Determination of the scope of the experimental-calculation method for measuring the touch voltage
Open Access
- 4 January 2023
- journal article
- research article
- Published by National Technical University Kharkiv Polytechnic Institute in Electrical Engineering & Electromechanics
- No. 1,p. 77-82
Abstract
The work is devoted to the improvement of methods for determining the normalized parameters of the grounding system (GS) of operating power stations and substations. The aim of the work is determination of the scope of the experimental-calculated method for measuring the touch voltage, depending on short-circuit (SC) current value for the given dimensions of the GS and the type of soil. Methodology. The study analyzed the non-linear effect of the SC current value on the touch voltage, taking into account such factors as the GS size and the soil type. The calculation used statistical data on the GS size and the characteristics of the soil obtained by monitoring the GS state of 585 operating electrical substations with a voltage class of 110-750 kV using the induction method and the method of vertical soil sounding, respectively. For the calculation, a mathematical model of a non-equipotential GS located in a three-layer semiconductor space with plane-parallel boundaries was used, this model was developed using the method of integro-differential equations. Results. To determine the scope of the method, in this work it is proposed to use the linearity criterion, which is determined due to the ratio of the constant of reduced touch voltage to the current value. The example shows the method for determining the threshold minimum and maximum values of the measuring current of the soil, in the range between which the measurements by experimental-calculated methods are impossible. A table of threshold current values has been formed and recommendations have been developed on the possibility of using experimental-measuring methods for determining the touch voltage depending on the GS size and soil characteristics.Keywords
This publication has 12 references indexed in Scilit:
- THE FACTORS OF THE INFLUENCE ON THE TOUCH VOLTAGE FROM THE REVIEW OF THE DEVELOPMENT OF RECOMMENDATIONS FOR THE RECONSTRUCTION OF THE GROUNDING DEVICETekhnichna Elektrodynamika, 2019
- ANALYSIS OF METHODS FOR MONITORING OF EXISTING ENERGY OBJECTS GROUNDING DEVICES STATE AT THE PRESENT STAGEElectrical Engineering & Electromechanics, 2019
- DETERMINATION THE ELECTRICAL POTENTIAL OF A CREATED GROUNDING DEVICE IN A THREE-LAYER GROUNDTekhnichna Elektrodynamika, 2018
- EXPERIMENTAL SUBSTANTIATION OF THE CALCULATION PROCEDURE OF NORMALIZED PARAMETERS OF GROUNDING DEVICE BASED ON THE THREE-LAYER SOIL MODELElectrical Engineering & Electromechanics, 2018
- An alternative approach for touch and step voltages measurement in high-voltage substationsElectric Power Systems Research, 2016
- ANALYSIS OF ELECTROPHYSICAL CHARACTERISTICS OF GROUNDS IN THE VICINITY ELECTRICAL SUBSTATION OF UKRAINEElectrical Engineering & Electromechanics, 2015
- IEEE Guide for Safety in AC Substation Grounding2015
- Simulation of electric fields in the presence of rods with rounded upper endsTechnical Physics, 2015
- IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Grounding System2012
- Parameters Estimation of a Horizontal Multilayer Soil Using Genetic AlgorithmIEEE Transactions on Power Delivery, 2010