Detection of the High Impedance Fault (HIF) has been a problem of research for decades due to its randomness and inability to cause a sufficient disturbance. In the present work, Data Mining and Ensembled Machine Learning (EML) are used in conjunction to detect HIF in the distribution network. The search for the HIFs in space of electrical parameters is curtailed using K-means clustering for the data mining algorithm. EML consisting of a Support Vector Machine (SVM) and Decision Tree (DT) is hence deployed to detect HIF. The data-driven algorithm is adaptive and hence improves detection accuracy in earlier stages of HIF evolution over time. The article also describes tuning strategies of EML algorithms with the objective of minimizing false HIF detection. The offline synthetic data for EML is generated from MATLAB Simulink. Power distribution line parameters are considered for the data generation.