This study analyses the performance of an integrated transcritical CO2 (R-744) refrigeration system operating in winter conditions within a supermarket in Trento, north Italy. This system fulfils multiple functions, providing the heating (for domestic hot water and space heating), cooling, and freezing capabilities for the supermarket. Energy analysis reveals that the average value of the total coefficient of performance, total COP, over the entire study period is calculated at 2.47. Notably, the medium-temperature (MT) compressor rack exhibits the highest power consumption, especially in sub −5 °C conditions. The auxiliary (AUX) compressor rack and the gas cooler (GC) fan contribute significantly to the electrical power usage. The air conditioning (AC) heating load is consistently high, averaging 41.6 kW, while the domestic hot water (DHW) heating load remains stable at approximately 5 kW. The refrigeration demands include an average MT cooling load of 25.86 kW and a low-temperature (LT) freezing load of 10–15 kW, with an average of 13.76 kW. The current study also delves into exergy analysis, disclosing an overall system exergy efficiency of 22.4%. The AUX compressor rack is identified as the primary exergy destructor, followed by the GC, AC coils, MT compressor rack, and the ejector. The LT compressor rack has the highest exergy efficiency, followed by the MT and LT expansion valves.Keywords
Funding Information
- European Union’s Horizon 2020 Research and Innovation Program (723137)
This publication has 23 references indexed in Scilit:
- Advanced exergy analysis of a CO2 two-phase ejectorApplied Thermal Engineering, 2022
- Conventional and advanced exergy analyses of transcritical CO2 ejector refrigeration system equipped with thermoelectric subcoolerEnergy Reports, 2021
- Experimental investigation on the influence of internal heat exchanger in a transcritical CO2 heat pump water heaterApplied Thermal Engineering, 2020
- Advanced exergy analysis of a carbon dioxide ammonia cascade refrigeration systemApplied Thermal Engineering, 2018
- Experimental investigation of a CO2 trans-critical cycle with IHX for chiller application and its energetic and exergetic evaluation in warm climateApplied Thermal Engineering, 2018
- Advanced exergy analyses of an ejector expansion transcritical CO2 refrigeration systemEnergy Conversion and Management, 2016
- Conventional and advanced exergy analysis of an ejector refrigeration systemApplied Energy, 2015
- Theoretical study on a novel dual-nozzle ejector enhanced refrigeration cycle for household refrigerator-freezersEnergy Conversion and Management, 2013
- Thermodynamic analysis of transcritical CO2 refrigeration cycle with an ejectorApplied Thermal Engineering, 2011
- Exergy analysis, parametric analysis and optimization for a novel combined power and ejector refrigeration cycleApplied Thermal Engineering, 2009