science Foundation of China (51667010, 51807085)
This publication has 27 references indexed in Scilit:
- Real time evaluation of DWT-based high impedance fault detection in EHV transmissionElectric Power Systems Research, 2010
- Approaches in High Impedance Fault Detection - A Chronological ReviewAdvances in Electrical and Computer Engineering, 2010
- Feature reduction using a singular value decomposition for the iterative guided spectral class rejection hybrid classifierISPRS Journal of Photogrammetry and Remote Sensing, 2009
- High impedance fault detection in power distribution networks using time–frequency transform and probabilistic neural networkIET Generation, Transmission & Distribution, 2008
- A hybrid ECG compression algorithm based on singular value decomposition and discrete wavelet transformJournal of Medical Engineering & Technology, 2007
- High-Impedance Fault Detection in Distribution Networks With Use of Wavelet-Based AlgorithmIEEE Transactions on Power Delivery, 2006
- Reduction of large frequency response function data sets using a robust singular value decompositionComputers & Structures, 2006
- High Impedance Fault Detection Based on Wavelet Transform and Statistical Pattern RecognitionIEEE Transactions on Power Delivery, 2005
- Novel Methods for High-Impedance Ground-Fault Protection in Low-Voltage Supply SystemsElectric Power Components and Systems, 2003
- High impedance fault arcing on sandy soil in 15 kV distribution feeders: contributions to the evaluation of the low frequency spectrumIEEE Transactions on Power Delivery, 1990